Standard Range Zone Pressure Multi-Sensor (ZPM)

 

Installation and Operation

 

Specifications subject to change without notice.

 

1 of 5

 

Catalog No. 11-808-711-01 

 

 

 

 

 

#38592 

– 

1/10/19 

Overview 

 

The Zone Pressure Multi-Sensor 
(Part #NSB-ZPM-SR-ST-D) is the 
most flexible pressure sensor on 
the market. Output, range, units, 
directionality, and response time 
are quickly set in the field with no 
tools, no power, and no small 
components.

 

The LCD display helps with 
troubleshooting because it displays 
the actual differential pressure

 

over the entire operational range 
regardless of which pressure 
range is selected for output to the 
system controller. Three LEDs on 
the face of the unit indicate when 

the pressure is “Out of Range 

Low”, “In Range”, or “Out of 

Range High”.

 

Bulkhead fitting 

for static tube

 

 
 
 
 
 
 

 

Mounting 

screws

 

 

Deadhead 

tubing

 

Static 
tube 
screws

 

Cover latch 

screw

 

Conduit 

foam plug

 

 
 
 
 
 
 

Static tube 

and hose 

with surge 

damper 

 

 

Specifications 

 

Power:

 

7 to 40 VDC for 4 to 20 mA Output

 

7 to 40 VDC or 18 to 32 VAC for 0 to 5 or 1 to 5 V Output

 

13 to 40 VDC or 18 to 32 VAC for 0 to 10 or 2 to 10 V Output

 

Power Consumption: 

20 mA max, DC only at 4 to 20 mA Output 
4.9 mA max DC at 0 to 5 VDC or 0 to 10 VDC Output 
0.12 VA max AC at 0 to 5 VDC or 0 to 10 VDC Output 

Load Resistance: 

4 to 20 mA Output 

850 Ω Maximum @ 24 VDC 

0 to 5 V or 0 to 10 V output 6K to 10KΩ minimum 

Accuracy for Standard Pressure Ranges at 72°F:   

±0.25% of range 

Stability:  

±0.25% F.S. per year 

 

 

 

 

 

      

 

Port Size:  

1/4” tubing (1/8” to 3/16” I.D.) 

Environmental Operating Range:  

-

4 to 140°F (-20 to 60°C)   

 

 

 

 

Storage Temperature:  

-40 to 203°F (-40 to 95°C) 

Temperature Error Standard Range:  

 

 

 

 

 

Figure 2:  ZPM Dimensions 

0.01% FS/°F (0.02% FS/°C) 

(±1.0” W.C @-4 to 140ᵒF (-20 to 60°C) 

Overpressure: 

Proof:  300.1 WC (10.83 PSI) 
Burst:  512.6 WC (18.5 PSI) 

Wiring: 

2 wires (4 to 20mA Current loop)* 
3 wires (AC or DC powered, Voltage out)* 

Humidity:  

0 to 95% RH, non-condensing 

Port Size:  

1/4” tubing (1/8” to 3/16” I.D.) 

Encl. Material:  

UV-resistant Polycarb., UL94, V-0 

Enclosure Rating:  

IP44, NEMA 2

 

 

 
 

 
 

Figure 1: 

ZPM unit and

 

associated parts

 

Selectable Standard Ranges

 

Inches WC 

Pascals

 

0 to 1.00.............................. 0 to  250

 

0 to 2.00.............................. 0 to  300

 

0 to 2.50.............................. 0 to  500

 

0 to 3.00........................... 0 to  1,000

 

0 to 5.00........................... 0 to  1,250

 

-1.00 to 1.00 .................. -250 to  250

 

-2.00 to 2.00 .................. -300 to  300

 

-2.50 to 2.50 .................. -500 to  500

 

-3.00 to 3.00 ............ -1,000 to  1,000

 

-5.00 to 5.00 ............ -1,250 to  1,250

 

Summary of Contents for NSB-ZPM-SR-ST-D

Page 1: ...o 32 VAC for 0 to 10 or 2 to 10 V Output Power Consumption 20 mA max DC only at 4 to 20 mA Output 4 9 mA max DC at 0 to 5 VDC or 0 to 10 VDC Output 0 12 VA max AC at 0 to 5 VDC or 0 to 10 VDC Output Load Resistance 4 to 20 mA Output 850 Ω Maximum 24 VDC 0 to 5 V or 0 to 10 V output 6K to 10KΩ minimum Accuracy for Standard Pressure Ranges at 72 F 0 25 of range Stability 0 25 F S per year Port Size ...

Page 2: ... and 0 to 5 Unidirectional 4 Choose UNITS Inches WC or PASCALS 5 Choose RESPONSE TIME Fast Response 1 2 second Slow Response 4 seconds 38592 1 10 19 Switch Setup Outputs Ranges Units Response Do not have power applied to unit when changing settings After changing settings apply power and Auto Zero the unit in its orientation of operation Figure 2 Setup Switches for Standard Range Units 1 Select OU...

Page 3: ...entation is with the pressure ports facing down Remove the deadhead tubing and push the system tubing onto the port nipple without creating any kinks or holes Figure 3 ZPM Mounting A locking screw can be inserted into the hole in the cover latch to prevent unintentional cover openings Figure 4 Cover Latch Screw Center hole is only needed for the Attached Tube AT version of the ZPM unit Figure 5 Mo...

Page 4: ...lied and voltage output is selected When 4 to 20 mA output is selected the light is on for 2 seconds at power up then goes off LED Blinking Fast Auto Zero or Error Mode LED Blinking Slow The pressure measurement is above or below the selected pressure range Note When the reading is above or below the selected pressure range the LCD on the face of the unit will alternate between showing the actual ...

Page 5: ...e is to form a drip loop in the tubing to prevent condensation from reaching the ZPM Troubleshooting POSSIBLE PROBLEMS LED does not light LED is blinking fast 1 2 second on 1 2 second off Display is alternating between a number and err Output stuck high or low Output not tracking pressure properly POSSIBLE SOLUTIONS Check power connections for proper power The unit may be performing an auto zero W...