background image

Catalog No. 11-808-639-01

 

7 of 8 

Specifications subject to change without notice.

 

Water Leak Detector 

Installation and Troubleshooting

 

#26268 

– 02

/28/2020 

Set Up and Commissioning 

Indication/Controls 

Description

 

Red LED  

LED illuminates when water is detected

 

Green LED  

LED illuminates when normal power is applied

 

Reset Button 

Resets latching alarm contact (only if water is no longer present) 

Latching Relay 

Left side of J1 set to top two pins listed as “L”

 

Non-Latching Relay 

Left side of J1 set to bottom two pins listed as “N” (Default) 

Supervised Relay***  

Right side of J1 set to top two pins listed as “S” (Default) 

Unsupervised Relay 

Right side of J1 set to bottom two pins listed as “U”

 

*** Supervised means the relay is energized when not in alarm and the relay de-energizes on a power failure or alarm.

 

1.

After the unit is installed and wired, turn on the power. (24VAC +/- 10%)

2.

Check that the green LED is on. If it is not on, check the power source.

3.

Dampen a cloth or sponge and touch both the sensor probe tip and the sensor base. An alarm should occur
within 5 seconds.

4.

The red LED should illuminate and the relay(s) should de-energize, or energize if set up as unsupervised. (To
check relay status, measure the resistance at the relay contacts or monitor the status from the BAS screen.)

5.

Remove the dampened rag or sponge to clear the alarm. If the unit is set up for a non-latching relay (J1 jumper
across the “N” pins), the red LED and relay(s) will energize, or de-energize if set up as an unsupervised relay. If the
unit is set up for a latching relay (J1 jumper across the “L” pins), the operator must push the reset switch on the
detector board or interrupt power to clear the alarm.

6.

Check the depth of the sensor probe screw (see 

Mounting) to be sure it’s at the appropriate water depth for alarm.

Operation Sequence 

When power is applied, the green LED will illuminate and the unit will start to detect for water at the sensor probe. When 
there is no detection of water (normal condition), the relays are not in an alarm state and the red LED remains off. For 
units set up in the unsupervised relay mode, the relays are de-energized. For units set up in the supervised relay mode 
(default), the relays will be energized. (

NOTE

  When there is a loss of power, a supervised relay will drop out indicating 

a water detection alarm.)

 

Within 5 seconds of water detection, the relays go into an alarm state and the red LED illuminates. For units set up 
in the unsupervised relay mode, the relays are energized. For units set up in the supervised relay mode (default), the 
relays are de-energized.

 

If the unit is in non-latching or auto-reset (default) operation, then the alarm state will automatically reset when the water 
has dried up. If the unit is in latching or manual-reset operation, then the unit will stay in an alarm state until the reset 
button is pressed or power is cycled. If there is still water detected during a reset button push, the unit will not reset. If 
there is still water detected after a power interrupt, the unit will initiate another alarm within 5 seconds. 

Diagnostics 

Possible Problem 

Possible Solution

 

Green LED not on 

Check for proper power to the unit (see Power spec on page 6).

 

Red LED not working 

1. Check for proper power to the unit (see Power spec on page 6). or relay

not energizing 

2. Check if water is touching the sensor probe and reference probe.

3.

Adjust sensor probe depth.

4.

For rope sensor units, check the sensitivity adjustment as described on page 4.

Unit will not reset 

1. Check for the presence of water or debris touching the two sensor probes.

2.

Be sure the sensor wires are not shorted.

3.

I

f the L pins on J1 are shorted, push the reset button or cycle power.

4.

For rope sensor units, check the sensitivity adjustment as described on page 4.

Summary of Contents for NSB-LDT4-PS-BB

Page 1: ...nsmitter can be set for latching alarm or non latching alarm with normally energized or de energized operation An optional remote water sensor is available for small inaccessible locations such as AHU pans or under floor water detection Figure 2 Water Leak Detector above with Remote Spot Sensor right and 10 ft FEP cable Part NSB LDT4 RS10 BB Water Leak Detector above with Water Rope Sensor below P...

Page 2: ...notice Water Leak Detector Installation and Troubleshooting 26268 02 28 2020 Figure 3 Water Leak Detector with Built in Sensor and a 5 Amp Relay in a System Diagram Side View Figure 4 Water Leak Detector with Remote Spot Sensor and a 5 Amp Relay in a System Diagram Side View ...

Page 3: ...tching local push button or power interrupt Sensor Reaction Responds to presence of water within 5 seconds Termination Terminal strip 4 10 terminals 12 24 AWG Agency RoHS UL94V 0 UV rated in Enclosure Set Up BB Sensor Adjustable depth from 063 to 84 1 16th default Remote Sensor Adjustable depth from 063 to 84 1 16th default Latching Latching version Stays Jumper energized after water has dried up ...

Page 4: ...sor down firmly Mount the detector enclosure in a visible location within cable length of the remote water sensor Alternatively a remote water sensor can be attached to the floor with screws Figure 8 Mount the detector enclosure in a more visible location within cable length of the remote water sensor Alternatively a rope water sensor can be laid on the floor or under pipes as shown in Figures 10 ...

Page 5: ... Pipe Sensor Mounting Figure 12 Vertical Pipe Sensor Mounting The following combinations of sensors can be used 1 Two rope sensors with a combined length of no more than 100 2 Two spot sensors with a combined length of no more than 75 3 One spot sensor with a maximum length of 25 and one rope sensor of no more than 50 Note Shielded or twisted pair wire cannot be used to extend the sensor wires Thi...

Page 6: ...M1 Alarm Contact 1 Common NO1 Alarm Contact 1 Normally Open to C1 when De energized GND NEU Power supply ground neutral V HOT Power supply input 24VAC 10 Not used for low current relay version SPST Form A Sensitivity Adjustment for 10 Remote Rope Sensor The unit s leak detection sensitivity is set at the Sensitivity Adjustment Potentiometer factory However for the remote rope sensors the sensitivi...

Page 7: ...th for alarm Operation Sequence When power is applied the green LED will illuminate and the unit will start to detect for water at the sensor probe When there is no detection of water normal condition the relays are not in an alarm state and the red LED remains off For units set up in the unsupervised relay mode the relays are de energized For units set up in the supervised relay mode default the ...

Page 8: ... no dirt or debris collected around the probes Dirt or debris around the probes may cause nuisance alarms in moist situations Change the service intervals depending on environmental conditions In very clean conditions the probe may never need maintenance Rope sensor may be wiped down with isopropyl alcohol warm soapy water on a cotton cloth or placed in a dishwasher Caution This unit is not intend...

Reviews: