Water Leak Detector
Installation and Troubleshooting
#26268
– 02
/28/2020
Rope Sensor Mounting
Figure 11:
Sub-floor Sensor Mounting
Figure 10:
Hot Water Tank Pan Mounting
Figure 13:
Horizontal Pipe Sensor Mounting
Figure 12:
Vertical Pipe Sensor Mounting
The following combinations of sensors can be used:
1. Two rope sensors with a combined length of no
more than
100’.
2. Two spot sensors with a combined length of no
more than
75’.
3. One spot sensor with a maximum length of
25’ and one rope sensor of no more than 50’.
Note: Shielded or twisted pair wire cannot be
used to extend the sensor wires. This applies
to both the remote spot sensor as well as the
rope sensor.