background image

Asense CO2 Duct Sensor

 

Installation and Operation

 

 

 

#NSA-ASENSE-D-LCD-REL, NSA-ASENSE-D-REL 

– 11/14/2019 

 
 

Specifications subject to change without notice. 

Catalog No. 11-808-745-01 

Page 

6

 of 

9

 

Dimensions and Holes 

 

Dimensions of sensor in mm and (inches) 

 

 

 

Mounting the sensor to the wall 

Use screws with head diameter less than 7,5 mm (0,295 inches) and head height less than 2,5 mm (0,1 inches) 

 

 

 

 

Summary of Contents for NSA-ASENSE-D-LCD-REL

Page 1: ...ASENSE series Applications Commercial Office Buildings Hospitals Schools Part Numbers NSA ASENSE D LCD REL NSA ASENSE D REL Specifications Supply Voltage 24 VAC VDC 20 50 60 Hz 10 5 to 40 VDC maximum Half wave rectified Power Consumption 1W Wiring Connections 0 00232 in 1 5 mm screw terminals Operating Environment Residential commercial and industrial spaces Operating Temperature 32ºF to 122ºF 0ºC...

Page 2: ... 6555 plastic Flammability Rating UL94V 0 Pipe PC ABS blend Flammability Rating UL94V 0 Product Dimensions H 5 95 151 9 mm x W 3 33 84 6 mm x D 1 85 47 mm Product Weight 0 812 lbs 0 368 kg Agency Approvals EMC Directive 2014 30 EC RoHS Directive 2011 65 EU RoHS 3 Directive 2015 863 EU 1 Accuracy is defined after minimum three 3 ABC periods 1 period 8 days of continuous operations 2 In normal Indoo...

Page 3: ...nge without notice Catalog No 11 808 745 01 Page 3 of 9 Installation 1 Top part 2 Lid 3 Front part 4 Wall plate 5 Screw 6 Label with settings inside the top part Dismounting the sensor Push the front part of the lid upwards while keeping the wallplate steady Fold the front part with the lid forwards and loose it from the hooks 1 ...

Page 4: ...be max 2 5 mm A Put the top tabs of the front part into the top holes of the wall plate B Press the lower edge of the case onto the wall plate to latch The top part is pushed under the locking hooks of the wall plate and secured with a screw Terminals and jumpers on aSENSE RL The darker positions are default settings Terminals and jumpers are located under the top part CAUTION If the PCB must be r...

Page 5: ...mA 2 10 VDC or 4 20 mA Same as Output 1 According to positions of OUT1 and start point jumpers 2 According to positions of OUT2 and start point jumpers 2 3 5 6 7 Normally closed relay Relay COM Normally open relay Contact free relay minimum load 1mA 5V rated load 0 5A 125VAC 1A 24VDC Triggered by register Out 3 8 Not Used 1 The ground terminal is used as negative power supply DC input or AC phase ...

Page 6: ...11 14 2019 Specifications subject to change without notice Catalog No 11 808 745 01 Page 6 of 9 Dimensions and Holes Dimensions of sensor in mm and inches Mounting the sensor to the wall Use screws with head diameter less than 7 5 mm 0 295 inches and head height less than 2 5 mm 0 1 inches ...

Page 7: ...ip 5 2 Plug the programming cable into a USB port and go into Device Manager on the computer to determine which port is being used 3 Open the UIP5 software 4 Power the sensor on and plug the programming cable into the sensor The programming cable must have the black wire with the arrow connected towards the top of the connector on PCB as shown in Figure 1 Figure 1 5 Click the Meter tab at the top ...

Page 8: ...5 01 Page 8 of 9 7 Select Any Address and all interface types 8 Click Connect The unit takes approximately 30 seconds to connect Figure 3 9 You can now adjust your settings ABC can be turned off change ppm change output scale etc 10 After the settings are changed power cycled the sensor Adjusting the trip point on the relay Figure 4 Click SET after adjustment is made ...

Page 9: ...eset flow regulator for disposables 1K PPM Span Gas for Bump Test https www mesagas com disposable calibration gas carbon dioxide co2 1 Click the CO2 tab at the bottom of the page 2 Ensure the target box under Calibration is set to 0 3 Apply the Nitrogen gas to above the CO2 sensor filter On the Asense Carrier recommens removing the PCB from the enclosure for best results Figure 5 4 Wait until the...

Reviews: