background image

 

  EVAPORATOR COMPARTMENT 

SERVICING 

U

   DANGER 

Before servicing unit, disconnect electrical 
service. Failure to disconnect electrical service 
could result in electrical shock and cause 
personal injury or death. 

 

1. 

After disconnecting the unit from the power 

supply, remove the grille retaining screw 
located in the upper-most part of the grille. 
(See Figure 2) 

2. 

Lift the grille up and away from the unit. 

3. 

Unplug the power supply cord located at the 

bottom of the cabinet. (See Figure 3) 

4. 

Remove the 4 philips screws that hold the 

evaporator cover. (See Figure 10) 

5. 

Hold the cover until it is completely loose 

and hanged by the supporting pins. (See 
Figure 11). 

U

   DANGER 

Before servicing unit, disconnect electrical 
service. Failure to disconnect electrical service 
could result in electrical shock and cause 
personal injury or death. 

 

 

FIGURE 10 – RELEASE EVAPORATOR COVER 

 

FIGURE 11 – EVAPORATOR COVER SUPPORT  

  EVACUATION 

Moisture in a refrigeration system may affect 
performance.  

When large amounts of moisture are present, 
system freeze ups will occur. Even in minute 
amounts, moisture will combine with refrigerants 
to form an acid.  

The corrosive action of this acid forms sludge, 
which will plug the lines and drier.  

Since most field type vacuum pumps cannot pull a 
low enough vacuum to remove all moisture from 
the system, it is recommended that the system be 
triple evacuated, breaking each time with dry 
refrigerant nitrogen. Use care to purge air from the 
charging hose when breaking the vacuum. 

  CHARGING REFRIGERATION 

SYSTEM 

Refer to Table 2 for refrigerant type and amount of 
charge. Since capillary tube systems have small 
critical refrigerant charges, it is recommended that 
a field charge either be weighed in or transferred 
from a portable charging cylinder. After maximum 
vacuum has been obtained as detailed above, 
attach charging cylinder to the system line making 
sure to purge air from hose with refrigerant. With 
the unit running, allow refrigerant to run slowly into 
the system until the desired charge is reached. 
When using refrigerant blends it is recommended 
to charge into the high side of the system with the 
initial charge and then add any remaining charge 
into the suction side; however, care must be taken 
to meter the remaining amount into the low side 
so that excess liquid does not enter the 
compressor. 

  TROUBLESHOOTING 

Refer to Table 3 and Figure 12.

 

 

Summary of Contents for Miracool

Page 1: ...cations or designs without notice and without incurring obligations Printed in Mexico 10 06 79BC560010 01_C OWNER S MANUAL MIRACOOL GLASS DOOR MERCHANDISER 2000L Sales Office P O Box 5932 Spartanburg S C 29304 5932 Technical Service 1 800 558 7627 Parts Order Fax 1 800 262 9381 ...

Page 2: ...sories and components including legs casters and shelves File a claim immediately with the shipping company if shipment is damaged or incomplete INSTALLATION LOCATE UNIT Refer to Figure 1 for unit components Units are designed for indoor placement only Provide at least 3 inches of space between unit cabinet and any adjacent wall or fixture Remove skid base by removing the retaining screws 8 hex he...

Page 3: ...3 FIGURE 1 MIRACOOL BOTTLE COOLER UNIT COMPONENTS MC2000H SHOWN ...

Page 4: ... U DANGER Before servicing unit disconnect electrical service Failure to disconnect electrical service could result in electrical shock and cause personal injury or death Swing Doors The door is equipped with gravity assisted cams and will not function properly without proper leveling of cabinet Adjust feet using adjustable wrench so that unit sits approximately level to floor and doors close prop...

Page 5: ... shelf clips Refer to the numbers on the pilaster to ensure that all clips are properly located 2 Insert top tab of the shelf clip into the desired hole of the pilaster The retaining tab should be facing upward as shown in Figure 4 3 Rotate the clip downward and insert the bottom tab into the appropriate hole on the pilaster If necessary squeeze the clip slightly during installation 4 Install all ...

Page 6: ...THOUT SAFETY SHIELD FIGURE 7 CHECK INSTALLATION OF LAMP WITH SHIELD ELECTRICAL SUPPLY AND CONNECTIONS Check to be sure that the electrical service to the unit meets all local and national electrical codes Unit electrical data is shown in the unit data label located on the inside of the cabinet in the upper lefthand corner Review this label before initiating electrical service Voltage range of powe...

Page 7: ...g TEMPERATURE CONTROL The temperature control knob is located inside the cabinet in the motors panel See Figure 8 Unit is factory set at the number 4 position normal which will maintain the product at approximately 38F For colder temperature turn the black adjustment knob to a higher setting Adjust temperature control in small increments one position at a time U CAUTION Allow 24 hours between temp...

Page 8: ...ER Liquid refrigerant control to the evaporator of the system is accomplished by the use of a capillary tube This capillary tube is soldered to the suction line to form a heat exchanger which subcools the liquid refrigerant to maintain high efficiency within the system SERVICE AND TROUBLESHOOTING CONDENSING UNIT SERVICING U DANGER Before servicing unit disconnect electrical service Failure to disc...

Page 9: ...ne with refrigerants to form an acid The corrosive action of this acid forms sludge which will plug the lines and drier Since most field type vacuum pumps cannot pull a low enough vacuum to remove all moisture from the system it is recommended that the system be triple evacuated breaking each time with dry refrigerant nitrogen Use care to purge air from the charging hose when breaking the vacuum C...

Page 10: ... overload protector 6 Compressor too hot return gas hot 6 Check refrigerant charge fix leak if necessary Check airflow across condenser 1 Overload protector 1 Check wiring diagram for correct wiring 2 Cold control 2 Differential set too close 3 Overcharge 3 Reduce refrigerant charge 4 Air in system 4 Recover and recharge Unit runs OK but short cycles 5 Undercharge 5 Fix leak and recharge with refr...

Page 11: ...11 FIGURE 12 WIRING DIAGRAM ...

Page 12: ...t Servicing section on page 8 Vacuum clean front surface of coil thoroughly or direct forced air through condenser fins Failure to clean condenser can cause compressor malfunction and will void warranty CABINET EXTERIOR Cabinets should be cleaned with a solution of mild soap and water or mild household cleaner Do not use caustic soap or abrasive cleaners since these might damage the cabinet finish...

Page 13: ...e Fatty Acids Milkstone where swabbing or rubbing is not practical Easy Off oven cleaner Apply generous coating Allow to stand for 10 to 15 minutes Rinse Repeated application may be necessary Excellent removal Satisfactory for use on all finishes Hard Water Spots and Scale Vinegar Swab or wipe with cloth Rinse with water and dry Satisfactory for use on all finishes Use of brand names is intended o...

Page 14: ...urer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Printed in Mexico 10 06 79BC560010 01_C Copyright 2006 Carrier Corporation ...

Reviews: