26
6.3.1.2.
Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. This can allow one setting to “push” the other to maintain this
difference. When the correct deadband is set, touch
SAVE
.
S
Deadband
: Adjustable from 0 to 6
_
F (0 to 2
_
C)
d
Default = 2
_
F
6.3.1.3.
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch
SAVE
.
S
Outdoor temperature:
Adjustable from --5 to 5
_
F (--3 to 3
_
C)
d
Default = 0
_
F
S
Humidity:
Adjustable from --10 – 10%
d
Default = 0%
6.3.1.4.
Reset factory defaults
This option allows the installer to reset certain factory parameters. After the
selections are made, touch
SAVE
.
S
Program Schedule:
Reset back to pre--programmed time and temperature.
S
User Settings:
Reset user settings back to pre--programmed values.
S
Install Settings:
Reset installation settings back to pre--programmed values.
S
Last 10 Faults:
Reset the last 10 system faults under the Service menu.
6.3.1.5.
Scheduling Enable
This option lets the installer allow programming features. After the selection is
made, touch
SAVE
.
S
Scheduling:
On or Off
Summary of Contents for Infinity SYSTXCCITN01