background image

PTCS Heat Pump Thermostat Support Sheet 

 

 

Manufacturer

: Carrier Infinity Touch Control 

Thermostat Models: 

SYSTXCCITW01-A, SYSTXCCINTN01-A, SYSTXCCITC01-A, SYSTXCCITC01-B 

The Carrier Infinity Touch is a communicating thermostat compatible with Carrier units only 

 

Page 

2

 of 

2

 

 

5.  Access Test Mode for testing system at full capacity 

a.

 

From the Service menu (accessed by pressing and holding the service baseball cap icon) press “Check Out”  

b.

 

Beside “Heat Pump”, select “Heating” or “Cooling” depending on the desired test 

c.

 

On all systems except for the Greenspeed series, select the amount of time you wish to run test and push 

the up arrow to the highest heating or cooling stage available 

d.

 

On the Greenspeed series, select the amount of time you wish to run the test and push the up arrow until it 

reads 100% 

e.

 

Select “Start” 

f.

 

Wait and listen to ensure that the system sounds as if it has ramped up to full fan speed. This may take a 

few minutes depending on the indoor unit characteristics 

g.

 

Wait at least 10 minutes before taking static pressure readings and inserting flow plate for Trueflow plate 

test 

h.

 

Wait at least 20 to 25 minutes before doing temperature split readings for refrigerant test. The longer the 

system is allowed to run, the more likely it will reach a steady state 

6.  Exit Service Menu 

a.

 

To exit the Service menu, press "DONE" in the bottom right hand corner of the screen 

7.  Exit Set-Up Menu 

a.

 

Depending on which Setup menu screen you are on, press "BACK" until you reach the main service menu 

screen 

b.

 

Press "Exit" and you will return to the home screen 

 

Caution: On the first screen when entering installer set-up mode (service menu), always press "Cancel" 

rather than "Save" to avoid changing  original installer settings.

 

 

Resources:

 Carrier Support: 1-800-227-7437 

Sources:

 Installation Manual

http://www.utcccs-cdn.com/hvac/docs/1009/Public/09/SYSTXCCITC-02SI.pdf

 

 

 

 