background image

49

5. Inducer Speed Change — If the cycle starts in medium heat,

the furnace control CPU reduces the inducer speed slightly

after flame sense. If cycle starts in high--heat, the furnace
control CPU increases the inducer speed after flame sense.
The reduction in speed in medium--heat is to optimize

combustion for maximum efficiency.

6. Blower--On delay — If the burner flame is proven the

blower--ON delay for medium--heat and high--heat are as
follows:
Medium--heat — 60 seconds after the gas valve GV--M is

opened the blower motor BLWM is turned ON at low-- or
medium--heat airflow.

High--heat — 35 seconds after the gas valve GV--M is
opened the BLWM is turned ON at high--heat airflow.
Simultaneously, the humidifier terminal HUM and

electronic air cleaner terminal EAC--1 are energized and
remain energized throughout the heating cycle.

7.

Switching from Medium-- to Low--Heat

— If the furnace

control switches from medium--heat to low--heat, the

furnace control will turn the blower ON at low--heat airflow,
energize the HPSR relay to open the NC contact, and slowly
decrease the inducer motor speed. When the HPSR relay is

energized and the NC contact opens the throttling valve TV
is deenergized and the gas flow reduces to low--heat rate.

Switching from Low-- to Medium--Heat

— If the furnace

control CPU switches from low--heat to medium--heat, the
furnace control CPU will de--energize the HPSR relay to

close the NC contact and slowly increase the inducer motor
speed until the medium--heat pressure switch MPS closes.

When the medium--heat pressure switch MPS closes, the
throttling valve solenoid TV is energized and the inducer

motor RPM is noted by the furnace control CPU. The RPM
is used to evaluate vent system resistance. This evaluation is
then used to determine the required RPM necessary to

operate the inducer motor in medium--heat and high--heat
mode. The blower motor BLWM will transition to

medium--heat airflow five seconds after the furnace control
CPU switches from low--heat to medium--heat.

Switching from Low-- to High--Heat

— If the furnace

control CPU switches from low--heat to high--heat, the
furnace control CPU will de--energize the HPSR relay to

close the NC contact and slowly increase the inducer motor
speed until the medium--heat pressure switch MPS closes.
When the medium--heat pressure switch MPS closes, the

throttling valve solenoid TV is energized and the inducer
motor RPM is noted by the furnace control CPU. The RPM

is used to evaluate vent system resistance. This evaluation is
then used to determine the required RPM necessary to

operate the inducer motor in medium-- and high--heat mode.
The blower motor BLWM will transition to high--heat
airflow five seconds after the furnace control CPU switches

from low--heat to high--heat. As the inducer RPM gradually
increases the high--heat pressure switch HPS closes and the

gas valve solenoid GV--HI is energized.

Switching from Medium-- to High--Heat

— If the furnace

control CPU switches from medium--heat to high--heat, the

furnace control CPU will gradually increase the inducer
motor speed to the required high--heat RPM. The blower

motor BLWM will transition to high--heat airflow five
seconds after the furnace control CPU switches from
medium--heat to high heat. As the inducer RPM gradually

increases the high--heat pressure switch HPS closes and the
gas valve solenoid GV--HI is energized.

Switching from High-- to Medium-- or Low--Heat

— The

furnace control CPU will not switch from high--heat to

medium-- or low--heat while the thermostat R to W circuit is
closed when using a single--stage thermostat.

8.

Blower--Off Delay

— When the thermostat is satisfied, the

R to W circuit is opened, de--energizing the gas valve

GV--M, stopping gas flow to the burners, and de--energizing
the throttling valve TV, and humidifier terminal HUM. The

inducer motor IDM will remain energized for a 15--second
post--purge period. The blower motor BLWM and air
cleaner terminal EAC--1 will remain energized at low--heat

airflow or transition to low--heat airflow for 90, 120, 150, or
180 seconds (depending on selection at blower--OFF delay

switches). The furnace control CPU is factory--set for a
120--second blower-- OFF delay.

Two--Stage Thermostat and Two--Stage Low / High

Heating

See Fig. 58 for thermostat connections.

NOTE

: In this mode the low--heat only switch SW1--2 must be

ON to select the low--heat only operation mode in response to
closing the thermostat R to W1 circuit. Closing the thermostat R to
W1--and--W2 circuits always causes high--heat operation,
regardless of the setting of the low--heat only switch.
The furnace will start up in either medium--, or high--heat. The

furnace will operate in low--heat after starting and operating for 1
minute at medium--heat before transitioning to low--heat.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
low--heat or closing the R to W1--and--W2 circuits for high--heat.

The furnace control performs a self--check, and verifies the

low--heat and medium--heat pressure switch contacts LPS and MPS
are open, then de--energizes the HPSR relay to close the NC

contact.
The start up and shut down functions and delays described above

apply to the 2--stage low/high heating mode as well, except for

switching from high-- to low--heat.

1.

Switching from High-- to Low--Heat

— If the thermostat

R to W2 circuit opens, and the R to W1 circuit remains
closed, the furnace control CPU will gradually decrease the
inducer motor speed to the required medium--heat RPM.

When the inducer motor IDM reduces pressure sufficiently,
the high heat pressure switch HPS will open and the

high--heat gas valve solenoid GV--HI will be de--energized.
The gas valve solenoid GV--M will remain energized as
long as the low--heat pressure switch LPS remains closed.

When the inducer motor speed gets within 15% of the
required medium--heat RPM the furnace control CPU will

start a 5 second blower airflow change delay. After the 5
second blower airflow change delay is completed the
blower airflow will transition to low--heat airflow. At this

point the furnace control CPU will energize the HPSR relay
to open the NC contact and slowly decrease the inducer

motor speed to the required low--heat RPM. When the
HPSR relay is energized and the NC contact opens the

throttling valve TV is de--energized and the gas flow
reduces to low--heat rate. When the inducer motor IDM
reduces pressure sufficiently, the medium--heat pressure

switch MPS will open.

Two--Stage Thermostat and Two--Stage Medium/High

Heating

See Fig. 58 for thermostat connections.

NOTE

: In this mode the medium--heat only switch SW4--2 must

be ON to select the medium--heat only operation mode in response
to closing the thermostat R to W1 circuit. Closing the thermostat R
to W1--and--W2 circuits always causes high--heat operation,
regardless of the setting of the medium--heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
medium--heat or closing the R to W1--and--W2 circuits for

high--heat. The furnace control performs a self--check, and verifies

the low--heat and medium--heat pressure switch contacts LPS and
MPS are open, then de--energizes the HPSR relay to close the NC

contact.

58MV

C

Summary of Contents for Infinity ICS 58MVC 100 Series

Page 1: ...rsonnel The authority having jurisdiction gas inspection authority municipal building department fire department etc should be consulted before installation to determine the need to obtain a permit ama REGISTERED ISO 9001 2000 CERTIFIED Consignes spéciales pour l installation de ventillation au Canada L installation faite au Canada doit se conformer aux exigences du code CSA B149 Ce systême de ven...

Page 2: ...haust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observ...

Page 3: ...lure to follow this warning could result in personal injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installer service agency local gas supplier or your distributor or branch for informa...

Page 4: ... Installation Codes and Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result ...

Page 5: ...minimize the corrosive effects of adhesives sealers and other construction materials It also prevents the entrainment of drywall dust into combustion air which can cause fouling and plugging of furnace components S The temperature of the return air to the furnace is maintained between 55_F 13_C and 80_F 27_C with no evening setback or shutdown The use of the furnace while the structure is under co...

Page 6: ...6 335122 201 REV B LIT TOP A08435 Fig 3 Clearances to Combustibles 60 80 27 C 16 C A06745 Fig 4 Return Air Temperature 18 IN 457 2 mm MINIMUM TO BURNERS A93044 Fig 5 Installation in a Garage 58MVC ...

Page 7: ...chusetts S This product must be installed by a licensed plumber or gas fitter S When flexible connectors are used the maximum length shall not exceed 36 inches 914 mm S When lever type gas shutoffs are used they shall be T handle type S The use of copper tubing for gas piping is not approved by the state of Massachusetts Electrical Connections S US National Electrical Code NEC ANSI NFPA 70 2008 S ...

Page 8: ...tubes 1 Collector Box Drain Inducer Housing Drain Relief Port and Pressure Switch Tubes These tubes should be factory attached to condensate trap and pressure switch ready for use in UPFLOW applications These tubes can be identified by their connection location and also by a color label on each tube These tubes are identified as follows collector box drain tube blue label inducer housing drain tub...

Page 9: ...n alternate location for the condensate trap is the left hand side of casing See Fig 2 and 8 NOTE If the alternate left hand side of casing location is used the factory connected drain and relief port tubes must be disconnected and modified for attachment See Condensate Trap Tubing Alternate Upflow Orientation section for tubing attachment To relocate condensate trap to the left hand side perform ...

Page 10: ...ry supplied in loose parts bag c Determine appropriate length then cut and connect tube Condensate Trap Field Drain Attachment Refer to Condensate Drain section for recommendations and procedures PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED INDUCER HOUSING MOLDED DRAIN TUBE VIOLET COLLECTOR BOX TUBE PINK COLLECTOR BOX DRAIN TUBE BLUE COLLECTOR BOX TUBE GREEN CONDENSATE TRAP A07281 Fig 8 Al...

Page 11: ...condensate trap casing holes with plastic filler caps factory supplied in loose parts bag CAP PLUG COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED INDUCER HOUSING MOLDED DRAIN TUBE VIOLET COLLECTOR BOX TUBE PINK COLLECTOR BOX DRAIN TUBE BLUE COLLECTOR BOX TUBE EXTENSION CONDENSATE TRAP COLLECTOR BOX TUBE GREEN COLLECTOR BOX EXTENSION DRAIN TUBE DRAIN TUBE COUPLING A07277 Fig 10 Downflow Tube Configura...

Page 12: ... box pressure tube pink label is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications The tube MUST be disconnected and used or the condensate trap relief port tube The other collector box pressure tube green label which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOW...

Page 13: ...tion and Working Platform for Direct Vent 2 Pipe Application VENT MANUAL SHUTOFF GAS VALVE SEDIMENT TRAP CONDENSATE TRAP DRAIN ACCESS OPENING FOR TRAP 30 IN 762mm MIN WORK AREA A 12 IN 305mm MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT 5 TO 8 FT 1 5 TO 2 4M VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE A 3 IN 76mm MINIMUM CLEARANCE TO COMBUSTION AIR INTAK...

Page 14: ...usly connected to condensate trap b Use inducer housing drain extension tube violet label and factory supplied in loose parts bag to connect LOWER inducer housing drain connection to condensate trap c Determine appropriate length cut and connect tube d Clamp tube to prevent any condensate leakage 3 Relief Port Tube a Extend collector box tube green label which was previously connected to condensat...

Page 15: ...abs through casing hole and rotating until tabs snap into locking position 5 Fill unused condensate trap casing holes with plastic filler caps factory supplied in loose parts bag UPFLOW OR DOWNFLOW HORIZONTAL FRONT FRONT LEVEL 0 TO 1 2 13mm MAX MIN 1 4 7mm TO 1 2 13mm MAX A02146 Fig 15 Proper Condensate Drainage Condensate Trap Tubing NOTE See Fig 14 or tube routing label on main furnace door to c...

Page 16: ...n is to reduce excessive condensate droplets from exiting the vent pipe See Fig 12 13 or 44 LOCATION General This furnace must S be installed so the electrical components are protected from water S not be installed directly on any combustible material other than wood flooring refer to SAFETY CONSIDERATIONS S be located so combustion air and vent pipe maximum lengths are not exceeded Refer to Table...

Page 17: ...death Do not install furnace on its back See Fig 16 Safety control operation will be adversely affected Never connect return air ducts to back of furnace WARNING The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance s combustion air supply or act to mix products of combustion with circulati...

Page 18: ...oil Box is used install as shown in Fig 21 NOTE Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase To remove furnace perforated discharge duct flange use hand scanners wide duct pliers or duct flange tool to bend flange back and forth until it breaks off Be careful of sharp edges See Fig 22 UNIT MAY NOT OPERATE HAZARD Failure to fol...

Page 19: ... Furnace Plenum and Subbase Installed on a Combustible Floor FACTORY SUPPLIED CASED COIL OR COIL BOX FURNACE COMBUSTIBLE FLOORING SHEET METAL PLENUM FLOOR OPENING A07586 Fig 21 Furnace Plenum and Coil Assembly or Coil Box Installed on a Combustible Floor NO YES YES PERFORATED DISCHARGE DUCT FLANGE 210 DEG MIN A93029 Fig 22 Duct Flanges 58MVC ...

Page 20: ...to ensure proper drainage 3 For non direct vent 1 pipe application bottom side combustion air entry cannot be used when furnace is installed with hangers as shown A PREFERRED ROD LOCATION B ALTERNATE ROD LOCATION DRAIN 5 3 4 146mm 3 8 IN HEX NUT WASHER 4 REQD PER ROD VENT COMBUSTION AIR PIPE DIRECT VENT 2 PIPE APPLICATION ALL SIZES COMBUSTION AIR INTAKE NON DIRECT VENT 1 PIPE APPLICATION 3 IN MINI...

Page 21: ...ace containing the furnace Secure ductwork with proper fasteners for type of ductwork used Seal supply and return duct connections to furnace with code approved tape or duct sealer Flexible connections should be used between ductwork and furnace to prevent transmission of vibration Ductwork passing through unconditioned space should be insulated to enhance system performance When air conditioning ...

Page 22: ... can be used with the factory supplied washable filter or a factory specified high efficiency disposable filter see cabinet instructions If installing the filter in the furnace blower compartment determine location for filter and relocate filter retaining wire if necessary See Table 2 to determine correct filter size for desired filter location Table 2 indicates filter size location and quantity s...

Page 23: ...ZARD Failure to follow this warning could result in personal injury death or property damage Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls Gas valve shutoff switch MUST be facing forward or tilted upward Never purge a gas line into a combustion chamber Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the...

Page 24: ...ecific gravity gas Ref Table 9 2 NFPA 54 2002 NOTE The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0 5 psig 14 in wc stated on gas valve See Fig 60 Piping should be pressure and leak tested in accordance with NFGC in the United States or CAN CSA B149 1 05 in Canada local and national plumbing and gas codes befo...

Page 25: ...al codes or in the absence of local codes with the National Electric Code ANSI NFPA 70 and or the Canadian Electric Code CSA C22 1 Part I if an external electrical source is utilized Use a separate branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace See Table 4 for wire size and fuse specifications A disconnecting means must be located within sight from a...

Page 26: ...S POWER ENTRY HOLE FILLER PLUG FACTORY SUPPLIED LOOSE PARTS BAG A05113 Fig 31 Factory Installed J Box Location J Box Relocation 1 Remove two screws holding auxiliary J box See Fig 32 2 Rotate J box 180_ and attach box to left side using holes provided FACTORY INSTALLED LOCATION ALTERNATE FIELD LOCATION POWER ENTRY HOLE FILLER PLUG FACTORY SUPPLIED LOOSE PARTS BAG UNUSED 7 8 IN DIAMETER POWER ENTRY...

Page 27: ...low this caution may result in premature component failure This furnace can be vented as either a direct vent 2 pipe furnace or as an optional ventilated combustion air application A direct vent system shall be installed in accordance with the direct vent 2 pipe procedures in the Combustion Air and Vent Pipe Systems section within this supplemental instruction For optional ventilated combustion ai...

Page 28: ... in Fig 36 for Direct Vent 2 Pipe system or Fig 37 for ventilated combustion air option A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code the current edition of the National Fuel Gas Code and the vent or...

Page 29: ... cement in a light uniform coat on inside of socket to prevent buildup of excess cement Apply second coat 8 While cement is still wet twist pipe into socket with 1 4 turn Be sure pipe is fully inserted into fitting socket 9 Wipe excess cement from joint A continuous bead of cement will be visible around perimeter of a properly made joint 10 Handle pipe joints carefully until cement sets 11 Horizon...

Page 30: ... AND COMM LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR AIR CONDITIONING A C AIRFLOW SETUP SWITCHES USER INTERFACE OR ADVANCED PRODUCT MONITOR CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OAT CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX ACRDJ AIR CONDITIONING RELAY DISABLE JUMPER FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES BOARD SERIAL NUMBER EXAMPLE...

Page 31: ...31 12 inches 30 cm for applieances 10 000 Btuh 3 kW and 100 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30kW V V A08600 Fig 34 Direct Vent Termination Clearance 58MVC ...

Page 32: ...32 A08601 Fig 35 Ventilated Combustion Air Vent Termination Clearance 58MVC ...

Page 33: ...ichever is greater typ A At least 36 in A Maintain 12 in 305mm min clearance above highest anticipated snow level Maximum of 24 in 614mm above roof 90 Note A denotes 0 to 2 in Between the first 2 vents Third vent must be 36 in away typ 914mm 305mm 914mm 305mm 305mm 914mm 914mm 457mm 51mm 914mm A05090 Fig 36 Combustion Air and Vent Termination for Direct Vent 2 pipe System Abandoned masonry used as...

Page 34: ... are required COMBUSTION AIR PIPE General Furnace combustion air connection must be attached as shown in Fig 39 Combustion air intake housing plug may need to be relocated in some applications COMBUSTION AIR COMBUSTION AIR AIR FLOW VENT VENT VENT AIR FLOW AIR FLOW AIR FLOW UPFLOW DOWNFLOW HORIZONTAL LEFT DISCHARGE HORIZONTAL RIGHT DISCHARGE Select 1 vent pipe connection and 1 combustion air pipe c...

Page 35: ...n may result in reduced furnace component life Air for combustion must not be contaminated by halogen compounds which include fluoride chloride bromide and iodide These elements may corrode heat exchangers and shorten furnace life Air contaminants are found in aerosol sprays detergents bleaches cleaning solvents salts air fresheners and other household products CAUTION The combustion air pipe cann...

Page 36: ...ing appliance to their previous conditions of use WARNING Combustion Air Termination Direct Vent 2 Pipe System Combustion air pipe must terminate outside the structure with the vent pipe as shown in Fig 36 Follow the clearance requirements shown in Fig 39 Refer to Vent Termination section for complete details on termination options VENT PIPE General Furnace vent connection must be attached as show...

Page 37: ...37 304 8mm minimum A06672 Fig 41 Attic Termination 304 8 mm minimum 76 2 mm minimum A06673 Fig 42 Crawlspace Termination 58MVC ...

Page 38: ...PE COMBUSTION AIR PIPE VENT PIPE COMBUSTION AIR PIPE VENT PIPE COMBUSTION AIR PIPE VENT PIPE 12 MIN 12 MIN 12 MIN 304 8mm 12 MIN 304 8mm NOTE A 12 in 304 8mm minimum offset pipe section is recommended with short 5 to 8 ft 1 5 to 2 5M vent systems This recommendation is to reduce excessive condensate droplets 305mm 305mm A96230 Fig 44 Short Vent 5 to 8 ft 1 5M to 2 4M System 58MVC ...

Page 39: ...tructions in termination kit for the latest version Combustion air and vent pipes MUST terminate outside structure A factory accessory termination kit must be installed as shown in Table 8 There are four options of vent combustion air termination kits available as shown in Table 8 NOTE Combustion air pipe must have the same diameter as vent pipe Concentric Vent Combustion Air Termination Kit Direc...

Page 40: ...39 11 9 47 14 3 55 16 8 20 F 29 C 2 51 8 2 4 21 6 4 25 7 6 31 9 4 37 11 3 100 20 F 7 C 2 1 2 64 42 12 8 70 21 3 70 21 3 70 21 3 70 21 3 0 F 18 C 2 1 2 64 18 5 5 38 11 6 43 13 1 53 16 2 61 18 6 20 F 29 C 2 1 2 64 9 2 7 23 7 0 27 8 2 34 10 4 41 12 5 120 20 F 7 C 3 76 44 13 4 70 21 3 70 21 3 70 21 3 70 21 3 0 F 18 C 3 76 18 5 5 38 11 6 44 13 4 54 16 5 63 19 2 20 F 29 C 3 76 8 2 4 23 7 0 27 8 2 35 10 ...

Page 41: ...ntric 1 1 2 38 42 12 8 37 11 2 32 9 8 27 8 2 22 6 7 17 5 2 2 51 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 80 000 2 Pipe or 2 In 51 Concentric 1 1 2 38 25 7 6 20 6 1 15 4 6 10 3 0 5 1 5 NA 2 51 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 100 000 2 Pipe or 2 In 51 Concentric 2 51 38 11 6 33 10 1 28 8 5 23 7 0 18 5 5 13 4 0 2 1 2 64 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 120 000 2 ...

Page 42: ...2 1 NA NA NA 2 51 62 18 9 60 18 3 58 17 7 56 17 1 51 15 5 46 14 0 100 000 2 Pipe or 2 In 51 Concentric 2 51 27 8 2 22 6 7 17 5 2 12 3 7 7 2 1 NA 2 1 2 64 62 18 9 60 18 3 58 17 7 56 17 1 55 16 8 53 16 2 120 000 2 Pipe or 3 In 76 Concentric 3 76 one disk 43 13 1 41 12 5 39 11 9 37 11 3 35 10 7 34 10 4 ALTITUDE UNIT SIZE BTUH Termination Type Pipe Dia In mm NUMBER OF 90_ ELBOWS 1 2 3 4 5 6 9001 to 10...

Page 43: ...To avoid condensate spillage select a pump with an overflow switch Furnace condensate is mildly acidic typically in the pH range of 3 2 to 4 5 Due to corrosive nature of this condensate a condensate pH neutralizing filter may be desired Check with local authorities to determine if a pH neutralizer is required Application The furnace A C and humidifier drains may be combined and drained together Th...

Page 44: ...low for two speed cooling units This setup feature allows continuous fan airflow or low cooling airflow to be adjusted To set desired continuous fan airflow or low cooling airflow 1 Remove main furnace door and blower access panel 2 Locate CF setup switches on furnace control See Fig 33 3 Determine desired continuous fan airflow or low cooling airflow 4 Use Fig 47 or wiring schematic to determine ...

Page 45: ...ZARD Failure to follow this caution may result in intermittent unit operation or performance satisfaction Condensate trap must be PRIMED or proper draining may not occur The condensate trap has two internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap CAUTION A04001 Fig 48 Example of Setup Switch in Off Position 58MVC ...

Page 46: ...46 A06677 Fig 49 Wiring Diagram 58MVC ...

Page 47: ...ent ON Turn ON to decrease Low Heat airflow 9 percent Medium Heat airflow 7 percent and High Heat airflow 15 percent for maximum comfort SW1 5 CFM per ton adjust OFF Turn ON for 400 CFM per ton Turn OFF for 350 CFM per ton SW1 6 Component Self Test OFF Turn ON to initiate Component Self Test for troubleshooting assistance when R thermostat lead is disconnected Turn OFF when Self Test is completed ...

Page 48: ... erased and the furnace control CPU will select medium heat for 1 minute low heat for 15 minutes and then switch to high heat as long as the thermostat continues to call for heat Subsequent selection is based on stored history of the thermostat cycle times The wall thermostat calls for heat closing the R to W circuit The furnace control CPU performs a self check verifies the low heat and medium he...

Page 49: ...m or low heat while the thermostat R to W circuit is closed when using a single stage thermostat 8 Blower Off Delay When the thermostat is satisfied the R to W circuit is opened de energizing the gas valve GV M stopping gas flow to the burners and de energizing the throttling valve TV and humidifier terminal HUM The inducer motor IDM will remain energized for a 15 second post purge period The blow...

Page 50: ... low cooling to high cooling the furnace control CPU will energize the air conditioning relay ACR When the air conditioning relay ACR is energized the R to Y1 and Y2 circuits switch the outdoor unit to high cooling speed and the R to G and Y1 and Y Y2 circuits transition the furnace blower motor BLWM to high cooling airflow High cooling airflow is based on the A C selection shown in Fig 47 NOTE Wh...

Page 51: ...r BLWM operation Continuous Blower Speed Selection from Thermostat To select different continuous blower airflows from the room thermostat momentarily turn off the FAN switch or push button on the room thermostat for 1 3 seconds after the blower motor BLWM is operating The furnace control CPU will shift the continuous blower airflow from the factory setting to the next highest CF selection airflow...

Page 52: ...gle Speed Air Conditioning A06679 Fig 53 Step Modulating Furnace with Two Speed Air Conditioner A06680 Fig 54 Step Modulating Furnace with Single Speed Heat Pump Dual Fuel A06681 Fig 55 Step Modulating Furnace with Two Speed Heat Pump Dual Fuel 58MVC ...

Page 53: ...Fig 57 Dual Fuel thermostat with Step Modulating Furnace and Two Speed Heat Pump A06684 Fig 58 Two Stage Thermostat with Step Modulating Furnace and Two Speed Air Conditioner A06685 Fig 59 Single Stage Thermostat with Step Modulating Fur nace and Two Speed Air Conditioner 58MVC ...

Page 54: ...t rate on rating plate is for installations at altitudes up to 2000 ft 609 6M In the USA the input rating for altitudes above 2000 ft 609 6M must be reduced by 2 percent for each 1000 ft 304 8M above sea level In Canada the input rating must be derated by 5 percent for altitudes of 2000 ft 609 6M to 4500 ft 1371 6M above sea level Adjust manifold pressure to obtain input rate Furnace input rate mu...

Page 55: ...ch SW1 2 on control center to ON position See Fig 33 NOTE DO NOT set low heat manifold pressure before setting medium heat manifold pressure DO NOT set low heat manifold pressure less than 5 in wc or more than 6 in wc for natural gas m When correct manifold pressures are obtained replace caps that conceal gas valve adjustment screws Main burner flame should be clear blue almost transparent See Fig...

Page 56: ... 6 0 60 44 3 8 1 6 0 60 43 3 4 1 5 0 55 875 44 3 4 1 4 0 55 44 3 5 1 5 0 55 44 3 6 1 5 0 60 44 3 7 1 6 0 60 4000 900 44 3 2 1 3 0 50 44 3 3 1 4 0 55 44 3 4 1 4 0 55 44 3 5 1 5 0 55 1219 925 45 3 7 1 5 0 60 45 3 8 1 6 0 60 44 3 2 1 4 0 50 44 3 3 1 4 0 55 950 45 3 5 1 5 0 55 45 3 6 1 5 0 55 45 3 7 1 6 0 60 45 3 8 1 6 0 60 750 43 3 7 1 6 0 60 43 3 8 1 6 0 60 42 3 2 1 4 0 50 42 3 3 1 4 0 55 4001 775 4...

Page 57: ... 60 45 3 7 1 6 0 60 44 3 2 1 4 0 50 825 45 3 3 1 4 0 55 45 3 4 1 4 0 55 45 3 5 1 5 0 55 45 3 6 1 5 0 60 625 43 3 8 1 6 0 60 42 3 2 1 4 0 50 42 3 3 1 4 0 55 42 3 4 1 5 0 55 8001 650 43 3 5 1 5 0 55 43 3 6 1 5 0 60 43 3 8 1 6 0 60 42 3 2 1 3 0 50 2439 675 44 3 7 1 6 0 60 43 3 4 1 4 0 55 43 3 5 1 5 0 55 43 3 6 1 5 0 60 700 44 3 5 1 5 0 55 44 3 6 1 5 0 60 44 3 7 1 6 0 60 44 3 8 1 6 0 60 725 44 3 2 1 4...

Page 58: ...ate n Remove jumper across R W W1 and W2 thermostat connections to terminate call for heat o Wait for blower off delay to finish then reset 115 v power to furnace p Wait for blower off delay to finish then reset 115 v power to furnace q Jumper R and W W1 thermostat connections on control to start furnace r Wait for the blower to turn ON then repeat items i through l for low heat operation This set...

Page 59: ...rise range when setup switch SW1 4 is OFF CAUTION Furnace must operate within ranges of temperature rise specified on the furnace rating plate Determine air temperature rise as follows 1 Place thermometers in return and supply ducts as near furnace as possible Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings This practice is particularly important with s...

Page 60: ...ontrol 3 The return air opening should be unblocked to permit normal air circulation By using this method to check the limit control it can be established that the limit is functioning properly and the furnace will operate safely if there is a restricted return air duct or motor failure If the limit control does not function during this test the cause must be determined and corrected Check Pressur...

Page 61: ...______ Sidewall ________________ Anticipator Setting Adjusted or ________________ Attic ________________ Cycle Rate 3 Cycles per Hr Selected ________________ Crawl Space Safety Controls Check Operation ________________ Termination Kit 2 Pipe or Concentric CHECKLIST START UP ________________ Combustion Air Pipe Length ________________ Gas Input Rate Set Within 2 percent of Rating Plate ____________...

Page 62: ... W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 12 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 58MVC 5SI Replaces 58MVC 4SI 58MVC ...

Reviews: