background image

24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

39

Vapor Injection Electronic Exp. Valve (EXV VI)
(5 Ton Models)

The EXV-VI is an electronically controlled needle valve for regulating
refrigerant flow during heating operation.  The EXV-VI is driven by a
12VDC, 2-phase, uni-polar stepper motor.  The EXV-VI has a 475 step

range between fully closed and fully open. The PCM drives the EXV at a
rate  of  77  steps  per  second.    The  PCM  initializes  the  EXV-VI  to  the
closed position when power is applied to the equipment.  This process

takes approximately 7 seconds.
When  operating  at  full  capacity  in  a  cooling  at  high  ambient
temperatures  or  in  heating  at  low  ambient  temperatures  in  efficiency
mode,  the  EXV-VI  is  actively  controlled  to  maintain  discharge  super
heat  to  a  control  target  value.   When  operating  at  a  lower  capacity,  in

comfort  mode,  at  mild  ambient  temperatures,  or  not  running,  the
EXV-VI is closed.
The brazed  plate heat exchanger assembly is mounted  to  the base  pan
using  a  grommet  and  stud  similar  to  the  accumulator  mounting.    The

BPHE assembly also contains a muffler either between the BPHE and
the  compressor  or  between  the  BPHE  and  the  liquid  service  valve.
Additionally, there are rubber dampers attached to the tube between the

BPHE and the compressor.  
If  any  part  of  the  BPHE  needs  to  be  repaired  then  only  a
factory-authorized part shall be used to replace the entire vapor injection
assembly.    It  is  recommended  that  the  coil  be  removed  to  replace  the

BPHE  assembly.    Upon  replacement  the  grommet  and  clip  used  for
mounting  can  be  re-used  and  the  dampers  shall  be  re-attached  to  the
BPHE assembly using a wire tie.  Failure to re-attach the dampers could

result in a premature tube failure."

REFRIGERATION SYSTEM REPAIR

Leak Detection

New  installations  should  be  checked  for  leaks  prior  to  complete

charging.  If a system has lost all or most of its charge, system must be
pressurized  again  to  approximately  150  psi  minimum  and  375  psi
maximum. This can be done by adding refrigerant using normal charging

procedures or by pressurizing system with nitrogen (less expensive than
refrigerant).  Nitrogen  also  leaks  faster  than  refrigerants.    Nitrogen
cannot,  however,  be  detected  by  an  electronic  leak  detector.  (See

Fig. 40

.)

A95422

Fig. 40 – Electronic Leak Detection

Assuming  that  a  system  is  pressurized  with  either  all  refrigerant  or  a
mixture  of  nitrogen  and  refrigerant,  leaks  in  the  system  can  be  found

with  an  electronic  leak  detector  that  is  capable  of  detecting  specific
refrigerants.
If  system  has  been  operating  for  some  time,  first  check  for  a  leak
visually. Since refrigerant carries a small quantity of oil, traces of oil at

any joint or connection is an indication that refrigerant is leaking at that
point. 

A  simple  and  inexpensive  method  of  testing  for  leaks  is  to  use  soap

bubbles.  (See 

Fig. 41

.) Any  solution  of  water  and  soap  may  be  used.

Soap solution is applied to all joints and connections in system. A small

pinhole leak is located by tracing bubbles in soap solution around leak. If

the  leak  is  very  small,  several  minutes  may  pass  before  a  bubble  will

form.  Popular  commercial  leak  detection  solutions  give  better,

longer-lasting bubbles and more accurate results than plain soapy water.

The bubble solution must be removed from the tubing and fittings after

checking for leaks as some solutions may corrode the metal.

A95423

Fig. 41 – Bubble Leak Detection

You may use an electronic leak detector designed for specific refrigerant
to check for leaks (See 

Fig. 40

). This unquestionably is the most efficient

and  easiest  method  for  checking  leaks.  There  are  various  types  of
electronic  leak  detectors.  Check  with  manufacturer  of  equipment  for
suitability.  Generally  speaking,  they  are  portable,  lightweight,  and

consist of a box with several switches and a probe or sniffer. Detector is
turned  on  and  probe  is  passed  around  all  fittings  and  connections  in
system. Leak is detected by either the movement of a pointer on detector

dial, a buzzing sound, or a light.
In all instances when a leak is found, system charge must be recovered
and leak repaired before final charging and operation.  After leak testing
or leak is repaired, replace liquid line filter drier, evacuate system, and

recharge with correct refrigerant quantity.

Coil Removal

Coils  are  easy  to  remove  if  required  for  compressor  removal,  or  to
replace coil.

1. Shut off all power to unit.
2. Recover refrigerant from system through service valves.
3. Break vacuum with nitrogen.
4. Remove top cover. 
5. Remove screws in base pan to coil grille.
6. Remove coil grille from unit.
7. Remove screws on corner post holding coil tube sheet.

8. Use midget tubing cutter to cut liquid and vapor lines at both sides

of coil. Cut in convenient location for easy reassembly with copper

slip couplings.

9. Lift coil vertically from basepan and carefully place aside.
10. Reverse procedure to reinstall coil.
11. Replace  filter  drier,  evacuate  system,  recharge,  and  check  for

normal systems operation.

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE  HAZARD

Failure to follow this warning could result in personal injury or death.
Due to the high pressure of nitrogen, it should never be used without a
pressure regulator on the tank.

BEEP

BEEP

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Before  installing,  modifying,  or  servicing  system,  main  electrical
disconnect switch must be in the OFF position. There may be more than

1 disconnect switch. Lock out and tag switch with a suitable warning
label. 

WARNING

!

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  or
equipment damage.
Cut tubing to reduce possibility of personal injury and fire.

LEAK

DETECTOR

SOLUTION

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...

Reviews: