5
COLUMN-TO-COLUMN WITH SHELVING (SEE FIG. 11)
1. Drill two
3
/
16
-in. holes for attaching runout.
2. Cut runout enclosure, back panel, and shelving to desired
length.
Maximum unsupported shelf length is 3 ft.
3. Fit runout enclosure into slots of 2 end frames.
4. Install end panels flush with front of runout enclosure,
leaving space at bottom to insert shelving. Fasten end
panels to runout enclosure with U-clips.
5. Insert shelving below end panels, with flanges turned
down. Shelving rests on lower flange of end frame.
6. Hang assembly on wall mounting strip and adjacent to
unit enclosure. Stiffener bracket lip must support bottom
of runout.
7. Attach end frame to unit enclosure with two No. 8 sheet
metal screws (field-supplied).
ENCLOSURE WITH SINGLE OR DUAL RUNOUT (SEE
FIG. 12)
1. Drill two
3
/
16
-in. holes for attaching runout.
2. Cut runout enclosure to desired length; fit into slots of 2
end frames.
3. Hang assembly on wall mounting strip and adjacent to
base unit enclosure. Stiffener bracket lip must support
bottom of runout.
4. Attach end frame to base unit enclosure with one No. 8
sheet metal screw (field-supplied).
Fig. 11 — Column-to-Column Enclosure with Shelving