2 - SAFETY CONSIDERATIONS

WARNING: Switch off the main electrical power 

supply to the unit and accessories (if installed) 

before doing any work on the unit.

2.1 - General

Installing, commissioning and servicing of the various 

component  (unit,  control  system,  hot  and  cold  water 

system,  air  distribution  system)  can  be  dangerous 

unless certain aspects of the installation, such as the 

presence of mains electricity and hot or cold water in 

the air conditioning equipment, are taken into account. 

Only  specially  trained  and  qualified  technicians  and 

installers who have been fully trained on the product 

concerned are authorised to install, commission and 

service this equipment.

During  servicing  work,  it  is  essential  to  apply  all 

recommendations and instructions given in service 

leaflets, on labels or in the instructions delivered with 

the equipment, and to comply with any other relevant 

instructions.

Definition of the pictograms used:

 

Electrical danger    

- Fig.4

 

Caution hand hazard  

- Fig.5

 

General danger  

 

- Fig.6

Comply with all safety rules and regulations currently in 

force. Wear eye protectors and work with hand gloves 

and any individual protection equipment following local 

legislation. Take care when moving or positioning of the 

equipment.

2.2 - 

Protection against electrocution

Only personnel qualified to perform electrical and 

maintenance work may make electrical connections. In 

particular it is obligatory to disconnect all power supplies 

to the unit and its accessories before carrying out any 

work.  Disconnect  the  main  power  supply  with  an 

isolating device (not supplied by Carrier).

IMPORTANT: The components, which make up the 

different control loops described in this manual 

include electronic items. As such, they may 

generate or be harmed by electromagnetic 

interference unless they are installed and used in 

accordance with these instructions. The components 

making up these control systems conform to the 

requirements of electromagnetic compatibility in 

residential, commercial and light industrial areas. 

They also comply with the low-voltage directive.

If the product is supplied without a Carrier control device, 

verification of EMC conformity is the responsibility of 

the installer.

2.3 - 

General installation conditions

IMPORTANT: The Carrier numeric controller, power 

module, or in general units fitted with controls loops 

must have an isolating device upstream (for 

example a double-pole circuit breaker). If necessary, 

an easily operated emergency stop device (such as 

a punch-button switch) must cut off the power to 

all equipment. The installation must be equipped 

with a device to protect against earth faults. The 

disconnect device must simultaneously disconnect 

the two poles (phase and neutral), and have a 

distance of at least 3 mm between the contacts, in 

compliance with the installation instructions. The 

mains power cable must have 3 conductors (blue, 

brown, green/yellow) and its cross section and type 

must comply with the specifications set out by the 

applicable EN or IEC standard. Refer to the selection 

sheet or the name plate to determine the maximum 

input current. These devices are not supplied by 

Carrier.

In general terms the following rules must be applied:

Upstream over voltage protection

Size (42NL & 42NH)

Without Elec. Heater

2_5; 2_9

T2A

3_5; 3_9

T2A

4_5; 4_9

T2A

5_5; 5_9

T3A

6_5; 6_9

T3A

7_9; 7_9

T3A

Size (42NL & 42NH)

With Elec. Heater

[0-1400W]

[1500-

2400W]

[3000-

3200W]

2_5; 2_9

T10A

NA

NA

3_5; 3_9

T10A

NA

NA

4_9

T10A

NA

NA

4_5

T10A

T16A

NA

5_5; 5_9

T10A

T16A

NA

6_5; 6_9

T10A

T16A

T20A

7_5; 7_9

T10A

T16A

T20A

 

Electrical connections must be made according to 

the  wiring  diagram  provided  with  the  unit  and  the 

installation and operation manual of the controller.

 

■ Units must be provided with over-voltage protection 

upstream (not supplied by Carrier).

 

■ The  power  disconnection  device  must  be  clearly 

labelled  to  identify  which  items  of  equipment  are 

connected to it.

 

■ The wiring of the components which make up the 

different control systems and the communication 

buses must be carried out in accordance with the 

latest rules and regulations by professional installers.

13

Summary of Contents for Idrofan 42NH

Page 1: ...Translation of the original document DUCTED FAN COIL UNITS 42NL 42NH INSTALLATION OPERATING AND M A I N T E N A N C E I N S T R U C T I O N S ...

Page 2: ......

Page 3: ...Installing the unit in the false ceiling 15 3 2 Installation procedure 15 3 3 Removal procedure 16 3 4 Safety considerations relating to final shut down 16 4 COMPONENTS AND MAINTENANCE 17 4 1 Fan motor assembly 17 4 2 Drain pan removal 18 4 3 Water coil 18 4 4 Duct connection spigots 18 4 5 Duct connection rectangular flanges 18 4 6 Optional filter and filter access 19 4 7 Fresh air controller 19 ...

Page 4: ...2NH L size 4 1114 300 50 42NH L size 5 1314 300 50 42NH L size 6 1314 345 50 42NH L size 7 1614 345 50 B C A B A B 42NH L size 2 744 300 42NH L size 3 914 300 42NH L size 4 1114 300 42NH L size 5 1314 300 42NH L size 6 1314 345 42NH L size 7 1614 345 C A B 4 ...

Page 5: ...A B 42NH L size 2 744 300 42NH L size 3 914 300 42NH L size 4 1114 300 42NH L size 5 1314 300 42NH L size 6 1314 345 42NH L size 7 1614 345 D A B E F G H I 0 5 5 ...

Page 6: ... 0 5 0 5 9a 9b L 11a 11a K 10a 10b M 12b 12a N 13a 13a 6 ...

Page 7: ...O Ø16 26 Ø16 4w v 2w v 2w v B 40 40 40 B B B G G G C C C C C H D I E J F F F F K 7 ...

Page 8: ...R BAS 60 50 75 100 70 80 90 DOWN 17a 17b 17c Q 16a 16b 16c 16d P 15a 15b 15d 15c 15e 8 ...

Page 9: ...S 18a 9 ...

Page 10: ...4w v 9 Water outlet of 2w v 10 Water outlet of 2w v B 2w v Two way valve 2w v B Two way valve and balancing function 4w v Four way valve Three way valve with integral by pass Connections for two way valve with balancing function Size 2 and 3 3 4 diameter Size 4 and 5 1 diameter Connections for other valves and coils Size 2 3 4 and 5 1 2 diameter Size 6 and 7 3 4 diameter 15 Meaning of wires propor...

Page 11: ...haracter may be present The copper aluminium coil or components inside the unit could suffer irreparable corrosion damage in their presence 1 1 4 Recommended coil water quality At installation handover and then periodically every year it is advised to analyse the water for bacteria detection of ferro bacteria H2S producing and sulphate reducing bacteria and chemicals in order to avoid problems due...

Page 12: ... 60 or 50 Hz 1ph 60Hz not available for 42NH3_5 NOTE All performances data certified by Eurovent are based on 50Hz application Carrier doesn t ensure the same performances when the unit operates at 60Hz the RPM and power input of the fan motor are usually higher WARNING Failure to take proper account of the above advice and unauthorised modification of the electrical connections will render the Ca...

Page 13: ...tic compatibility in residential commercial and light industrial areas They also comply with the low voltage directive If the product is supplied without a Carrier control device verification of EMC conformity is the responsibility of the installer 2 3 General installation conditions IMPORTANT The Carrier numeric controller power module or in general units fitted with controls loops must have an i...

Page 14: ...4 Caution for the control of the unit IMPORTANT It is not permitted to connect several units to the same control device electronic NTC controller WTC controller or any other third party controller Carrier electronic Thermostat type A B for AC motors require additional accessory board to allow master slave function Carrier electronic Thermostat type C D for EC motors can be connected upto 10 units ...

Page 15: ...ts need to be installed it may be advisable to produce a drilling template The method of fixing the threaded hangers not supplied by Carrier depends on the ceiling type maximum diameter of the threaded hangers is 10 mm Once the threaded hangers are fixed to the ceiling tighten the first nuts WARNING When moving the units do not use water pipes condensate drain pan valves or flexible pipes to lift ...

Page 16: ...alled open the stop valves on the manifolds bleed and then pressurize the circuits To bleed the coils slightly loosen the bleed screws The installation can then be started NOTE Do not switch on the power until all connections are made and earthed 3 3 Removal procedure Switch off the unit power supply at the isolator provided for the purpose during installation isolator not supplied by Carrier Disc...

Page 17: ...Disconnect the capacitor by withdrawing the flat spade connectors from the back of the capacitor Replacement of the capacitor assembly is by the reversal of the above procedure 4 1 3 Fan wiring For any modifications of the wiring harness refer to the fan wiring diagrams provided with the units With the optional electrical box three of the available five or six speeds of AC motor are connected maxi...

Page 18: ... fixing screws Pull out the drain pan and coil assembly the drain pan remains attached to the unit for approximately 100 mm until the coil is completely detached Then remove the coil from the drain pan Replacement is by the reversal of the procedure described above Ensure that all gaskets are changed new gaskets fitted and that the inlet and outlet connections to the coil are made correctly using ...

Page 19: ...f the supply air flow delivered by the unit at minimum speed NOTE To operate correctly the constant fresh air flow controller requires a differential pressure in the range of 60 Pa to 210 Pa 4 7 2 Fresh air controller with variable air volume The unit can be equipped with a variable fresh air flow controller from 0 to 55 l s 0 to 200 m3 h This is connected to the numeric Carrier controller and can...

Page 20: ...lable ON OFF actuator Not Standard Available Available Moduling 3p actua Not Standard Available Available Waterflow range 200 l h 600 l h 1200 l h 1600 l h MINI NA NA NA NA 0 2 NA NA NA NA 0 4 NA NA NA NA 0 5 30 100 NA NA 0 6 35 115 200 220 0 8 40 130 260 290 1 50 160 310 250 1 2 60 180 380 420 1 4 70 210 430 480 1 6 80 240 490 550 1 8 90 270 550 610 2 100 300 610 680 2 2 110 320 660 740 2 4 120 3...

Page 21: ... to the valve body maximum torque 15 N m 4 8 5 Valve body replacement procedure Disconnect the power supply before carrying out any work on a unit Close the isolating valves on the manifolds Unscrew the union nuts to disconnect the flexible water pipes Remove the valve actuators taking care to identify the cooling and heating valves Disconnect the flexible condensate drain pipe which is held in pl...

Page 22: ... above 1400 W capacity All units delivered with an electrical box or a Carrier controller are always equipped with a relay if the capacity of the electrical heater is above 1400W WARNING In case of customer supplied controller it is the responsability of the installer to set up an additional protection relay corresponding to the electrical heater capacity 4 11 Optional water sensor A water tempera...

Page 23: ......

Page 24: ... 08 2022 Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Supersedes order No X 00DCG000132000D 09 2017 Manufacturer reserves the right to change any product specifications without notice Printed in the European Union ...

Reviews: