background image

3 - INSTALLATION OF THE UNIT

3.1 - Procedure for installation

3.1.1 - Introduction

42GR ATMs are designed to be installed in a technical service 

room in the centre of the space to be treated. They are arranged 

side by side and their very high pressure provided enables them 

to operate with large duct networks.
42GR ATMs are composed of 3 main components to be installed 

in the following order (Fig.4):

 

-

The attachment rail: Fig.4a

 

-

The suspension box: Fig.4b

 

-

The air treatment module (ATM): Fig.4c

The  assembly  instructions  for  each  component  are  explained 

below.

3.1.2 - Attachment rail

Fix the attachment rail firmly into the concrete slab overhanging 

the technical room. The attachment rail drawing is detailed in Fig.5. 

It makes it possible to receive the suspension box for the support 

of the ATM. It is supplied as packages of 5 rails of two metres. 

The assembly makes it possible to suspend 40 size 1 or 23 size 

2 ATMs. The rails can be cut to the required length.

3.1.3 - Suspension box

CAUTION: The suspension boxes cannot be dismantled at 

all, once they are installed, sheathed and if the false ceiling 

of the technical rooms is closed.
PRECAUTIONS FOR INSTALLATION: During installation of 

the  unit,  ensure  that  any  construction  debris  which  has 

remained in the ducts cannot damage the unit.

 

-

Attach the suspension box

 to the attachment rail in order 

to support the ATM and to ensure the bulkhead connection 

of the technical room (Fig.6b). The suspension box comprises 

an uninsulated plenum consisting of ferrules, one for the air 

recirculated (Fig.6g) and one for the air blown (Fig.6h). In 

accordance with the mandatory requirements for sound 

levels, silencers may be provided.

 

-

Complete the ventilation connections

 for the suspension 

box (blowing and recirculation of air). Ensure that the insides 

of the ducts are clean to avoid the movement of construction 

debris  which  could  damage  the  mechanical  parts  of  the 

system such as the fan turbine or the thermostat component 

of the diffuser.

CAUTION: Load losses in the ducts must be compatible with 

the performance of the device. The duct must be as taut as 

possible. Avoid sharp bends. Check that the ducts have no 

air leaks and that they are not overburdened.

 

-

Prepare the hydraulic system

 with installation of collectors 

and stop valves in standby position on the various spurs. 

Sufficient clearance will have been provided for the assembly 

and dismantling of the ATMs as well as for maintenance of 

the filters through the filter access door (Fig.6c).

3.1.4 - Air treatment module (ATM)

CAUTION: Never lift the ATM by using exposed pipes, valves/ 

hoses, electrical wiring harnesses, or condensate drains.

 

-

Fix the ATM to the suspension box

. For this, it must be 

attached to the suspension hook (Fig.6j); then push the ATM 

against the box. This will cause crushing of the seal located 

between the box and the ATM and locking of the latch hook 

(Fig.6i). Then connect the hydraulic hoses.

 

-

Connect the condensate drains of the ATM (Fig.7) 

using 

a  fastener  for  flexible  tube  of  inner  ø  16  mm 

 

(Fig.7a). To avoid the emergence of odour, it is MANDATORY 

to  install  a  siphon  of  at  least  100  mm  on  each ATM  (for 

example yoke with the condensate drainage tube) (Fig.7b). 

Make a slope of 20mm/m on the common drain pipe (Fig.7c) 

without blip or lifting.

 

-

Connect the hydraulic hoses 

between the stop valves of 

the collectors and the water inlet(s)/ outlet(s) of the 42GR 

ATM (Carrier recommends the use of hydraulic hoses which 

can be supplied as accessories). Each hose is provided with 

a G1/2” rotating nut depending on the model. Do not forget 

to insert a seal between the rotating nut and the stop valve 

(seal not supplied by Carrier).

 

-

When all the units are installed, open the stop valves located 

on the collectors, purge the circuits, and then pressurize. To 

purge  the  coils:  slightly  loosen  the  vent  screws.  The 

installation can then operate.

NOTE: Do not turn on unless all the 42GR ATM are connected 

and earthed.

3.2 - Connection of fresh air

Fresh air (optional) can be connected either to the suspension 

box or to the ATM depending on the adjustment selected.

3.2.1 - Fresh air to suspension box

3.2.1.1 - 

Case of the constant fresh air flow suspension 

box (fig. 8)

This multipurpose box is provided to receive the regulators for 

constant fresh air flow (See 4.5.1 – Regulator for constant fresh 

air flow). The use of this box enables the treatment of fresh air 

through the battery and the filter of the ATM.
This box is provided with a ferrule for connection and a flexible 

duct of maximum length 700 mm ø 160 mm.

3.2.1.2 - 

Case of the variable fresh air flow suspension box 

(fig. 9)

The use of this box enables the treatment of fresh air through the 

battery of the ATM. This fresh air flow can be adjusted using the 

Carrier regulator (See 4.5.2 – Regulator for variable fresh air flow).
This box is provided with duct connection. Carrier recommends 

the installation of a semi-rigid circular cross-section duct of 250 

mm length and a minimum static pressure of 180 Pa upstream of 

the fresh air flow regulator.

3.2.1.3 - 

Case of the standard suspension box (fig. 10)

In this adjustment, the box does not have a fresh air inlet. However, 

fresh air intake can be ensured through the air treatment module 

(ATM) (See 3.2.2 – Fresh air in ATM).

3.2.2 - Fresh air in ATM (Fig 11)

Fresh air is connected to the ATM through the fan access door 

(Fig.11c). Three adjustments of the fresh air flow are possible:

 

-

Only ferrule for connection ø 125 mm (without fresh air flow 

regulator), air duct provided.

 

-

Ferrule  for  connection  with  fixed  constant  fresh  air  flow 

regulator  (See  4.5.1.1  –Fixed  constant  fresh  air  flow 

regulator).  This  latter  is  inserted  into  a  flexible  duct  of 

maximum length 450 mm ø 75 mm.

 

-

Ferrule for connection with adjustable constant fresh air flow 

regulator (See 4.5.1.2 – Adjustable constant fresh air flow 

regulator).  This  latter  is  inserted  into  a  flexible  duct  of 

maximum length 450 mm ø 125 mm.

NOTE: Each duct is provided with a clamp facilitating the 

mounting of the latter on the manifold of the main supply.

13

Summary of Contents for Idrofan 42GR ATM

Page 1: ...I N S TA L L AT I O N I N S T R U C T I O N S Original document AIR TREATMENT MODULE 42GR ATM...

Page 2: ......

Page 3: ...ONSIDERATIONS 12 2 1 General points 12 2 2 Protection against electrocution 12 2 3 General recommendations for installation 12 2 4 Recommendation regarding the regulation 12 2 5 Regulations 12 3 INSTA...

Page 4: ...B C D 4a 4b 4c E 2000 125 12 5 250 480 518 480 11 19 9 500 500 500 250 5a 125 F 4...

Page 5: ...6k 6f 6f 6f 6e 6i 6d 6b 6a 6g 6h 6c E B A C D 6j 6e A B C D E F 42 GR T19 334 585 895 1138 805 12 5 42 GR T29 416 585 895 1138 805 12 5 G 7b 7c 7a 22 17 50 15 50 30 50 100 mm H 5...

Page 6: ...B A D 8a C L E G H I J F K J A B C D E F G H I J K L 42 GR T19 90 107 137 125 230 159 93 58 250 93 177 250 42 GR T29 90 147 267 125 230 199 122 170 420 120 160 250 B A D 9a C L E G H I J F K A C E F...

Page 7: ...E F G H I J 42 GR T19 250 402 198 674 128 742 344 600 183 75 125 42 GR T29 420 402 198 674 128 742 344 600 183 75 125 11a 11b 11c L B C 450 max J H G F I D E C L 12c 12b 12d 12a M 0 10 V 230 V N E B...

Page 8: ...P 15a 15b O 14c 14b 14a 16b 16c 16e 16d 16a 16f Q 17c 17b 17a 17d R 8...

Page 9: ...MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR90 25 90 3 2 2 2 MR100 28 100 2 1 2 1 MR105 29 105 2 1 1 1 MR110 31 110 1 1 1 1 MR120 33 120 3 3 MR130 36 130 2 1 MR140 39 140 1 1 MR160 44...

Page 10: ...12d Fan motor N LEC vitesse variable wires nus 1 Phase 230 V brown wire 2 Neutral 230 V blue wire 3 Earthing green and yellow wire 4 0 10 V yellow wire 5 GND blue wire O Replacement of the electric b...

Page 11: ...ling and corrosion The water circuit must include components required for the treatment of water lters additives intermediate exchangers purges vents isolating valves etc depending on the results of t...

Page 12: ...blue brown green yellow and its cross section and type must comply with the specifications set out by the applicable EN or IEC standard Refer to the selection sheet or the name plate to determine the...

Page 13: ...Then connect the hydraulic hoses Connect the condensate drains of the ATM Fig 7 using a fastener for exible tube of inner 16 mm Fig 7a To avoid the emergence of odour it is MANDATORY to install a siph...

Page 14: ...ded with check valves provide a container making it possible to drain the battery Disconnect the condensate drain pipes Disconnect the fresh air supply in the case where it is xed to the ATM See 3 2 2...

Page 15: ...the Size 19 42GR ATM the electric battery is located in the suction eye of the fan motor CAUTION Before any intervention on this product it is imperative to cut the electrical power supply of the unit...

Page 16: ...of regulator enables bringing in fresh air ow from 30 m3 h 8 3 l s 10 20 Procedure for replacement of the xed constant fresh air ow regulator Disconnect the exible fresh air duct Fig 11a from the fer...

Page 17: ...e body on the battery put new seals Reinstall the servomotors taking care to see that they are correctly calamped onto the valve body Reconnect the hydraulic hoses by screwing back the G 1 2 rotating...

Page 18: ...t A TOR 230V C 3 pts 230V Digit 13 Without Probe C Change over Digit 16 W WC VARIABLE Digit 14 A F5 K F6 P F7 Active carbon S Filter UVPCO Digit 15 Without X SPECIAL J Only ferrule without regulator K...

Page 19: ......

Page 20: ...2021 replaces No 14243 03 2014 The manufacturer reserves the right to modify the product specifications without prior notice Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in th...

Reviews: