background image

4.9.1 - 

Optional balancing valves

Two-way  valve  with  water  flow  balancing  function  is 

embedded with a differential pressure controller (with 

or without pressure test points to control the water flow 

settings). The setting of the valve is shown in Fig. 16.

The manual control knob (16a) is ready fitted to protect 

valve stem and pre-set mechanism and facilitates 

manual control of valve during commissioning.
Setting procedure:

 

- Remove control knob from the valve (16a)

 

- Loosen knurled nut (16b).

 

-

Adjust the desired dial setting with the white knob 

(16c) - see table below.

 

- Retighten knurled nut by hand (16d).

WARNING: The valves have to be open when 

flushing  or  pressure  testing  the  system.  Strong 

pressure impacts can damage closed valves.

Differential pressure across the valve’s control path 

is not allowed to exceed 400 kPa.

4.9.2 - 

230 V - Actuators

Two types of valve actuators are provided: electro 

thermal actuator (on/off control) or modulating actuator 

(3-point).
The actuator supply is 230 V a.c.

4.9.3 - 

24 V - Actuators

Three types of valve actuators are provided: one electro 

thermal actuator (on/off control) or two modulating 

actuators (3-point or 0-10V).
Both modulating actuators can be operated manually 

with a hexagonal key. The 0-10V command voltage 

range of the modulating actuator can also be adjusted.

The actuator supply is 24 V a.c.

NOTE: 24V actuators are not compatible with Carrier 

controllers (Thermostats A/B/C/D, WTC & NTC).

4.9.4 - Actuator replacement procedure

The actuators on both the chilled water and the hot water 

valves may be replaced in case of failure.

WARNING: Do not connect on the same neutral wire 

the valve actuator 24 Vac and the controller.

 

- Disconnect the power supply to the unit before 

carrying out any work on a unit.

 

- Disconnect the actuator power supply cable.

•  230 V type actuator used with the Carrier 

numeric controller: Disconnect the actuator 

power supply cable fitted with a quick connector.

•  230 V actuator used with an electronic 

thermostat: Remove the plastic protection cover 

held in place with two screws. Disconnect the 

actuator power supply cable connected to the 

quick connector. This can be done by pressing 

down the spring tongue using a screwdriver and 

pulling out the wire from the appropriate terminal.

 

-

Uncouple  the  faulty  actuator.  Refitting  is  by  the 

reversal of the procedure described above.

WARNING: Ensure that the actuator is firmly screwed 

to the valve body (maximum torque 15 N·m).

4.9.5 - 

Valve body replacement procedure

 

- Disconnect the power supply before carrying out 

any work on a unit.

 

- Close the isolating valves on the manifolds.

 

-

Remove flexible water pipes.

 

- Remove the valve actuators taking care to identify 

the cooling and heating valves.

 -

Disconnect the flexible condensate drain pipe which 

is held in place by a collar (the collar is not supplied 

by Carrier).Remove the two-way or four-way water 

flow control valve bodies. Depending how the unit is 

configured, the four-way valve coupling may be fitted 

with a heating/cooling changeover switch, if so do 

not remove it.

 

-

Fit the new valve body to the coil (fit new gaskets).

 

-

Reconnect  the  flexible  condensate  drain  pipe 

which is held in place by a collar (the collar is not 

supplied by Carrier).

 

-

Refit the valve actuators taking care to ensure that 

they are correctly fixed to the valve body.

 

-

Reconnect the flexible water pipes by tightening 

the union nuts. Retighten all the water connections 

and ensure that all gaskets have been changed 

and correctly fitted (maximum torque 15 N·m).

 

- Open the isolating valves on the manifolds and 

purge all air from the system.

 

- Check that there are no leaks and reconnect the 

power to the unit.

WARNING: When replacing a valve always ensure 

that  the  direction  of  flow  through  the  valve  is  as 

shown by the arrow on the valve body. If the 

direction of flow is wrong, the valve body will 

deteriorate rapidly and the flow control will be 

distorted.

4.10  -  Flexible pipe option

 

Minimum bending radius:

 

- Non-insulated pipes 72 mm

 

- Insulated pipes 106 mm.

Connections 1/2” diameter (female)

4 - COMPONENTS AND MAINTENANCE

18

Summary of Contents for Idrofan 42EP-SIZE 0

Page 1: ...Original document Hydronic Extra Slim Ducted Fan Coil Units 42EP INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...13 2 4 Caution for the control of the unit 14 2 5 Conformity 14 3 INSTALLATION OF THE UNIT 15 3 1 Preliminary checks 15 3 2 Installing the unit in the false ceiling False floor 15 3 3 Installation pr...

Page 3: ...1 1 2 Floor unit UNIT SIZE A B C 42EP SIZE 0 914 170 50 42EP SIZE 1 1114 170 50 42EP SIZE 2 1314 170 50 Ceiling unit 2 1 Floor unit 2 2 UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZ...

Page 4: ...nit 3 1 3 2 Floor unit UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZE 2 1314 190 Ceiling unit 4 1 Floor unit 4 2 UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZE 2 13...

Page 5: ...n accordingly with type of unit model UNIT 3 L UNIT 1 Funit Fmain responsibility of the installer to ensure adequate short circuit protection of installation Fmain N L UNIT 3 N L UNIT 2 N L N L UNIT 1...

Page 6: ...Floor unit 10 a 10 b 10 2 11 a 11 a 11 6...

Page 7: ...Ceiling unit a b 12 1 Floor unit b a 12 2 a a Ceiling unit Floor unit 13 7...

Page 8: ...a b c d c 16a 16b 16c 16d 14 15 16 8...

Page 9: ...d Voir DETAIL A SEE DETAIL DETAIL A ECHELLE 3 10 a 17 18 19 9...

Page 10: ...t outlet positions all sizes a Cooling water outlet 4 and 2 pipe coil b Coolingwaterinlet 4and2 pipecoil c Heating water outlet 4 pipe coil d Heating water inlet 4 pipe coil e Air vent f water purge 1...

Page 11: ...aline character may be present The copper aluminium coil or components inside the unit could suffer irreparable corrosion damage in their presence 1 1 4 Recommended coil water quality At installation...

Page 12: ...h NOTE All performances data certified by Eurovent are based on 50Hz application Carrier doesn t ensure the same performances when the unit operates at 60Hz the RPM and power input of the fan motor ar...

Page 13: ...e control systems conform to the requirements of electromagnetic compatibility in residential commercial and light industrial areas They also comply with the low voltage directive If the product is su...

Page 14: ...type recommended by Carrier and make sure all cables are connected to the controllers and power modules 2 4 Caution for the control of the unit IMPORTANT It is not permitted to connect several units...

Page 15: ...it without any filter and with a free inlet at the same time Lift place the unit and align it on the threaded hangers insert the second nuts and tighten them slightly NOTE At this point do not tighten...

Page 16: ...e condensate drain pipe held in place by a collar the collar is not supplied by Carrier Remove the top panel Remove the coil Retrieve the drain pan by sliding it from the support During the drain pan...

Page 17: ...NOTE When installing a unit in a ceiling floor void check that no T bars will obstruct filter access and removal 4 8 Fresh air controller 4 8 1 Fresh air controller with adjustable constant air volume...

Page 18: ...V actuator used with an electronic thermostat Remove the plastic protection cover held in place with two screws Disconnect the actuator power supply cable connected to the quick connector This can be...

Page 19: ...ater pipe for cold draft function that prevents the operation of the unit when the heating network is off NOTE In case of unit with an electrical box for Carrier Thermostats a switch is provided as an...

Page 20: ...Order No EN7573046 00 12 2019 Supersedes order No New Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: