background image

3 - INSTALLATION OF THE UNIT

3.1 - 

Preliminary checks

For all procedures, switch off the unit power supply 

at the isolator provided for the purpose during 

installation (isolator not supplied by Carrier).
CAUTION: After disconnecting power supply, keep 

the unit idle for 15-20min to cool heating circuit 

temperature

 

- Disconnect the power supply and connection 

cables.

 

- Close the isolating valves on the manifolds.

 

-

Disconnect the flexible water pipes by unscrewing 

the gas connectors.

WARNING:  Since  the  flexible  water  pipes  do  not 

have drain valves, a receiver must be provided to 

allow the cooling coil to be drained.

 

- Disconnect the supply air ducts.

 

-

Disconnect  the  flexible  condensate  drain  pipe. 

Drain the siphon into a suitable vessel.

 

- Support the unit lightly and release it by unscrewing 

the four nuts on the threaded hangers. Lower or 

lift the unit carefully according to unit type (floor 

or ceiling).

3.2 - 

Installing the unit in the false ceiling 

/ False floor

The positioning of the unit must not create an obstacle 

that may lead to an unequal distribution and/or return 

flow of the air. The ceiling/floor must be sufficiently even 

to allow a simple installation without danger from the 

unit. The supporting structure must be able to carry the 

unit weight and prevent deformation, breaks or 

vibrations during operation.

INSTALLATION PRECAUTIONS: During the 

installation process, remove all debris and 

construction material from the ducts to prevent any 

damage to the unit.

3.3 - Installation procedure

NOTE: The fan-coil units are delivered upside down 

when stacked on a pallet.

 

- Place the unit close to where it will be installed. 

For installation in a false floor/ceiling use a 

hydraulic lift and a folding ladder to make the task 

easier (Fig. 9).

 

- Check that the clearances around the unit are 

sufficient to allow easy maintenance. Please refer 

to the diagram that shows the service clearances.

 

- Mark the position of the threaded hangers on the 

floor/ceiling (if several units need to be installed, 

it may be advisable to produce a drilling template). 

The method of fixing the threaded hangers (not 

supplied by Carrier) depends on the ceiling/floor 

type (maximum diameter of the threaded hangers 

is 10 mm). Once the threaded hangers are fixed 

to the ceiling, tighten the first nuts.

WARNING: When moving the units, do not use water 

pipes, condensate drain pan, valves or flexible pipes 

to lift them.

‘Without  filter’  unit  must  be  connected  to  an  air 

ductwork. It is not allowed to operate the unit without 

any filter and with a free inlet at the same time.

Lift/place the unit and align it on the threaded hangers, 

insert the second nuts and tighten them slightly

NOTE: At this point do not tighten the nuts fully and 

do not clamp the unit up to the ceiling or on the floor 

(leave  a  space  between  the  ceiling/floor  and  the 

unit). The nuts will be adjusted finally, when the unit 

has been connected to the pipework and ducts and 

levelled.
Level the unit according images section (Fig.10)

.

Adjust the hanger nuts so that the unit is inclined 0.5% 

towards the condensate drain pan. In the other direction 

(air flow direction) the unit must be perfectly level (Fig.10).
Condensate drain pipe (Fig. 11): Use a flexible pipe with an 

inside diameter of 16 mm and provide a constant fall of 20 

mm/m over the whole horizontal pipe run. Install a 50 mm 

(minimum) siphon to prevent gases and odors from flowing 

back into the ceiling/floor void.

WARNING: After drain pipe connection, control 

clamping of the drain pipe and be sure there is no 

water leakage.

If several units are connected to a common collector, a 

device must be installed (Fig. 13). Before operating the 

unit, ensure that the water flows into the internal 

condensate drain pan by pouring some water into it. If 

problems are detected, check the drain pipe slope and 

look for possible obstructions. In all cases the 

connection duct(s) at the unit outlet must be insulated 

to prevent any condensation on the walls.

NOTE: The pressure losses of these ducts must be 

compatible  with  the  unit  performance.  The  duct 

must be as smooth as possible. Avoid sharp bends. 

Check that there are no leaks or kinks, and that there 

is  no  dirt  or  installation  debris  inside  the  ducts. 

Debris within the ducts might damage the fan wheel 

and the damper in the air diffusers.

Once installation is complete - i.e. when the unit is 

attached to the ceiling/floor, air ducts are complete, water 

manifolds are in position with stop valves ready on the 

connection stubs, and electrical installation is prepared; 

then connect the water pipe (1/2” gas screw connector).

WARNING: Be sure that the coil protective caps are 

removed before connecting the water pipes (see 

Fig.19). 
NOTE: Each fan-coil units shall be connected with 

water flexible pipes in order to avoid any damage 

due to vibrations.

Ensure that a gasket (not supplied by Carrier) is installed 

between the screw connector and the stop valve.
When all units are installed, open the stop valves on 

the manifolds, bleed and then pressurize the circuits. 

To bleed the coils, slightly loosen the purge screws. The 

installation can then be started

NOTE:  Do  not  switch  on  the  power  until  all 

connections are made and earthed.

15

Summary of Contents for Idrofan 42EP-SIZE 0

Page 1: ...Original document Hydronic Extra Slim Ducted Fan Coil Units 42EP INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...13 2 4 Caution for the control of the unit 14 2 5 Conformity 14 3 INSTALLATION OF THE UNIT 15 3 1 Preliminary checks 15 3 2 Installing the unit in the false ceiling False floor 15 3 3 Installation pr...

Page 3: ...1 1 2 Floor unit UNIT SIZE A B C 42EP SIZE 0 914 170 50 42EP SIZE 1 1114 170 50 42EP SIZE 2 1314 170 50 Ceiling unit 2 1 Floor unit 2 2 UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZ...

Page 4: ...nit 3 1 3 2 Floor unit UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZE 2 1314 190 Ceiling unit 4 1 Floor unit 4 2 UNIT SIZE A B 42EP SIZE 0 914 190 42EP SIZE 1 1114 190 42EP SIZE 2 13...

Page 5: ...n accordingly with type of unit model UNIT 3 L UNIT 1 Funit Fmain responsibility of the installer to ensure adequate short circuit protection of installation Fmain N L UNIT 3 N L UNIT 2 N L N L UNIT 1...

Page 6: ...Floor unit 10 a 10 b 10 2 11 a 11 a 11 6...

Page 7: ...Ceiling unit a b 12 1 Floor unit b a 12 2 a a Ceiling unit Floor unit 13 7...

Page 8: ...a b c d c 16a 16b 16c 16d 14 15 16 8...

Page 9: ...d Voir DETAIL A SEE DETAIL DETAIL A ECHELLE 3 10 a 17 18 19 9...

Page 10: ...t outlet positions all sizes a Cooling water outlet 4 and 2 pipe coil b Coolingwaterinlet 4and2 pipecoil c Heating water outlet 4 pipe coil d Heating water inlet 4 pipe coil e Air vent f water purge 1...

Page 11: ...aline character may be present The copper aluminium coil or components inside the unit could suffer irreparable corrosion damage in their presence 1 1 4 Recommended coil water quality At installation...

Page 12: ...h NOTE All performances data certified by Eurovent are based on 50Hz application Carrier doesn t ensure the same performances when the unit operates at 60Hz the RPM and power input of the fan motor ar...

Page 13: ...e control systems conform to the requirements of electromagnetic compatibility in residential commercial and light industrial areas They also comply with the low voltage directive If the product is su...

Page 14: ...type recommended by Carrier and make sure all cables are connected to the controllers and power modules 2 4 Caution for the control of the unit IMPORTANT It is not permitted to connect several units...

Page 15: ...it without any filter and with a free inlet at the same time Lift place the unit and align it on the threaded hangers insert the second nuts and tighten them slightly NOTE At this point do not tighten...

Page 16: ...e condensate drain pipe held in place by a collar the collar is not supplied by Carrier Remove the top panel Remove the coil Retrieve the drain pan by sliding it from the support During the drain pan...

Page 17: ...NOTE When installing a unit in a ceiling floor void check that no T bars will obstruct filter access and removal 4 8 Fresh air controller 4 8 1 Fresh air controller with adjustable constant air volume...

Page 18: ...V actuator used with an electronic thermostat Remove the plastic protection cover held in place with two screws Disconnect the actuator power supply cable connected to the quick connector This can be...

Page 19: ...ater pipe for cold draft function that prevents the operation of the unit when the heating network is off NOTE In case of unit with an electrical box for Carrier Thermostats a switch is provided as an...

Page 20: ...Order No EN7573046 00 12 2019 Supersedes order No New Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: