Troubleshooting
MPC Open XP
MPC Open XP IO48/816
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
All rights reserved
33
To replace the fuse:
1
Turn
off
the MPC Open XP's power.
2
If the fuse is on an expander, remove the coverplate.
3
Using needle-nose pliers, pull the bad fuse from the MPC Open XP.
4
Cut the wires on the new fuse so that the total length is approximately 1 inch and the fuse is centered.
1 inch
5
Bend the wire ends so that the length is approximately 1/2 inch.
inch
2
1/
6
Use the pliers to grip one wire end of the fuse and push into a fuse socket on the MPC Open XP.
7
Grip the other wire end of the fuse and push into the other fuse socket.
8
If working on an expander, replace the coverplate.
9
Turn on the power and verify that the Power LED is lit.