6
Protection
Incoming power - 2 replaceable 3 Amp Pico
®
fuses
Power, network, I/O connections - protected against voltage transient and surge
events
Status indicators
LED's indicate status of communications, running, errors, and outputs
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
NOTE
Install in a UL Listed enclosure only.
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged aluminum cover, removable screw-type terminal blocks
Overall dimensions
A:
B:
9 in. (22.9 cm)
4-13/16 in. (12.2 cm)
Mounting dimensions
(in a panel)
C:
D:
E:
F:
8-5/8 in. (21.8 cm)
1 in. (2.5 cm)
2-13/16 in (7.1 cm)
1/4 in. (.6 cm)
Depth
1-7/16 in. (3.7 cm)
Weight
13.3 oz. (.377 kg)
Listed by
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
Safety considerations
WARNING
Disconnect electrical power to the MPC Open XP before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.