background image

5

5˝ø 

65 

CFM

5˝ø 

64 

CFM

4˝ø 

42 

CFM

4˝ø 

42 

CFM

4˝ø 

42 

CFM

6˝ø 

96 

CFM

6˝ø 

84 

CFM

6˝ø 

138 

CFM

7˝ø 

222 

CFM

7˝ø 

222 

CFM

6˝ø 

93 

CFM

6˝ø 

129 

CFM

A12289

Fig. 9 - Example of a design for a fully ducted system for a unit having a high speed performance of 222 cfm

Installing the Ductwork and the Registers

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Never install a stale air exhaust register in a room where there

is a combustion device, such as a gas furnace, a gas water

heater or a fireplace.

!

WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
The ductwork is intended to be installed in compliance with

all local and national codes that are applicable.

CAUTION

!

Fully Ducted System

STALE AIR EXHAUST DUCTWORK:

S

Install registers in areas where contaminants are produced:

Kitchen, bathrooms, laundry room, etc.

S

Install registers 6 to 12 inches (152 to 305 mm) from the ceiling

on an interior wall OR install them in the ceiling.

S

Install the kitchen register at least 4 feet (1.2 m) from the range.

S

If possible, measure the velocity of the air flowing through the

registers. If the velocity is higher than 400 ft/min. (122 m/min),
then the register type is too small. Replace with a larger one.

FRESH AIR DISTRIBUTION DUCTWORK:

S

Install registers in bedrooms, dining room, living room and
basement.

S

Install registers either in the ceiling or high on the walls with air
flow directed towards the ceiling. (The cooler air will then cross

the upper part of the room, and mix with room air before
descending to occupant level.)

S

If a register must be floor installed, direct the air flow up the wall.

Exhaust Ducted System

STALE AIR EXHAUST DUCTWORK:

Same as for Fully Ducted System above.

FRESH AIR DISTRIBUTION:

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When performing duct connection to the furnace, installation

must be done in accordance with all applicable codes and

standards. Please refer to your local building code.

!

WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When performing duct connection to the furnace supply duct,

this duct must be sized to support the additional airflow

produced by the ERV/HRV. Also, use a metal duct. It is

recommended that the ERV/HRV is running when the furnace

is in operation in order to prevent backdrafting inside

ERV/HRV.

CAUTION

!

There are two methods for connecting the unit to the furnace:
METHOD 1: SUPPLY SIDE CONNECTION

S

Cut an opening into the furnace supply duct at least 18 inches (0.5

m) from the furnace.

S

Connect this opening to the fresh air distribution port of the
HRV/ERV (use metal duct). See Fig. 10.

M

ETAL

 

DUCT

M

INIMUM

18’’ (0.5 

M

)

A12290

Fig. 10 - Supply Side Connection

Summary of Contents for HRVXXLHB

Page 1: ...taller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Page 2: ...orced air heating See Fig 2 Moist stale air is exhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to the cold air return or the supply...

Page 3: ...Remove parts bag from inside unit File claim with shipping company if shipment is damaged or incomplete Select Location The HRV should be located in a conditioned space and in close proximity to a fu...

Page 4: ...es two exhaust registers one for the kitchen one for the bathroom I will connect these registers to a main duct which will connect to the unit high speed performance value of 140 cfm What size of duct...

Page 5: ...N DUCTWORK S Install registers in bedrooms dining room living room and basement S Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling The cooler air...

Page 6: ...HRV CAUTION There are two methods for connecting the unit to the furnace ducts See Fig 12 and 13 B A METAL DUCT MINIMUM 18 0 5 M A B NOT LESS THAN 10 3 1 M A12292 Fig 12 Method 1 Return Supply MINIMUM...

Page 7: ...ect the rigid ducts to the ports IMPORTANT Do not use screws to connect rigid ducts to the ports Make sure that both balancing dampers are left in a fully open position before connecting the ducts to...

Page 8: ...ntrol will override the optional main control Refer to table below to see how to operate the unit using its integrated control PRESS ON PUSH BUTTON LED COLOR RESULTS Once Amber Unit is on Low Speed Tw...

Page 9: ...ight dimming circuits electrical motors dwelling building power or lighting wiring or power distribution panel Use the terminal connector included in the installation kit to perform the electrical con...

Page 10: ...losed to outside Off Low Air exchange with outside Open to outside Low Intermittent 40 min off 20 min exchange low speed Air exchange with outside Open to outside 20 min Closed 40 min Low Off High Air...

Page 11: ...idity and outdoor temperature It may cycle on off every 30 minutes depending on humidity and outside temperature LOW low speed all of the time HIGH high speed all of the time DEHUM will only turn on i...

Page 12: ...ng the unit in you are assured that the unit is not in a defrost cycle 2 Place the magnehelic gauge on a level surface and adjust it to zero A11217 Fig 30 Magnehelic Gauge A12307 Fig 31 Open Balancing...

Page 13: ...14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 ICP BK Y R...

Page 14: ...intense use This will ensure maximum efficiency of the plastic partitions within the core Allow heat recovery core to soak for 3 hours in a solution of warm water and mild soap Rinse under stream of...

Page 15: ...S The wires may be broken S Inspect every wire and replace any that are damaged S The wire in the wall OR the wall S Remove the wall control and test it right beside the unit using another control may...

Page 16: ...3 68 20 12 09 124 51 4 026 180 82 1 577 44 42 209 9 14 10 42 47 70 21 11 63 126 52 3 896 181 83 1 533 43 41 198 9 16 9 40 57 72 22 11 20 128 53 3 771 183 84 1 492 40 40 188 5 18 8 38 77 73 23 10 78 12...

Reviews: