23
Table 12 – Blower Performance Data -- Variable Speed Constant CFM
Models
Min Airflow (CFM)
Airflow Settings
CFM From Communicating Wall Control
Heating
Cooling
024 --- Low
450
Max
714
714
EFF 1
580
580
EFF 2
625
625
COM
532
531
QUIET
N/A
455
024 --- High
612
Max
971
971
EFF 1
789
789
EFF 2
850
850
COM
724
723
QUIET
N/A
619
036 --- Low
738
Max
1171
1171
EFF 1
952
952
EFF 2
1025
1025
COM
872
871
QUIET
N/A
747
036 --- High
900
Max
1429
1429
EFF 1
1161
1161
EFF 2
1250
1250
COM
1064
1063
QUIET
N/A
911
048 --- Low
936
Max
1486
1486
EFF 1
1207
1207
EFF 2
1300
1300
COM
1107
1105
QUIET
N/A
947
048 --- High
1080
Max
1714
1714
EFF 1
1393
1393
EFF 2
1500
1500
COM
1277
1275
QUIET
N/A
1093
060 --- Low
1044
Max
1657
1657
EFF 1
1346
1346
EFF 2
1450
1450
COM
1234
1233
QUIET
N/A
1056
060 --- High
1224
Max
1943
1943
EFF 1
1579
1579
EFF 2
1700
1700
COM
1447
1445
QUIET
N/A
1239
072 --- Low
1152
Max
1829
1829
EFF 1
1486
1486
EFF 2
1600
1600
COM
1362
1360
QUIET
N/A
1166
072 --- High
1368
Max
2171
2171
EFF 1
1764
1764
EFF 2
1900
1900
COM
1617
1615
QUIET
N/A
1384
NOTES
: --- CFM based on standard air conditions at 0.5” w.c. external static pressure with 2” MERV 13 filter.