Engineering Guide Specifi cations

General

The water-source heating units shall be high temperature water-to-
water heat pumps. Units shall be performance rated in accordance 
with EN 14511-2 or ARI/ISO/ASHRAE 13256-2, and listed by a 
recognized safety-testing laboratory or agency, such as ETL. Each unit 
shall be water run-tested at the factory. The quality control system 
shall automatically perform via computer: triple leak check, pressure 
tests, evacuate and accurately charge system, perform detailed 
heating mode tests, and quality cross check all operational and test 
conditions to pass/fail data base. Each unit shall be pallet mounted 
and shipped with appropriate protective packaging to help avoid 
damage in transportation. 

The units shall be warranted by the manufacturer against defects 
in materials and workmanship for a period of 10 years on all parts, 
and 10 years on the compressor and refrigerant circuit parts with a 
service labor allowance for 5 years on refrigeration components and 
2 years on other parts. An optional extended warranty is available 
for the 50YEW Series units, which increases the labor allowance to 
10 years on all parts. The water source units shall be designed to 
operate with entering Source temperature between 20 and 110°F 
[-7 and 43°C], and entering Load temperature between 50 and 
130°F [10 and 54°C] with a maximum leaving load temperature of 
145°F [63°C].
 

Casing & Cabinet

The cabinet shall be fabricated from heavy-gauge galvanized steel and 
painted with a polyester powder coating. Access door shall be hinged 
for easy access. The interior shall be insulated with 1/2” [13mm] 
thick, multi-density, foil-backed coated glass fi ber.  Three access panels 
shall be provided and shall be removable with piping in place. The 
internal component layout shall provide for major service with the 
unit in place for restricted access installations. The units shall have 
an insulated compressor section to minimize the transmission of 
compressor noise.

Refrigerant Circuit

All units shall contain Puron

®

 (HFC-410A) sealed refrigerant circuit 

employing a hermetic motor-compressor, thermal expansion valve, 
coaxial tube water-to-refrigerant Source heat exchanger, brazed plate 
Load heat exchanger, compressor discharge muffl er, 100% molecular 
sieve fi lter drier with XH-11 desiccant, and service ports. An optional 
Domestic Hot Water mode shall be available. Compressors shall be 
scroll type designed for heat pump duty and shall be double isolated 
from the cabinet with two sets of compressor mounting hardware. 
Compressor motors shall be single-phase PSC with internal over 
load protection. 

The coaxial water-to-refrigerant heat exchangers shall be designed 
for close approach temperatures and be constructed of a convoluted 
copper (optional cupro-nickel) inner tube and steel outer tube. The 
brazed plate heat exchanger shall be designed for close approach 
temperatures and shall be constructed with stainless steel plates. The 
thermal expansion valve shall provide proper superheat over the 
entire fl uid temperature range with minimal “hunting”. The coaxial 
heat exchangers and refrigerant suction lines shall be insulated to 
prevent condensation at low liquid temperatures.

Electrical

CXM Control – A microprocessor-based compressor controller 
shall be provided to monitor and control unit operation. The control 
shall provide compressor enable, high and low pressure monitoring, 
fi eld selectable water coil low temperature sensing, and over/under 
voltage monitoring. The control shall also provide for water valve 
connection, a test mode, short cycle protection, random start-
up, as well as fault LED, fault memory, and intelligent fault retry. 
The control shall employ quick attach harness assemblies for low 
voltage connections to the control board to aid in troubleshooting 
or replacement. An integral terminal block with screw terminals 
shall be provided on the control for connection to other low 
voltage controls. The control system microprocessor board shall be 
specifi cally designed to protect against building electrical system noise 
contamination, EMI, and RFI interference.

MPC Control – A programmable controller shall be provided to 
monitor buffer tank temperature, Domestic Hot Water (DHW) 
tank temperature, outdoor air temperature, and other inputs to 
determine when to operate the compressor, pump(s) and hot water 
valve.  The MPC shall be factory-wired to the CXM compressor 
control module and user interface.  MPC programming shall include 
outdoor temperature reset, warm weather shutdown, cooling enable, 
heat pump staging, emergency DHW output, pump control, vacation 
mode, DHW time schedule, advanced diagnostics, user interface 
communication, and sensor monitoring.

Digital User Interface – A panel-mounted backlit digital user interface 
shall be factory installed and wired for customization of the MPC 
programming.  Four arrow keys and a select key will be used to 
control a large dot-matrix style 2” x 2” (5 x 5 cm) backlit display.  The 
main screen shall display current outdoor and water temperatures, 
and allow the user to change settings by selecting from one of 
the menus at the bottom of the screen.  A special installer set up 
mode will allow the technician to change some of the default MPC 
parameters.  The user interface shall include a time schedule for 
DHW operation, Fahrenheit/Celsius selection, vacation mode for 
DHW, and other user preference options.

12-point terminal block – A low voltage terminal block with a blue/
gray pattern for ease of identifi cation shall be provided to connect 
thermistors and external wiring.  The MPC, user interface, CXM 
board and other relays/components shall be factory-wired to the 
terminal block.

Line voltage lugs shall be provided for unit wiring. A circuit breaker 
protected 75VA transformer shall be employed. Units shall have 
knockouts for entrance of low and line voltage wiring. 

Piping

Source/Load supply and return water connections, as well as 
Domestic Hot Water supply and return connections shall be FPT 
(Female Pipe Thread) copper fi ttings and shall be securely mounted 
fl ush to the cabinet allowing for connection to an MPT (Male Pipe 
Thread) fi tting without the use of a back-up wrench. All Source 
water piping shall be insulated to prevent condensation at low liquid 
temperatures.

50YEW

20

GT-PW Water-to-Water (50YEW) Series

Carrier : Turn to the Experts.

Summary of Contents for GT-PW

Page 1: ...GT PW 50YEW Water To Water Series WATER TO WATER PURON SYSTEMS SIZE 010 10 kW Revised May 8 2013...

Page 2: ...Efficiencies 6 Performance Data 7 Physical Data 9 Dimensions 10 Electrical Data 11 Wiring Diagrams 12 Engineering Guide Specifications 20 Accessories Options 21 Warranty Information 21 Revision Histor...

Page 3: ...of installation and service Galvanized steel construction with protective powder coat paint and hinged front access door Bi directional thermal expansion valve Puron HFC 410A zero ozone depletion ref...

Page 4: ...Panel For Long Life Taupe Metallic 9 Fully Insulated Water and Refrigerant Lines 7 Optional Full Condensing Hot Water Generation With Internal Secondary Heat Exchanger and Potable Water Circulating Pu...

Page 5: ...A 0 1 0 C W 3 1 1 4 5 6 7 8 9 10 11 12 Unit Size Voltage Controls 1 Single Pack Domestic Packaging 1 Current Revision Level 1 2 3 Residential Series 010 10kW Prefix 3 208 230 60 1 D Copper Source Braz...

Page 6: ...C 104 F are based upon AHRI ISO Standard 13256 2 all other ratings are based upon Standard EN 14511 2 50YEW010 Model Ground Loop Heat Pump Ground Water Heat Pump Heating Heating Indoor 30 35 C Outdoo...

Page 7: ...30 32 1 3 92 18 7 141 8 2 6 0 3 0 7 31 0 3 82 18 0 138 5 2 4 0 7 1 6 8 3 0 7 1 7 50 48 9 1 13 45 0 68 1 12 7 0 8 1 7 49 3 1 12 49 3 63 5 12 9 1 8 4 0 70 45 5 1 83 39 2 86 8 7 3 0 6 1 4 45 9 1 73 40 0...

Page 8: ...1 120 34 2 3 64 21 8 139 8 2 8 1 7 4 0 36 3 3 27 25 1 133 6 3 3 3 5 8 0 70 6 75 0 6 1 3 50 49 5 1 96 42 8 78 1 7 4 1 9 4 3 54 1 1 79 48 0 70 0 8 9 3 7 8 6 70 46 9 2 41 38 7 96 8 5 7 1 8 4 2 51 3 2 20...

Page 9: ...Unit PSIG kPa 500 3445 DHW Option PSIG kPa 145 999 Internal Source Pump w Expansion Tank PSIG kPa 145 999 Internal Load Pump w Expansion Tank PSIG kPa 145 999 Weight Operating lbs kg 455 207 Weight Pa...

Page 10: ...Water In E Source Outdoor Water Out F Load Indoor Water In G DHW Water Out H Load Indoor Water Out J DHW Water In K Low Voltage L Low Voltage M Power Supply 010 in 26 8 25 6 48 9 3 4 8 1 22 3 11 3 17...

Page 11: ...FLA Min Circuit Amps Max Fuse HACR Qty RLA LRA THW010 G 208 230 60 1 197 254 1 20 7 81 1 07 1 07 22 8 28 45 1 07 1 07 1 07 23 9 29 1 45 Standard No DHW Model Voltage Code Voltage Min Max Voltage Comp...

Page 12: ...50YEW010 Electrical Wiring Diagram 230 60 1 96B0108N05 Electrical Wiring Diagrams 50YEW 12 GT PW Water to Water 50YEW Series Carrier Turn to the Experts...

Page 13: ...50YEW010 Electrical Wiring Diagram 230 60 1 96B0108N05 Carrier Geothermal Heat Pump Systems 50YEW 13 Residential Products Technical Guide...

Page 14: ...50YEW010 Electrical Wiring Diagram 230 60 1 VSFP 96B0108N06 50YEW 14 GT PW Water to Water 50YEW Series Carrier Turn to the Experts...

Page 15: ...50YEW010 Electrical Wiring Diagram 230 60 1 VSFP 96B0108N06 Carrier Geothermal Heat Pump Systems 50YEW 15 Residential Products Technical Guide...

Page 16: ...50YEW010 Electrical Wiring Diagram 230 60 1 DHW 96B0108N08 50YEW 16 GT PW Water to Water 50YEW Series Carrier Turn to the Experts...

Page 17: ...50YEW010 Electrical Wiring Diagram 230 60 1 DHW 96B0108N08 Carrier Geothermal Heat Pump Systems 50YEW 17 Residential Products Technical Guide...

Page 18: ...50YEW010 Electrical Wiring Diagram 230 60 1 DHW VSFP 96B0108N09 50YEW 18 GT PW Water to Water 50YEW Series Carrier Turn to the Experts...

Page 19: ...50YEW010 Electrical Wiring Diagram 230 60 1 DHW VSFP 96B0108N09 Carrier Geothermal Heat Pump Systems 50YEW 19 Residential Products Technical Guide...

Page 20: ...ng The coaxial heat exchangers and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures Electrical CXM Control A microprocessor based compressor controller s...

Page 21: ...be provided to sense the domestic water storage tank temperature Internal Source and Load Pumps Internal Expansion Tanks Optional Source pump s Load pump and expansion tank s shall be factory install...

Page 22: ...arranty Paint Nomenclature Updates 30 Mar 10 All Misc format physical data and electrical data 30 Mar 10 Decoder Page Decoder Updated 1 Mar 10 All Misc format and desc updates 15 Dec 09 All Updated Pe...

Reviews: