NOTE:

Read the entire instruction manual before starting the installation.

This symbol

indicates a change since the last issue.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance.
The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions
packaged with kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code
(NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit and in instructions manuals, be alert to

the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal

Fig. 1—Model FV4B

A98023

Installation Instructions

FV4B

Fan Coil for Puron® Refrigerant
002, 003, 005, 006

Form:

IM-FV4B-02

Cancels:

IM-FV4B-01

Printed in U.S.A.

6-03

Catalog No.

63FV-4B1

Summary of Contents for FV4B

Page 1: ...work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local buildi...

Page 2: ...orizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications Units may be converted for downflow applications usin...

Page 3: ...ide of unit and reinstall on coil support rail on right side of unit Fig 2 Slope Coil Unit in Upflow Application A00091 A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETU...

Page 4: ...e sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRA...

Page 5: ...cal pan fitting to door joint to retain the low air leak performance of the unit Failure to follow this CAUTION could result in personal injury or product and property damage In this application field...

Page 6: ...nect switch remote to the unit is turned off Failure to do so will result in electrical shock causing personal injury or death A Line Voltage Connections If unit contains an electric heater remove and...

Page 7: ...nufactured housing applications the Code of Federal Regulations Title 24 Chapter XX Part 3280 714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 deg F except f...

Page 8: ...n Coil Wiring with 1 Speed Air Conditioner A98477 O W2 Y1 W2 W W1 G R W2 Y1 INDOOR CONTROL FAN COIL 1 SPEED AIR CONDITIONER W1 G C Y C DHUM HUM B S1 S2 Y Y2 R O C DH HEAT STAGE 2 N A HEAT STAGE 1 COOL...

Page 9: ...Wiring with 1 Speed Heat Pump A98475 O W2 W W1 Y1 W2 G R O W2 INDOOR CONTROL FAN COIL 1 SPEED HEAT PUMP W1 G C Y R W2 O C DHUM HUM B S1 S2 Y Y2 R Y1 C DH HEAT STAGE 3 HEAT STAGE 2 HEAT COOL STAGE 1 R...

Page 10: ...condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See...

Page 11: ...ory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to select air conditioner or heat pump size to ensure t...

Page 12: ...ave a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden Four motor operation delay profiles are provided to customize and enhance system operation See Fig 17...

Page 13: ...AC HP CFM ADJUST Select NOM 5 ON OFF DELAY Select 0 90 profile 6 CONTINUOUS FAN Select desired fan speed when thermostat is set to continuous fan I COMFORT OPTIONS WARMER HEATING AND SUPER DEHUMIDIFY...

Page 14: ...AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 vac signal whenever the G terminal is energized See Fig 17 and 18 During Super Dehumidify and SuperC...

Page 15: ...iguration instructions If the indoor temperature is below the temperature set point and the humidity is above the humidity set point the Thermidistat closes circuit R to O opens circuits R to DH and R...

Page 16: ...60 1050 610 770 1225 700 880 1400 875 1100 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI o...

Page 17: ...LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1...

Page 18: ...SELECT BOARD 1 Unplug harness from board 2 Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered See Table 7 for values and see example below If proper signals are no...

Page 19: ...e The disconnect when used on access panel does not disconnect power to the line side of disconnect but does allow safe service to all other parts of unit If unit does not have a disconnect disregard...

Page 20: ...utor for maintenance procedures WARNING As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User...

Page 21: ...n as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Page 22: ...22...

Page 23: ...23...

Page 24: ...2003 CAC BDP 7310 W Morris St Indianapolis IN 46231 imfv4B02 24 Book Tab 1 4 3d 2e Catalog No 63FV 4B1...

Reviews: