background image

 

PMSTR-4000                         

Quick Start Tips 

September 15, 2021 

 

 

 

Page 4 

 

 

TROUBLESHOOTING MODBUS COMMUNICATION ISSUES 

Here are some common issues with Modbus wiring between the PMSTR-4000 and the 
connected units: 

  Modbus wiring is backwards – swap the wires between A+ and B- on the 

PMSTR-4000 terminal block. A+ should connect to all the terminals P12.3 (in 
series) and B- should connect to all the terminals P12.4 (in series). 

  Modbus wiring is inconsistent – some units may have the wiring connected 

backwards while others do not. This may appear as only some units 
communicating. 

  Addresses programmed into the units are not correct. These need to be set from 

1 to 8. Since these are the same addresses used from the BMS Modbus port, 
ensure that the BMS integrators know that these can’t be changed. Note that by 
default, a new unit has an address of 247. 

  One of the connected units had the LEAD/LAG key pressed on the keypad and is 

attempting to become master. This will cause interference and loss of 
communication on the Modbus network as a network can typically only have one 
master. Follow the steps described earlier in this document to disable the 
LEAD/LAG key on the keypad to prevent this. The key will highlight in green or 
flash in green when it has been pressed. 

  If the Modbus network has a long run of wiring or a lot of connected units, it may 

benefit to add a 120-ohm resistor across P12.3 and P12.4 at the last unit. This is 
referred to as a “termination resistor” and can help mitigate the impedance in the 
large run of wiring. 

 

 

Reviews: