background image

10

B. Humidifier

Connect humidifier and humidistat to fan coil unit as shown in Fig.

24 and Fig. 25. The cooling lockout relay is optional.

R

G

C

E

L

O

Y

THERMOSTAT

R

R

C

O

Y

G

C

W

2

W

2

W

2

W

3

E

FAN COIL

(CONTROL)

HEAT PUMP

(CONTROL)

RED

GRY

BRN

WHT

WHT

BLU

VIO

HUMIDISTAT

RELAY

FAN HUMIDIFIER

115V

M

A95294

Fig. 24 -- Wiring Layout of Humidifier to Heat Pump

R

G

W

Y

THERMOSTAT

R

G

W

2

W

3

E

C

FAN COIL

(CONTROL)

C

Y

AIR COND.

HUMIDISTAT

FAN HUMIDIFIER

115V

RED

GRY

WHT

WHT

BLU

VIO

BRN

M

A95295

Fig. 25 -- Wiring Layout of Humidifier to Fan Coil

With Electric Heat

Step 9 — Sequence of Operation

A. Continuous Fan

Thermostat closes R to G. G energizes fan relay on PCB which

completes circuit to indoor blower motor. When G is de--energized,
there is a 90--sec delay before relay opens.

B. Cooling Mode

Thermostat energizes R to G, R to Y, and R to O (heat pump only).

G energizes fan relay on PCB which completes circuit to indoor

blower motor. When G is de--energized, there is a 90--sec delay
before fan relay opens.

C. Heat Pump Heating with Auxiliary Electric Heat

Thermostat energizes R to G, R to Y, and R to W. G energizes fan

relay on PCB which completes circuit to indoor blower motor. W
energizes electric heat relay(s) which completes circuit to heater

element(s). When W is de--energized, electric heat relay(s) open,
turning off heater elements. When G is de--energized there is a

90--sec delay before fan relay opens.

D. Electric Heat or Emergency Heat Mode

Thermostat closes R to W. W energizes electric heat relay(s) which

completes circuit to heater element(s). Blower motor is energized
through normally closed contacts on fan relay. When W is

de--energized, electric heat relay(s) opens.

START--UP PROCEDURES

Refer to outdoor unit Installation Instructions for system start--up

instructions and refrigerant charging method details.

UNIT COMPONENT HAZARD

Failure to follow this caution may result in product damage.
Never operate unit without a filter. Damage to blower motor

or coil may result. Factory authorized filter kits must be used

when locating the filter inside the unit. For those applications

where access to an internal filter is impractical, a

field--supplied filter must be installed in the return duct

system.

CAUTION

!

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment
failure, it is essential that periodic maintenance be performed on

this equipment. Consult your local dealer as to the proper
frequency of maintenance contract.
The ability to properly perform maintenance on this equipment
requires certain mechanical skills and tools. If you do not possess

these, contact your dealer for maintenance. The only consumer

service recommended or required is filter replacement or cleaning
on a monthly basis.

FB

4C

/F

Y5

B

Summary of Contents for fb4c

Page 1: ...ost serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation ELECTRICAL OPERATION HAZARD Fa...

Page 2: ...E A07565 Fig 1 Slope Coil Unit in Upflow Application B Downflow Installation In this application field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit Use fireproof resilient gasket 1 8 to 1 4 in 3 to 6 mm thick between duct unit and floor UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage Th...

Page 3: ...er kit instructions 8 Align holes with tubing connections and condensate pan connections and reinstall access panels and fitting panel Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating Install after brazing COIL MOUNTING SCREW BLOWER ASSEMBLY REFRIGERANT CONNECTIONS SECONDARY DRAIN PRIMARY DRAIN DRAINPAN SLOPE COIL SKI COIL SUPPORT RAIL A03001 Fig 5 ...

Page 4: ...3 mm thick right angle brackets Attach brackets to fan coil using no 10 self tapping screws and to wall stud using 5 16 in lag screws See Fig 8 Step 3 Air Ducts Connect supply air duct over the outside of 3 4 in 19 mm flanges provided on supply air opening Secure duct to flange using proper fasteners for type of duct used and seal duct to unit joint If return air flanges are required install facto...

Page 5: ...ard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness See Electric Heater Installation Instructions For units without electric heater 1 Connect 208 230v power leads from field disconnect to yel low and black stripped leads 2 Connect ground wire to unit ground lug NOTE Units installed without electric heat should have a field supplied sheet metal blo...

Page 6: ... this caution may result in product or property damage If W2 W3 and E on any 3 stage heater 18 20 24 or 30kW are individually connected as with outdoor thermostats or any other situation emergency heat relay must be used This relay is in kit Part No KHOT0201SEC and is normally used with kit Part No KHAOT0301FST for 2 outdoor thermostat systems CAUTION The controls are factory circuited for single ...

Page 7: ...ctory default position and move to desired speed tap 1 2 3 or 5 Speed taps 1 2 and 3 have a 90 second blower time delay pre programmed into the motor Speed tap 4 is used for electric heat only with 0 second blower time delay and the WHITE wire must remain on tap 4 Speed tap 5 is used for high static applications but has a 0 second blower time delay pre programmed into the motor see Table 1 FB4C Ai...

Page 8: ...y exit the fitting to retain the low leak rating of the unit UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A coil and slope units The vertical drains have an overflow hole between the primary and secondary drain holes This hole is plugged...

Page 9: ...sate will be noticeable The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See Fig 21 Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from over...

Page 10: ... electric heat relay s open turning off heater elements When G is de energized there is a 90 sec delay before fan relay opens D Electric Heat or Emergency Heat Mode Thermostat closes R to W W energizes electric heat relay s which completes circuit to heater element s Blower motor is energized through normally closed contacts on fan relay When W is de energized electric heat relay s opens START UP ...

Reviews: