EVD4X, ESD4X, WMVC, WMSC: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

condensate line (with appropriate trap) should be run from the unit into

the  pan.  Any  condensate  in  this  external  condensate  pan  should  be

drained  to  a  noticeable  place. As  an  alternative  to  using  an  external

condensate  pan,  some  localities  may  allow  the  running  of  a  separate

¾-inch (19 mm) condensate line (with appropriate trap) per local code to

a  place  where  the  condensate  will  be  noticeable.  The  owner  of  the

structure must be informed that when condensate flows from secondary

drain  or  external  condensate  pan,  the  unit  requires  servicing  or  water

damage  will  occur. To  further  protect  against  water  damage,  install  a

float switch to shut the unit off if the water in the secondary pan gets too

high. 

A10216

Fig. 9 – Condensate Drain to Waste Line

Waste Line Connection

If the condensate line is to be connected to a waste (sewer) line, an open

trap must be installed ahead of the waste line to prevent escape of sewer

gases (

Fig. 9

).

Humidifier Application

When  installing  a  humidifier  in  a  system  which  contains  a  V-coil,

consideration must be given to location of coil slabs (

Fig. 10

).

1. The humidifier should be mounted to the supply plenum or return

duct whenever possible.

2. Ensure that humidifier has adequate airflow.

A200229B

Fig. 10 – Humidifier Application

Care and Maintenance

To continue high performance and minimize possible equipment failure,

it is essential that periodic maintenance be performed on this equipment.

Consult your local dealer as to the proper frequency of maintenance, but

it should be done at least annually.
The ability to properly perform maintenance on this equipment requires

certain mechanical skills and tools. If you do not possess these, contact

your dealer for maintenance. The only consumer service recommended

or required is filter replacement or cleaning on a monthly basis.

Condensate
Line

Trap

Sewer Line

Air Gap Above
Liquid Level

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental damage.
Remove and recycle all components or materials (i.e., oil, refrigerant,

etc.) before unit final disposal. 

Summary of Contents for EVD4X

Page 1: ...ath CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installati...

Page 2: ...refrigerant Use only with outdoor units designed for R 410A NOTE These TXVs are factory set at approximately 10 superheat measured at the suction service valve and are not field adjustable A210138 Fi...

Page 3: ...he factory installed foil faced insulation in the front and rear of the coil are required to prevent bypass airflow Heat shields for the condensate drain pan in upflow installations and cross members...

Page 4: ...sted and therefore full performance specifications have not been certified In instances where a not recommended installation configuration is required it is the responsibility of the installer to ensu...

Page 5: ...using field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line S...

Page 6: ...n It is highly RECCOMMENDED and in some locals is it a code requirement to install a trap on the drain line s Please use the following guidelines to assure proper drainage Install a trap in condensate...

Page 7: ...is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases Fig 9 Humidifier Application When installing a humidifier in a system...

Reviews: