Carrier DLFLDA Series Owner'S Manual Download Page 12

12

 32802000301

Specifications  subject to change without notice.

COMMON PROBLEMS

Table 3—Common Problems

PROBLEM

POSSIBLE CAUSES

Unit does not turn on when pressing ON/ OFF

The unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be
restarted within three minutes of being turned off.

Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/ Defrost) indicators are lit up,
the outdoor temperature is too cold and the unit’s anti-cold wind is activated in order to defrost the unit.

In Cooling-only Models: If the “Fan Only” indicator is lit up, the outdoor temperature is too cold and the unit’s
anti-freeze protection is activated in order to defrost the unit.

The unit changes from COOL mode to FAN mode

The unit changes its setting to prevent frost from forming on the unit. Once the temperature increases, the unit
will start operating again.

The set temperature has been reached, at which point the unit turns off the compressor. The unit will resume
operating when the temperature fluctuates again.

The indoor unit emits white mist

In humid regions, a large temperature difference between the room’s air and the conditioned air can cause
white mist.

Both the indoor and outdoor units emit white mist

When the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated
from the defrosting process.

The indoor unit makes noises

A squeaking sound is heard when the system is OFF or in COOL mode. The noise is also heard when the drain
pump (optional) is in operation.

A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the
unit’s plastic parts.

Both the indoor unit and outdoor unit make noises

A low hissing sound may occur during operation. This is normal and is caused by refrigerant gas flowing
through both the indoor and outdoor units.

A low hissing sound may be heard when the system starts, has just stopped running or is defrosting. This noise
is normal and is caused by the refrigerant gas stopping or changing direction.

The outdoor unit makes noises

The unit will make different sounds based on its current operating mode.

Dust is emitted from either the indoor or outdoor unit

The unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is
turned on. This can be mitigated by covering the unit during long periods of inactivity.

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be
emitted during operations.

The unit’s filters have become moldy and should be cleaned.

The fan of the outdoor unit does not operate

During operation, the fan speed is controlled to optimize product operation.

Table 4—Troubleshooting Tips

PROBLEM

POSSIBLE CAUSE

SOLUTION

Unit/System Does Not Work

The circuit breaker has tripped or a fuse has blown.

Power failure.

Diagnostic lights illuminate.

*

Voltage is too low

Remote control batteries are dead

The unit's 3 minute protection has been activated.

Reset the circuit breaker or replace the fuse with the specified

replacement fuse.

Restart operation when the power is restored.

Call your service representative.

Call your service representative.

Replace the remote control batteries

Wait three minutes after restarting the unit.

Poor cooling performance

The filter is blocked with dust.

Temperature is not set properly.

A window or door is open.

The outdoor unit is obstructed.

The fan speed is too low.

The operation mode is in Fan instead of Cool.

Low refrigerant due to leak or long-term use of

refrigerant.

Clean the air filter.

Check the temperature and reset if necessary.

Ensure all doors and windows are closed while operating the

unit.

Turn the unit off, remove the obstruction and turn it back on.

Change the fan speed selection.

Change the operating mode to Cool or reset the unit.

Check for leaks, re-seal if necessary and top off refrigerant.

Poor heating performance

The filter is blocked with dust.

Temperature is set too low.

A window or door is open.

The outdoor unit is obstructed.

Clean the air filter.

Check the temperature and reset if necessary.

Ensure all doors and windows are closed while operating the

unit.

Turn the unit off, remove the obstruction and turn it back on.

Unit Stops During Operation

The Off timer is not operating correctly.

Diagnostic lights illuminate.

*

Restart the operating mode.

Call your service representative.

* Diagnostic lights are a combination of lights that will illuminate in the display area on the unit. They are a combination of the lights you see during normal operation.

Copyright 2018

CMNA 1025 Cobb Place Pkwy Kennesaw, GA 30152

Summary of Contents for DLFLDA Series

Page 1: ...your new equipment in the spaces provided This information along with the installation data and dealer contact information will be helpful should your system require maintenance or service UNIT INFORM...

Page 2: ...MPORTANT The ducted fan coil unit should be installed by authorized personnel only using approved tubing and accessories If technical assistance service or repair is needed contact the installer The d...

Page 3: ...R WIRELESS REMOTE Air outlet Air inlet Air filter Drain hose field supplied Electric control cabinet Refrigerant connecting pipe field supplied ON OF F T E MP FP TIMER ON TIMER OFF MODE FAN SLC SLEEP...

Page 4: ...ll flash on the display area Then press the or button to confirm SLEEP Function This function maintains the most comfortable temperature and saves energy It is available in COOL HEAT or AUTO modes onl...

Page 5: ...compartment 3 Replace the battery compartment cover NOTE 1 When replacing batteries do not use old batteries or a different type battery This may cause the remote control to malfunction 2 If the remot...

Page 6: ...y Setting the Room Temperature Set Point Press the increase temperature set point Y and decrease B buttons to raise or lower the temperature The unit confirms the signal receipt with a beep and the va...

Page 7: ...of the unit Set the Auto On Time 1 Press the SET button The Timer on indicator displays and flashes The last Auto on setting time and the signal h shows on the LCD display area Now it is ready to res...

Page 8: ...ill show the temperature again The indicator remains on and this function is activated Combined Timer Setting both ON and OFF timers simultaneously TIMER OFF TIMER ON On Stop Start operation Fig 15 Co...

Page 9: ...trol sends this signal to the air conditioner every 3 minutes This function is not available for DRY and FAN modes Freeze Protection Mode Press FP for approximately 2 seconds to activate or deactivate...

Page 10: ...must be replaced Contact your local dealer for replacement filters 1 Unscrew filters from the frame 2 Pull filters down to remove A150678 Fig 17 Remove the Filters 3 Vacuum filters A150648 Fig 18 Vacu...

Page 11: ...OR UNIT EVERY MONTH EVERY 6 MONTHS EVERY YEAR Clean Air Filter Change Remote Control Batteries S S OUTDOOR UNIT EVERY MONTH EVERY 6 MONTHS EVERY YEAR Clean Outdoor Coil from Outside Clean Outdoor Coil...

Page 12: ...e unit may accumulate dust during extended periods of non use which will be emitted when the unit is turned on This can be mitigated by covering the unit during long periods of inactivity The unit emi...

Reviews: