Fig. 2 -- Damper Hood Panels

C07342

Fig. 3 -- Damper and Hood Panel Installation

6. Adjust the actuator limiter to limit the maximum open

position of the damper to the amount of desired ventilation

air from step 2. The adjustment is made by setting the set
screw on the end of the actuator to the desired position.
Tighten screw firmly to hold in place. (See Fig. 5--7.)

Adjustments can be made after the assembly is installed, by
removing rooftop unit’s horizontal return panel and

accessing the actuator.

7. Lift damper assembly and set in place over the top of the

bottom panel, per Fig. 3. Secure the damper assembly in

place with provided screws.

8. Remove the jumper plug shipped attached to the

economizer harness in the HVAC unit. DO NOT
DISCARD. Connect the plug from the damper actuator
assembly to the economizer plug in the HVAC unit. Set the

jumper plug aside in case it is determined at a later date that
the two position damper is no longer required, at which

time the jumper plug can be reinstalled.

C07343

Fig. 4 -- Filter Installation

C07344

Fig. 5 -- Actuator Limit Screw

9. Install the assembled outside--air hood onto the HVAC unit,

covering the damper assembly. Screw in place.

10. Install the provided aluminum filter into the hood. Lock in

place with top filter clips. (See Fig. 4.)

11. Replace the top filter access panel.
12. Remove lockout tag and restore base unit to operation.