Power Exhaust Installation for Horizontal Return

Air Applications

Use the following instructions for horizontal return air duct appli

-

cations of the power exhaust fan assembly. (See Fig. 10.)

1. A transition in the duct height is required. To assure that the

transition  required  will  accommodate  the  exhaust  opening

size begin at least 5 ft away from the back of the outside air

hood. Provide a 42.5 in. W x 23.2 in. H opening in the side of

the return air duct, as shown in Fig. 11.

NOTE: Any obstruction closer than 5 ft will interfere with

airflow and result in rain entering the hood through the filters. 

2. Provide  engagement  holes  (12)  for  1/4-14  x  3/4  in.  gasket

head screws (AL31AZ308) around the opening as shown in

Fig. 11.

3. Apply silicone caulking to corners and back side of mating

flanges of the power exhaust fan assembly.

4. Set the power exhaust hood assembly into the opening in the

duct, bottom lip first as shown in Fig. 12.

5. Lift  the  assembly  to  allow  the  bottom  corner  tabs  to  hook

over the opening in the duct work. (See Fig. 12.)

Fig. 10 — Typical Horizontal Air Return Application

Fig. 11 — Horizontal Discharge Mounting Opening

CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing, safety glasses and gloves

when handling parts and servicing air conditioning equipment.

Outdoor Air

Hood

Field Supplied

Return Duct

Power Exhaust

5 in. Min.

Clearance

5 ft. Minimum

0.62

23.12

0.95

0.99

42.50

2 x 10.25 (= 2 0 .50)

0.46

0.99

9.25

2 x 12.00 (= 2 4.00)

Engagement holes for 
1/4-14 x 3/4 in. gasket head screws 
(12 places)

Summary of Contents for CRPWREXH068A00

Page 1: ...tial for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Page 2: ...1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 17 5 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 20 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1...

Page 3: ...l box is PEM2 Fig 1 Power Exhaust Relay Installation Vane Axial Fan Units Fig 2 Power Exhaust Relay Installation Belt Drive Fan Units 5 Install wiring harness 50HEMRAX A00 in the control box as shown...

Page 4: ...serrated head screws AL48AM217 Fig 5 Unit Return Air Panel Removal for Vertical Return Air Applications 3 Install three No 10 x 5 8 in serrated head screws AL48AM217 in the three locations shown in Fi...

Page 5: ...t located in the top left corner of the control box 10 Connect the 6 pin plug PL 9 from the wiring harness into the 6 pin plug of the power exhaust fan assembly Make sure that the PL 9 connection is m...

Page 6: ...Fig 11 3 Apply silicone caulking to corners and back side of mating flanges of the power exhaust fan assembly 4 Set the power exhaust hood assembly into the opening in the duct bottom lip first as sho...

Page 7: ...ntrol box 14 Bundle up excess wire of the motor harness and secure with wire ties When bundling wires be sure to gather wires as close as possible so that the wires can not contact moving parts for th...

Page 8: ...d indoor fan systems USER INTERFACE The user interface consists of a LCD display and a 4 button keypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 15 are used...

Reviews: