Installing the Vertical Power Exhaust

NOTE: Before installing, ensure voltage of power exhaust

agrees with power supply to equipment.
1. Turn off unit power supply and install lockout tag. For

gas units, turn off the gas supply

2. Remove the power exhaust knockout plugs located on

the lower left side of the EconoMi$er accessory. (See
Fig. 2.)

Fig. 2 — Power Exhaust Knockout Location

3. Remove the RTU unit filter panel to allow access to the

inside of the rooftop.

4. The panel covering the horizontal return opening on the

unit may also be removed for easier access and installa-
tion. Be sure to replace this panel when installation is
complete.

5. Install the vertical economizer per the instructions pro-

vided with the economizer. Do not install the rainhood
shipped with the economizer. Set aside the aluminum air
filter for use with the power exhaust.

6. Remove fan shield so power exhaust can lay flat without

bending the shield or damaging the roof.

7. Remove the shipping blocks from the bottom of the

accessory vertical power exhaust. (See Fig. 3.)

Fig. 3 — Shipping Block Removal

8. There may be a hinged door panel in place of the filter

panel. Open the hinged door, remove the screws and
hinges, remove the door and set it aside. Keep all screws
and hinges.

9. Place the power exhaust close to the EconoMi$er to

allow for wiring harness connection.

10. Follow the wiring instructions specific to the

EconoMi$er. Be sure power exhaust wiring does not
interfere with damper operation.

Power Exhaust Wiring with EconoMi$er IV and
EconoMi$er X

Follow these instructions if using the vertical power ex-

haust with EconoMi$er IV or EconoMi$er X accessories.
1. The 2-wire low voltage harness from the power exhaust

and the 24 to 36 in. (610 or 915 mm) low voltage exten-
sion harness are plugged together for shipping. Unplug
these 2 harnesses for installation.

2. Insert the 2-wire low voltage harness plug from the

power exhaust into the top knockout on the EconoMi$er.
(See Fig. 2.)

3. From the rear of the EconoMi$er, connect the 24-in.

(601mm) low voltage extension harness plug to the
power exhaust harness.

4.

For EconoMi$er IV:

 Route the other end of the low volt-

age extension harness to the EconoMi$er IV controller.
(See Fig. 4.) The harness is connected to the controller
by connecting the tan wire to the tan wire 24 VAC COM
terminal on the controller. The terminal on the gray wire
is connected to terminal EF1 on the controller. See Fig. 6
and 7 for EconoMi$er wiring diagrams. Install the gray
jumper wire on the controller from the exhaust fan termi-
nal (EF), to the 24 VAC HOT terminals. The gray jumper
is shipped wire tied to the control harness.

For EconoMi$er X:

 Route the other end of the low volt-

age extension harness to the EconoMi$er X 12 pin plug,
(PL6). (See Fig. 5.) The gray wire from the low voltage
extension harness connects to the yellow wire coming
from terminal 8 in the 12 pin plug. The tan wire from the
low voltage extension harness connect to the brown wire
coming from terminal 4 in the 12 pin plug. See Fig. 6 and
7 for EconoMi$er X wiring diagrams.

5. The high voltage harness from the power exhaust and the

high voltage extension harness are plugged together for
shipping. Unplug these 2 harnesses for installation.

6. Insert the high voltage harness plug from the power

exhaust into the bottom knockout on the EconoMi$er.
(See Fig. 2 and 4.)

R-410A Rooftop Models Only:

 For single point wiring

application, connect the power exhaust power wire har-
ness to the compressor contactor or indoor fan contactor
in the control box. Install the power exhaust power wire
harness into the pressure lugs on the compressor contac-
tor or indoor fan contactor, used for the field power wir-
ing also.

WARNING

Electrical shock can cause personal injury and death.
Before beginning any modification, be certain that the

main-line electrical disconnect switch is in the OFF posi-

tion. Close the main gas supply shutoff valve. Tag discon-

nect switch and gas valve with suitable warning labels.

POWER 
EXHAUST
KNOCKOUTS

ECONOMI$ER

SHIPPING
BLOCKS

POWER 
EXHAUST
ASSEMBLY

CAUTION

Failure to follow this caution may result in equipment dam-

age.
Be careful to route wires to avoid pinching or cutting

during assembly. It can be difficult to protect the wires

while attaching the power exhaust to the unit.

Summary of Contents for CRPWREXH021A01

Page 1: ...cautions that may apply Follow all safety codes including ANSI American National Standards Institute Z223 1 Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire e...

Page 2: ...installed transformer part no HT01AH859 must be used with 208 230v power exhaust The vertical power exhaust can be used with 3 different types of economizers While the physical installation of the po...

Page 3: ...nsion harness plug to the power exhaust harness 4 For EconoMi er IV Route the other end of the low volt age extension harness to the EconoMi er IV controller See Fig 4 The harness is connected to the...

Page 4: ...ig 4 Power Exhaust Harness Installation for EconoMi er IV with W7212 Controller Fig 5 Power Exhaust Harness Installation for EconoMi er X with W7220 Controller COIL FILTERS HVAC UNIT W7212 CONTROLLER...

Page 5: ...d Wiring 575 V transformer No HT01AH859 is ordered separately from power exhaust Economizer actuator and controller are shipped with the Economizer not with power exhaust Connections from End Switch p...

Page 6: ...X Field Supplied Wiring Economizer actuator and controller are shipped with the Economi er not with power exhaust Connection from End Switch Plug to the Economi er controller are made by installer If...

Page 7: ...Do not drill routing holes Be careful not to route the power exhaust harness on top of the indoor coil 9 Wire the end of the high voltage harness extension to the power exhaust power source 10 Field I...

Page 8: ...ALLED POSITION ROOF HIGH VOLTAGE HARNESS KNOCKOUTS UNIT ROOF CURB HIGH VOLTAGE EXTENSION HARNESS LOW VOLTAGE EXTENSION HARNESS TO PERMIERLINK CONTROLLER PREMIERLINK TERMINAL J8 PWR HS3 EXH RVS CUT FOR...

Page 9: ...r open ing of the power exhaust Filter will slide past filter clips Close filter clips which will lock filter in place 6 Reinstall the fan shield 7 Return power to unit and remove lockout tag 8 Test p...

Page 10: ...n the hinged door was removed See Fig 16 8 Close the hinged door and adjust handle if necessary Fig 14 Power Exhaust Installation Fig 15 Install Sealing Angle Fig 16 Install the Hinged Door PremierLin...

Page 11: ......

Page 12: ...scontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480206 01 Printed in U S A Form IIK CRPWREXH021 07 Pg 12 8 18 Replaces IIK CR...