10

Installing the Hinged Door Angle (Small and
Large Cabinet)

Follow these instructions if the unit has a hinged panel in-

stead of a standard filter panel. Hinged Door Angle CRPE-

CONV003A00 is for small cabinets and CRPE-

CONV004A00 is for large cabinets.
NOTE: A separate hinged door angle kit must be ordered for the

extra-large cabinet.
1. Find the sealing angle and three screws provided in the

power exhaust kit.

2. Attach the sealing angle to the top of the power exhaust

hood using the screws provided. Refer to Fig. 14 and 15.
Note that the gasketing flange will be facing out.

3. If there are NO pre-drilled holes in the Power Exhaust

hood: Lay the hinged panel, insulation side up, on top of
the hood so that the hinge screw holes align with the pre-
drilled screw holes in the sealing angle. (For hoods with
pre-drilled holes, skip to Step 7.)

4. Check the alignment of the hinged door with the side of

the filter opening to be sure it will close properly.

5. Use a pencil to mark the hood where the screw holes will

be.

6. Remove the hinged door and drill four (4) 

11

/

64

 in. holes

where the marks are.
NOTE: The sealing angle will be in place; use the holes
in it as a guide.

7. Place the door and hinges back on the unit. Screw

through the door hinges and sealing angle into the
flanged top of the hood using the 4 screws set aside when
the hinged door was removed. (See Fig. 16.)

8. Close the hinged door and adjust handle if necessary.

Fig. 14 — Power Exhaust Installation

Fig. 15 — Install Sealing Angle

Fig. 16 — Install the Hinged Door

PremierLink™ — Operational Notes for Testing
Purposes

If the “continuous power exhaust” function is disabled, the

power exhaust fan will operate during EconoMi$er purge cy-

cles when the EconoMi$er damper position is above the con-

figured minimum value. If enabled, the power exhaust fan

will follow the supply fan's operation for PremierLink ver-

sion 1.2 and will follow the occupancy configuration for Pre-

mierLink version 1.3.

The PremierLink “Auxiliary Output” function defines the

specific use of the auxiliary output (HS3/EXH/RVS) for the

power exhaust. The output will be energized or deenergized

by the appropriate algorithm that uses that specific output.

A setting of 1 = Exhaust fan output.
The Power Exhaust set point in the set point table deter-

mines the power exhaust damper “percent open” when the

power exhaust is energized. The damper percentage set point

has a 10% hysteresis.

If “Continuous” in the service configuration table is set to

“enable”, the power exhaust output will energize when occu-

pied (for PremierLink controls version 1.3 and later) and will

be energized when the supply fan relay is on (for versions pri-

or to 1.3).

POWER 
EXHAUST
SIDE FLANGES

GASKET
LOCATION
(STANDARD
FILTER PANEL
ONLY)

GASKET LOCATION

GASKETED
FLANGE

SEE
NOTE

SEE
NOTE

SEALING
ANGLE

SCREW ANGLE
TO HOOD (3)

SEALING
ANGLE

HINGED DOOR

POWER EXHAUST
HOOD

Summary of Contents for CRPWREXH021A01

Page 1: ...cautions that may apply Follow all safety codes including ANSI American National Standards Institute Z223 1 Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire e...

Page 2: ...installed transformer part no HT01AH859 must be used with 208 230v power exhaust The vertical power exhaust can be used with 3 different types of economizers While the physical installation of the po...

Page 3: ...nsion harness plug to the power exhaust harness 4 For EconoMi er IV Route the other end of the low volt age extension harness to the EconoMi er IV controller See Fig 4 The harness is connected to the...

Page 4: ...ig 4 Power Exhaust Harness Installation for EconoMi er IV with W7212 Controller Fig 5 Power Exhaust Harness Installation for EconoMi er X with W7220 Controller COIL FILTERS HVAC UNIT W7212 CONTROLLER...

Page 5: ...d Wiring 575 V transformer No HT01AH859 is ordered separately from power exhaust Economizer actuator and controller are shipped with the Economizer not with power exhaust Connections from End Switch p...

Page 6: ...X Field Supplied Wiring Economizer actuator and controller are shipped with the Economi er not with power exhaust Connection from End Switch Plug to the Economi er controller are made by installer If...

Page 7: ...Do not drill routing holes Be careful not to route the power exhaust harness on top of the indoor coil 9 Wire the end of the high voltage harness extension to the power exhaust power source 10 Field I...

Page 8: ...ALLED POSITION ROOF HIGH VOLTAGE HARNESS KNOCKOUTS UNIT ROOF CURB HIGH VOLTAGE EXTENSION HARNESS LOW VOLTAGE EXTENSION HARNESS TO PERMIERLINK CONTROLLER PREMIERLINK TERMINAL J8 PWR HS3 EXH RVS CUT FOR...

Page 9: ...r open ing of the power exhaust Filter will slide past filter clips Close filter clips which will lock filter in place 6 Reinstall the fan shield 7 Return power to unit and remove lockout tag 8 Test p...

Page 10: ...n the hinged door was removed See Fig 16 8 Close the hinged door and adjust handle if necessary Fig 14 Power Exhaust Installation Fig 15 Install Sealing Angle Fig 16 Install the Hinged Door PremierLin...

Page 11: ......

Page 12: ...scontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480206 01 Printed in U S A Form IIK CRPWREXH021 07 Pg 12 8 18 Replaces IIK CR...