background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480206-01

Printed in U.S.A.

Form IIK-CRPWREXH021-07

Pg 1         8-18

Replaces: IIK-CRPWREXH021-06

Installation Instructions

PART NO. CRPWREXH030A01, CRPWREXH021A01, CRPWREXH022A01,

CRPWREXH023A01, CRPWREXH080A00, CRPWREXH081A00

FOR USE WITH VERTICAL ECONOMI$ER

®

 IV, ECONOMI$ER

®

 2, OR

ECONOMI$ER

®

 X ONLY

TABLE OF CONTENTS

SAFETY CONSIDERATIONS

 . . . . . . . . . . . . . . . . . . . .1

PACKAGE CONTENTS AND USAGE

. . . . . . . . . . . . .1

GENERAL

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

INSTALLATION

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Installing the Vertical Power Exhaust

. . . . . . . . . . . .3

Power Exhaust Wiring with EconoMi$er IV and

EconoMi$er X

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Power Exhaust Wiring with EconoMi$er and

PremierLink Controller or RTU-MP/OPEN

. . . . . .7

Attaching Power Exhaust to the Unit

 . . . . . . . . . . . .9

Installing the Hinged Door Angle

(Small and Large Cabinet)

 . . . . . . . . . . . . . . . . . . .10

PremierLink — Operational Notes for

Testing Purposes

 . . . . . . . . . . . . . . . . . . . . . . . . . . .10

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, re-

pair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-

tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.

When working on air-conditioning equipment, observe precau-

tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.

Follow all safety codes, including ANSI (American National

Standards Institute) Z223.1. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.

PACKAGE CONTENTS AND USAGE

See Tables 1 and 2 for package content and usage.

Table 1 — Package Contents

NOTES:

1. Both wiring harnesses are shipped attached to the power

exhaust assembly.

2. The sealing angle was included beginning with unit serial num-

bers 3502Gxxxxx (21A-23A and 30A power exhaust only). For
use with Hinged Panel units only.

Table 2 — Package Usage

IMPORTANT: Read entire instructions before installing

the accessory.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all discon-

nect locations to alert others not to restore power until work

is completed.

QTY

CONTENTS

1

Power Exhaust Hood/Fan Assembly

1

1

Low Voltage Wiring Harness with plug and 12-in. (305 

mm) gray jumper wire

1

1

High Voltage Wiring Harness with plug

1

8

No. 10 x 

3

/

4

 in. (19 mm) Mounting Screws

1

Gasketing Roll

1

Sealing Angle

2

UNIT CONFIGURATION

UNIT FOOTPRINT (IN.)

POWER EXHAUST PART NUMBER

POWER EXHAUST VOLTAGE

Small Cabinet

46 

3

/

4

 x 74 

3

/

8

CRPWREXH030A01

208/230 V, 1 Ph

CRPWREXH021A01

460 V, 3 Ph

Large Cabinet

58 

1

/

2

 x 88 

1

/

8

CRPWREXH022A01

208/230 V, 1 Ph

CRPWREXH023A01

460 V, 3 Ph

Extra Large Cabinet

66 

3

/

8

 x 115 

7

/

8

CRPWREXH080A00

208/230 V, 1 Ph

CRPWREXH081A00

460 V, 3 Ph

Gas Heating/Electric Cooling,

 Electric Cooling, and Heat Pump Units

3 to 15 Tons Small Rooftop Units

Vertical Power Exhaust Accessory

Summary of Contents for CRPWREXH021A01

Page 1: ...cautions that may apply Follow all safety codes including ANSI American National Standards Institute Z223 1 Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire e...

Page 2: ...installed transformer part no HT01AH859 must be used with 208 230v power exhaust The vertical power exhaust can be used with 3 different types of economizers While the physical installation of the po...

Page 3: ...nsion harness plug to the power exhaust harness 4 For EconoMi er IV Route the other end of the low volt age extension harness to the EconoMi er IV controller See Fig 4 The harness is connected to the...

Page 4: ...ig 4 Power Exhaust Harness Installation for EconoMi er IV with W7212 Controller Fig 5 Power Exhaust Harness Installation for EconoMi er X with W7220 Controller COIL FILTERS HVAC UNIT W7212 CONTROLLER...

Page 5: ...d Wiring 575 V transformer No HT01AH859 is ordered separately from power exhaust Economizer actuator and controller are shipped with the Economizer not with power exhaust Connections from End Switch p...

Page 6: ...X Field Supplied Wiring Economizer actuator and controller are shipped with the Economi er not with power exhaust Connection from End Switch Plug to the Economi er controller are made by installer If...

Page 7: ...Do not drill routing holes Be careful not to route the power exhaust harness on top of the indoor coil 9 Wire the end of the high voltage harness extension to the power exhaust power source 10 Field I...

Page 8: ...ALLED POSITION ROOF HIGH VOLTAGE HARNESS KNOCKOUTS UNIT ROOF CURB HIGH VOLTAGE EXTENSION HARNESS LOW VOLTAGE EXTENSION HARNESS TO PERMIERLINK CONTROLLER PREMIERLINK TERMINAL J8 PWR HS3 EXH RVS CUT FOR...

Page 9: ...r open ing of the power exhaust Filter will slide past filter clips Close filter clips which will lock filter in place 6 Reinstall the fan shield 7 Return power to unit and remove lockout tag 8 Test p...

Page 10: ...n the hinged door was removed See Fig 16 8 Close the hinged door and adjust handle if necessary Fig 14 Power Exhaust Installation Fig 15 Install Sealing Angle Fig 16 Install the Hinged Door PremierLin...

Page 11: ......

Page 12: ...scontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480206 01 Printed in U S A Form IIK CRPWREXH021 07 Pg 12 8 18 Replaces IIK CR...

Reviews: