Step 2 — Mounting and Electrical Connec-
tions for Motormaster® V Control 

48/50P030-060 UNITS — For 48/50P030-035 units, the Mo-

tormaster controlled outdoor-fan motor (OFM) is the no. 1

OFM (see Fig. 3). The no. 2 OFM is controlled by the 

Com-

fort

link head pressure control routine.

For 48/50P040 units, the Motormaster controlled outdoor-

fan motor (OFM) is the no. 3 OFM (see Fig. 3). The no. 1 and 2

OFMs are controlled by the 

Comfort

link head pressure control

routine.

For 48/50P050-060 units, the Motormaster controlled out-

door-fan motor (OFM) is the no. 1 OFM (see Fig. 3). The no. 2,

3, and 4 OFMs are controlled by the 

Comfort

link head pressure

control routine.

Use the following procedure to mount and connect the

MMV controllers to these units:

1. Disconnect power to the unit. Lockout and tag power dis-

connect. 

2. Remove control box covers.
3. For size 030-035 units, remove panel from condenser

section on OFM 1 side of the unit in order to gain access

to the outdoor fan section. See Fig. 4. For size 040-060

units, remove panel above control box as shown in Fig. 5

and 6.

4. Mount accessory fuse block HY11UT035 and fan relay

base HN79KK035 inside control box as shown in Fig. 7.

Secure components with ½-in. sheet metal screws.

a. Insert fuses into fuse blocks and relays into relay

bases.

b. Install harness 48EJ402454 from load side of CCB

(control circuit breaker terminals 21, 22, 23) to line

side of MMF (Motormaster V fuse block) as

shown in Fig. 8. Note that it may be easier to pick

up the load side of CCB from the ¼-in. male quick

connect terminals on the line side (terminals 11,

12, 13) of the OFC contactors (see power sche-

matic on control box door).

c. Connect FR (fan relay) coil to OFC1 coil using the

72-in. long 16 gage white and gray wires (stripped

end goes to FR) as shown in Fig. 8.

5. Mount the MMV controller enclosure 30RA500381 on

the bulkhead of the unit inside the outdoor fan section, as

shown in Fig. 4-6, using the mounting brackets

50EJ500656 installed on the enclosure. Remove the en-

closure cover and install the ½-in. HW60EA001 and 1-in.

HW60HH006 connectors in the holes in the lower right

hand side of the enclosure.

6. Connect transducer HK05ZZ001 to the liquid line service

Schrader port of refrigerant Circuit A. Plug transducer ca-

ble 48EJ403240 into transducer. Run cable to the MMV

enclosure, as shown in Fig. 4-6. 
Run MMPT (Motormaster V pressure transducer) cable

through ½-in. connector of MMV enclosure (do not tight-

en connector screws at this time). Connect red, green, and

black wires to MMV terminals 6, 5, and 2 as shown in

Fig. 8. Terminate drain wire of transducer cables under

one of the lower MMV mounting screws.

7. Make remaining electrical connections to MMV (see

Fig. 8).

a. In main control box, disconnect black, red, blue,

and green wires from load side (terminals 21, 22,

23) of OFC1 (sizes 030-035, 050-060) contactor or

OFC 3 (size 040) (label cable from OFC1 or OFC3

(size 040) as OFM1 or OFM3 (size 040). Pull

wires out through the hole in the bottom of the

control box and run them up the corner post to the

opening of the cable tray on the side of the control

box, as shown in Fig. 4-6. Run the cable through

the wire tray to the MMV enclosures. 

b. Run the OFM1/OFC3 (040) cable through the 1-in.

connector of the MMV enclosure (do not tighten

connector screws at this time). Remove ring termi-

nals from black, red, and blue wires and strip insu-

lation back 3/8-in. Connect black, red, and blue

wires to MMV terminals T1, T2, and T3. Connect

green ground wire to MMV ground screw.

c. In the main control box connect Motormaster VFD

(variable frequency drive) harness 48ZZ401971 to

the load side of the MMF (label the opposite end of

this harness as MMF). Run the harness along the

bottom of the control box and out through the hole

that the OFM harness was in. Pull the harness out

through the hole in the bottom of the control box

and run it through the opening of the cable tray (in

the same manner as the OFM harnesses).

d. Run the MMF cable through 1-in. connector of the

MMV enclosure (do not tighten connector screws

at this time). Connect L1, L2, and L3 wires to

MMV terminals L1, L2, and L3. Connect green

ground wire to MMV ground screw. Place 1 large

varnish cloth 48DA510141 around both cables at

the point they enter the 1-in. connector. Tighten

down connector screws being careful not to dam-

age the cables.

e. In the main control box connect one Motormaster

VFD harness 48ZZ402001 to the NO (normally

open) contact of the FR (see Fig. 8). Run the har-

nesses along the bottom of the control box and out

through the hole that the OFM harness was in. Pull

the harness out through the hole in the bottom of

the control box and run it through the opening of

the cable (in the same manner as the OFM

harness).

WARNING

To avoid possibility of electric shock and personal

injury, open and tag all electrical disconnects before

installing or servicing unit.

WARNING

Hazard of electric shock. Wait three minutes after discon-

necting incoming power before servicing drive. Capacitors

retain charge after power is removed.

CAUTION

To avoid damage to the small terminals on the Motormas-

ter V control, use care when tightening the compression

terminals and use the proper size screwdriver.

CAUTION

DO NOT connect incoming AC power to Motormaster V

output terminals T1, T2, and T3. Severe damage to the con-

trol will result.

Summary of Contents for CRLOWAMB033A00

Page 1: ...nd permits operation at lower outdoor ambient temperatures To operate these units at very low ambient temperatures Mo tormaster V controls Fig 1 mustbe added Field fabricated and installedwindbaffles...

Page 2: ...HY10KB151 3 HY10KB151 3 Fuse 20A KTK R Class CC HY10KB200 3 Harness Assembly 48ZZ401971 Harness Assembly 48EJ402454 Harness Assembly 48ZZ402001 Label 48ZZ502002 Transducer HK05ZZ001 Transducer Harness...

Page 3: ...CRLOWAMB037A00 CRLOWAMB038A00 Connector 1 2 in HW60EA001 2 Connector 1 in HW60HH006 2 Controller 230 V 2 Hp HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30...

Page 4: ...ils NOTE 48 50P030 035 and 070 100 units do not require baffles UNIT SIZE QUANTITY DIMENSION A in mm 030 035 Not Used 040 060 2 78 125 0 125 1984 3 070 100 Not Used BAFFLE INSTALLATION LOCATION SIZES...

Page 5: ...wire of transducer cables under one of the lower MMV mounting screws 7 Make remaining electrical connections to MMV see Fig 8 a In main control box disconnect black red blue and green wires from load...

Page 6: ...outine 090 100 1 Controlled by the ComfortLink head pressure control routine 2 MMV B 3 Controlled by the ComfortLink head pressure control routine 4 5 6 MMV A Control Box 1 2 Control Box 1 2 3 Control...

Page 7: ...N THE WIRES ALONG THE OUTSIDE OF THE COIL TRAY Fig 5 MMV Control Mounting 48 50P040 Units a48 8563 RUN ELECTRICAL HARNESSES UP THE SIDE OF THE UNIT IN THE SPACE BETWEEN THE CORNER POST AND THE CONTROL...

Page 8: ...IONS FR A OFC1 13 14 C1 C2 ADD FAN RELAY FR IN PARALLEL WITH OFC1 CCB MM F BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK GRY WHT 11 12 13 22 23 21 FR A Fig 8 Motormaster V Accessory W...

Page 9: ...liquid line ser vice Schrader ports located under the V coils of the con denser fan sections of refrigerant circuit A and B Circuit A is the one closest to the Indoor Fan Motor section and circuit B...

Page 10: ...bel the opposite end of this harness as FR A and the other Motormaster VFD harness 48ZZ402001 to the NO contact of FR B label the opposite end of this harness as FR B Run the har nesses along the bott...

Page 11: ...when the compressor en gages The control will adjust the fan speed to maintain ap proximately 320 psig Above that pressure the fan should op erate at full speed For size 030 060 units the Motormaster...

Page 12: ...2 T3 B B BLK 1 2 5 6 11 12 2 14 13A 13B 13C 15 5 9 FR A MMPT A 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC 3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC 3 MMF A...

Page 13: ...ion of observing system operation and VFD display information If the liquid line pressure is above the set point and the VFD is running at full speed this is a normal condition The fan CANNOT go any f...

Page 14: ...50 P28 Fixed boost 0 5 at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Pres...

Page 15: ...User data and Carrier defaults in the EPM are corrupted Restore factory defaults by toggling P48 to another mode Then set P48 to desired mode to restore all defaults for that mode See Drive Programmin...

Page 16: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480070 01 Printed in U S A Form 48 50P 2SI Pg 16 9 09 Replaces New Copy...