background image

START-UP

Operating Sequence

COOLING

3 to 6 Ton Units — When the outdoor-air temperature is above
the OAT setting and the room thermostat calls for cooling,
the compressor contactor is energized to start the compres-
sor and outdoor-fan motor. The indoor-fan motor (IFM) is
energized and the economizer damper moves to the mini-
mum position. After the thermostat is satisfied, the damper
moves to the fully closed position when indoor-fan motor is
deenergized.

When the outdoor-air temperature is below the OAT set-

ting and the thermostat calls for Y1 and G, the economizer
damper moves to the minimum position when the indoor fan
starts. The first stage of cooling is provided by the econo-
mizer. If the supply-air temperature is above 57 F, a switch
on the supply-air thermostat is closed between the T2 ter-
minal and the 24 vac terminal. This causes the damper to
continue to modulate open until the supply-air temperature
falls below 55 F or the damper reaches the fully open
position.

When the supply-air temperature is between 55 F and

52 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals and between the T1 and 24 vac
terminals. This causes the economizer damper to remain in
an intermediate open position.

If the supply-air temperature falls below 52 F, a switch on

the supply-air thermostat is closed between the T1 terminal
and the 24 vac terminal. This causes the damper to modulate
closed until the supply-air temperature rises above 55 F or
the damper reaches the minimum position.

When the supply-air temperature is between 55 F and

57 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals. This causes the economizer damper
to remain in an intermediate open position.

If the outdoor air alone cannot satisfy the cooling require-

ments of the conditioned space, economizer cooling is in-
tegrated with mechanical cooling, providing second stage
cooling. The compressor and outdoor fan will be energized
and the position of the economizer damper will be deter-
mined by the supply-air temperature.

When the second stage of cooling is satisfied, the com-

pressor and outdoor-fan motor will be deenergized. The damper
position will be determined by the supply-air temperature.

When the first stage of cooling is satisfied, and the IFM

is deenergized, the damper will move to fully closed
position.

Fig. 14 — Typical Economizer Supply-Air

Thermostat

Fig. 15 — Barometric Relief Damper

Characteristics — 3 to 6 Ton Units

Fig. 13 — Wiring Connections for Outdoor-Air

Thermostat

Fig. 16 — Barometric Relief Damper

Characteristics — 7

1

2

to 12

1

2

Ton Units

5

Summary of Contents for CRECOMZR001A02

Page 1: ...red Record amount of air for use in Step 10 2 Remove filter access panel by raising panel and swing ing panel outward Panel is now disengaged from track and can be removed No tools are required to remove filter access panel Remove indoor coil access panel Dis card panel and save screws See Fig 1 3 Assemble outdoor air hood top and side plates as shown in Fig 2 Install seal strips on hood top and s...

Page 2: ...ting bracket until the top screw is in the position determined by Fig 9 or 10 Tighten screws 11 Install outdoor air opening panel with screws from Step 2 12 Fasten hood top and side plate assembly and bottom stop on 71 2 to 121 2 ton units to unit with screws provided See Fig 2 FILTER ACCESS PANEL INDOOR COIL ACCESS PANEL Fig 1 Typical Access Panel Locations Fig 2 Outdoor Air Hood Details Fig 3 Ve...

Page 3: ...lamp screens to gether using clasp provided While holding screen s in place fasten screen retainer to hood using screws provided NOTE Only 1 screen is provided with 3 to 6 ton units EXAMPLE Given Negative Pressure 0 2 in wg Outdoor Air 1100 cfm Determine Setting 6 in Fig 9 Economizer Minimum Position Setting 3 to 6 Ton Units EXAMPLE Given Negative Pressure 0 1 in wg Outdoor Air 1100 cfm Determine ...

Page 4: ... 9 19 Replace filter access panel 20 Turn on base unit power 21 Barometric relief damper characteristics are shown in Fig 15 and 16 4 3 2 1 0 5 6 7 8 9 POSITION SETTING BRACKET TOP SCREW Fig 11 Minimum Position Setting Bracket MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOO...

Page 5: ...to remain in an intermediate open position If the supply air temperature falls below 52 F a switch on the supply air thermostat is closed between the T1 terminal and the 24 vac terminal This causes the damper to modulate closed until the supply air temperature rises above 55 F or the damper reaches the minimum position When the supply air temperature is between 55 F and 57 F the supply air thermos...

Page 6: ...ween the T1 terminal and the 24 vac terminal This causes the damper to modulate closed until the supply air temperature rises above 55 F or the damper reaches the minimum position When the supply air temperature is between 55 F and 57 F the supply air thermostat has open switches between theT2 and 24 vac terminals This causes the economizer damper to remain in an intermediate open position If the ...

Page 7: ... and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired properly and no 24 vac exists check wiring see unit label diagram 2 If supply air temperature is greater than 57 F 24 vac should be found at ter minal T2 on the SAT pink wire If 24 vac is not present replace SAT Damper ...

Page 8: ...rves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 1 4 4 4 Tab 1a 1b 5a 5a 6a 6b PC 111 Catalog No 534 892 Printed in U S A Form 48 50 39SI Pg 8 9 95 Replaces 48 50 31SI ...

Reviews: