Step 4 — Run Sensor Lead

1. Remove blower compartment panel and run sensor lead

across top of box and pass through grommet on right side

for connection to sensor. See Fig. 1 and Fig. 5.

Step 5 — Install Sensor

1. If an economizer is installed on unit it must be removed

to access filter rack and condensate pan.

2. Remove air filters and filter rack. See Fig. 6.
3. Remove indoor coil bracket on left side. See Fig. 7.
4. Install sensor (Item 4) on bracket (Item 5) and tighten

thumb screw into hole in bracket. Fasten to indoor coil

bracket using (2) Item 6 screws. See Fig. 8 and 9.

5. Remove wire ties holding economizer wire harness. Place

indoor coil bracket back into slot in condensate pan as

shown in Fig. 9 and pass sensor wire into blower com-

partment. Leave excess wire in blower compartment for

later connection. 

6. Run wire harness through U-slot while placing indoor

coil bracket back into position. See Fig. 10. Refasten with

previously removed screws and replace wire ties.

7. Reinstall filter rack and filters. See Fig. 6.

Step 6 — Connect Wire

1. Connect wire lead from controller to sensor lead and wire

tie excess wire to wire harness. See Fig. 5.

2. Reassemble unit.

Fig. 3 — Single Compressor

Fig. 4 — Dual Compressor

Summary of Contents for CRCNDOVR003A00

Page 1: ...the compressor s after 10 seconds of constant water contact if the drain trap becomes plugged It requires 5 minutes to reset after the water has cleared See Table 1 for control logic PRE INSTALLATION Remove accessory packaging and inspect shipment for damage See Table 2 for kit contents File claim with shipping company if accessory is damaged Verify unit is level and ad just if necessary See Table...

Page 2: ... to BLU Cond 1 In wire from controller Connect BLU Cond 1 Out wire from controller to open terminal on C1 coil See Fig 3 2 The 2 extra ORN wires should be tied back Step 3 For DUAL Compressor Units 1 Remove wire from C1 coil and connect to BLU Cond 1 In wire from controller Connect BLU Cond 1 Out wire from controller to open terminal on C1 coil See Fig 4 2 Remove wire from C2 coil and connect to O...

Page 3: ...sten to indoor coil bracket using 2 Item 6 screws See Fig 8 and 9 5 Remove wire ties holding economizer wire harness Place indoor coil bracket back into slot in condensate pan as shown in Fig 9 and pass sensor wire into blower com partment Leave excess wire in blower compartment for later connection 6 Run wire harness through U slot while placing indoor coil bracket back into position See Fig 10 R...

Page 4: ...4 Fig 5 Sensor Wire Connection ...

Page 5: ...5 Fig 6 Filters and Filter Rack Fig 7 Indoor Coil Bracket INDOOR COIL BRACKET ...

Page 6: ...6 Fig 8 Sensor and Bracket CORRECT INSTALLATION CORRECT INSTALLATION INCORRECT INSTALLATION Fig 9 Bracket Installation ...