Table 7B — High Efficiency Electric Cooling Unit Electric Heater Packages — 208/240 V, 3-Phase, 60 Hz
UNIT
SIZE
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER
CONNECTION
DIAGRAM
(Fig. No.)
ELECTRIC HEAT
(kW)
HEATER
FLA
UNIT ONLY
MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
MAX FUSE
OR HACR
BRKR
208 V
240 V
208 V
240 V
MCA
Max
Fuse/
HACR
208 V
240 V
208 V
240 V
036
—
—
—
—
—
—
17.8
25
—
—
—
—
007A00
30
7.5
10.0
20.9
24.1
—
—
29.6
33.6
30
35
008A00
30
11.3
15.0
31.3
36.1
—
—
42.6
48.6
45
50
009A00
30
13.1
17.5
36.5
41.0
—
—
49.1
54.8
50
60
042
—
—
—
—
—
—
20.0
30
—
—
—
—
007A00
30
7.5
10.0
20.9
24.1
—
—
30.0
33.9
30
35
008A00
30
11.3
15.0
31.3
36.1
—
—
43.0
49.0
45
50
009A00
30
13.1
17.5
36.5
41.0
—
—
49.5
55.1
50
60
048
—
—
—
—
—
—
25.2
40
—
—
—
—
007A00
30
7.5
10.0
20.9
24.1
—
—
32.4
36.3
40
40
008A00
30
11.3
15.0
31.3
36.1
—
—
45.3
51.4
50
60
009A00
30
13.1
17.5
36.5
41.0
—
—
51.8
57.5
60
60
060
—
—
—
—
—
—
33.4
50
—
—
—
—
007A00
30
7.5
10.0
20.9
24.1
—
—
35.1
39.1
50
50
008A00
30
11.3
15.0
31.3
36.1
—
—
48.1
54.1
50
60
009A00
30
13.1
17.5
36.5
41.0
—
—
54.6
60.3
60
60
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code (U.S.A. Standard)
NOTE: In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
Table 7C — High Efficiency Electric Cooling Unit Electric Heater Packages — 480 V, 3-Phase, 60 Hz
UNIT
SIZE
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER
CONNECTION
DIAGRAM
(Fig. No.)
ELECTRIC HEAT
(kW)
HEATER
FLA
UNIT ONLY
MIN CIRCUIT AMPACITY
FOR WIRE SIZING
MAX FUSE
OR HACR BRKR
480
MCA
Max
Fuse/HACR
480 V
480 V
036
—
—
—
—
9.0
10
—
—
010A00
32
10.0
12.2
—
—
17.0
20
011A00
32
15.0
18.1
—
—
24.4
25
012A00
32
17.5
21.1
—
—
28.1
30
042
—
—
—
—
10.4
15
—
—
010A00
32
10.0
12.2
—
—
17.3
20
011A00
32
15.0
18.1
—
—
24.6
25
012A00
32
17.5
21.1
—
—
28.4
30
048
—
—
—
—
13.4
20
—
—
010A00
32
10.0
12.2
—
—
18.1
20
011A00
32
15.0
18.1
—
—
25.5
30
012A00
32
17.5
21.1
—
—
29.3
30
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code (U.S.A. Standard)
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. This unit must be supplied from a 480 v, 3-phase power supply
with a maximum voltage to ground of 300 v.
14