background image

3

17.

48/50HG028 208/230-v Units only

:

Do not install control wiring harness included with the
accessory. The control wires for the power exhaust
contactors are included with the unit harness as a bundle
and can be connected to the appropriate terminals on the
contactors. See Fig. 11.

All other units:

Install control wiring harness as indicated in Fig. 12.

18. Dress the wiring in the control box so that the wires are

adequately supported and secured using the wire ties
supplied.

19. Replace the control box cover.
20. Re-apply power to the unit.
21. The

Comfort

Link™ control can now be configured to

operate the power exhaust. To do this the unit must be
configured for Power Exhaust Enabled (default is
DISABLED), Power Exhaust 1 Percentage setting
(default is 40%), Power Exhaust 2 Percentage setting
(default is 75%). These configurations are accomplished
through the Scrolling Marquee Display by using the
Configuration menu.

22. The control system must be configured to use the power

exhaust. A password may be required to edit the configu-
rations, depending on the previous settings configured in
the unit. Default password is “1111”.

23. To access the configuration, use the arrow keys to scroll

the red LED on the display to the “Configuration”
position and press

. Use the arrow keys to scroll

down until the display reads “ECON”, and press the

key. At the Power Exhaust Enabled (PE.EN)

setting, press

twice. The display should be

flashing DSBL. Use the arrow keys to change the
configuration to “ENBL” and press

and then

. Use the arrow keys to scroll down to the

Power Exhaust 1 Percentage setting (PE1.P) and press

twice. Use the arrow keys to increase or

decrease the economizer position percentage that will
start the first power exhaust fan, and press

and

. Use the arrow keys to scroll down to the

Power Exhaust 2 setting (PE2.P) and press
twice. Use the arrow keys to increase or decrease the
economizer position percentage that will start the second
power exhaust fan, and press

and

.

24. Configuration of the power exhaust is now complete.

Pressing the

key several times will return the

display to the auto scroll setting.

25. Consult the Controls and Troubleshooting Guide for

complete instructions on using the

Comfort

Link control

system.

26. The unit is now ready for normal operation.

ENTER

ENTER

ENTER

ENTER

ESCAPE

ENTER

ENTER

ESCAPE

ENTER

ENTER

ESCAPE

ESCAPE

Summary of Contents for COMFORTLINK 48HG014

Page 1: ...there are two different versions of this accessory This accessory literature covers acces sories manufactured for units with design revision 1 Design revision 0 units are not covered in this acces sor...

Page 2: ...it and into final operating position See Fig 8 10 Secure the assembly using the screws removed earlier from Step 1 11 Snap the 6 pin connector of the control box harness into the plug plate provided w...

Page 3: ...ngs configured in the unit Default password is 1111 23 To access the configuration use the arrow keys to scroll the red LED on the display to the Configuration position and press Use the arrow keys to...

Page 4: ...EXHAUST CONTACTOR Fig 8 Assembly in Operating Position Fig 10 Compressor Section Fig 6 Power Exhaust Relief Damper Assembly Fig 7 Bracket and Hood Positioning Fig 9 Control Box Detail Fig 5 Pivot Poin...

Page 5: ...ng Diagram 48 50HG028 208 230 v Units LEGEND C Contactor CAP Capacitor ECB Economizer Control Board FIOP Factory Installed Option FU Fuse IAQ Indoor Air Quality OAQ Outdoor Air Quality PEC1 Power Exha...

Page 6: ...tom The short piece is for the two sides 3 Place the barometric relief assembly into the unit The accessory should pivot on the unit end panel See Fig 5 4 Fold barometric relief assembly back into the...

Page 7: ......

Page 8: ...or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80230 Printed in U S A Form 48 50H P 14SI Pg 8 3 05 Replaces New Book 1 1 4 4 Tab...

Reviews: