background image

2

INSTALLATION

1. Remove return end cover and save screws for reuse. See

Fig. 2.

2. As shown in Fig. 3, the power exhaust motor is factory

wired to terminal 1 (high speed). To change motor speed,
move the black wire from terminal 1 to terminal 2 (medi-
um speed) or terminal 3 (low speed). If high speed is
desired, no wiring changes are required. The motor
closest to the control box is PEM1. The motor furthest
away from the control box is PEM2.

3. Position the power exhaust damper assembly at the return

end of the unit. Add seal strip to the edges of the hood
assembly. See Fig. 4. The long piece of seal strip is for the
top and bottom and the short piece is for the two sides.

4. Remove patch plate attached to the bottom of the com-

pressor partition behind compressor B1. Save screws.

5. Feed 6-pin connector of the motor harness through hole

created by the removal of the patch plate. Pull as much
wire through the hole as possible without causing damage
to the harness.

6. Place the power exhaust/damper assembly into the unit.

The accessory should pivot on the unit end panel. See
Fig. 5.

7. Fold power exhaust/damper assembly back into the unit

as shown in Fig. 6.

8. Install the side brackets using the screws included (

1

/

4

x

3

/

4

-in.). Be sure to properly position the hood. See Fig. 7.

9. Tilt the assembly out of the unit and into final operating

position. See Fig. 8.

10. Secure the assembly using the screws removed earlier

from Step 1.

11. Snap the 6-pin connector of the control box harness into

the plug plate provided with the accessory.

12. Plug the 6-pin connectors together (PL9). Bundle up

excess wire in the motor harness and secure with a
wire tie. When bundling wires, be sure to gather wires
as close as possible to compressor partition so as to
reduce the overall length of the wires. Push excess
wire through hole in partition. Secure plate with
screws originally used to secure patch plate. This will
ensure that the extra wire length will not come into
contact with moving parts.

13. Remove the control box cover and install the two power

exhaust contactors to the side of the control box using the
screws included with the kit (8-18 x

1

/

2

-in.). See Fig. 9.

14. Install the plastic snap bushing into the bottom of the con-

trol box as shown in Fig. 10.

15. Route the power exhaust harness through the compressor

section and into the control box, through the snap bush-
ing. See Fig. 10.

16. Connect the wires of the harness in the control box as

shown in the wiring diagram. The harness wires are
labeled to match the corresponding component and
connection position.

When removing panels from the unit, be careful not to
damage roof or other surfaces with the panels.

Fig. 2 — Unit Return End (48/50HG Units)

LEGEND

Fig. 3 — Power Exhaust Motor Wiring

(48/50HG Units)

CAP

Capacitor

PEM

Power Exhaust Motor

PL

Plug

Fig. 4 — Hood Assembly

Summary of Contents for COMFORTLINK 48HG014

Page 1: ...there are two different versions of this accessory This accessory literature covers acces sories manufactured for units with design revision 1 Design revision 0 units are not covered in this acces sor...

Page 2: ...it and into final operating position See Fig 8 10 Secure the assembly using the screws removed earlier from Step 1 11 Snap the 6 pin connector of the control box harness into the plug plate provided w...

Page 3: ...ngs configured in the unit Default password is 1111 23 To access the configuration use the arrow keys to scroll the red LED on the display to the Configuration position and press Use the arrow keys to...

Page 4: ...EXHAUST CONTACTOR Fig 8 Assembly in Operating Position Fig 10 Compressor Section Fig 6 Power Exhaust Relief Damper Assembly Fig 7 Bracket and Hood Positioning Fig 9 Control Box Detail Fig 5 Pivot Poin...

Page 5: ...ng Diagram 48 50HG028 208 230 v Units LEGEND C Contactor CAP Capacitor ECB Economizer Control Board FIOP Factory Installed Option FU Fuse IAQ Indoor Air Quality OAQ Outdoor Air Quality PEC1 Power Exha...

Page 6: ...tom The short piece is for the two sides 3 Place the barometric relief assembly into the unit The accessory should pivot on the unit end panel See Fig 5 4 Fold barometric relief assembly back into the...

Page 7: ......

Page 8: ...or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80230 Printed in U S A Form 48 50H P 14SI Pg 8 3 05 Replaces New Book 1 1 4 4 Tab...

Reviews: