Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 534-80230

Printed in U.S.A.

Form 48/50H,P-14SI

Pg 1

3-05

Replaces: New

Book 1

1

4

4

Tab

1a 1b 6a 6b

Installation Instructions

Power Exhaust Part Numbers: CRPWREXH018B00,

CRPWREXH019B00, CRPWREXH020B00

Barometric Relief Part Number: CRBARRLF003B00

CONTENTS

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1, 2

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6

Barometric Relief Damper

. . . . . . . . . . . . . . . . . . . . . . . . 6

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform the basic maintenance

functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.

GENERAL

Consult price pages for the economizer accessory if the unit

is not already equipped. Refer to Table 1 for a complete list of
parts contained in each kit.

Each hood assembly has 2 power exhaust blowers.

Brackets, wires and extra gasket screws are also included in the
package.

POWER EXHAUST PACKAGE USAGE

Table 1 — Power Exhaust/Barometric Relief Parts List

IMPORTANT: There are two different design revision
48/50HG units currently being produced. Because of
these differences, there are two different versions of
this accessory. This accessory literature covers acces-
sories manufactured for units with design revision 1.
Design revision 0 units are not covered in this acces-
sory book.

To determine the design revision, refer to the full unit
model number. See Fig. 1 for an example of an HG
model number. The design revision number in the model
number nomenclature is located in position 13.

Turn off main power to the unit and tag disconnect switch
before performing service or maintenance operations. Elec-
trical shock could cause personal injury or death.

IMPORTANT: The power exhaust accessory requires
the use of the economizer. Power Exhaust will not
operate without the use of an economizer.

UNIT

VOLTAGE

PART NUMBER

48/50HG014-028,

48/50PG20-28

208/230 V

CRPWREXH018B00

460 V

CRPWREXH019B00

575 V

CRPWREXH020B00

ITEM DESCRIPTION

DESCRIPTION (QUANTITY)

CRPWREXH018B00

CRPWREXH019B00

CRPWREXH020B00

CRBARRLF003B00

Blower/Damper
Assembly

Power Exhaust

(208/230 V)

Power Exhaust

(460 V)

Power Exhaust

(575 V)

Barometric Relief

Contactor

HN52KC010 (2)

HN52KC010 (2)

HN52KC010 (2)

Screw 8-18 x

1

/

2

AL56AU166 (4)

AL56AU166 (4)

AL56AU166 (4)

Power Wiring Harness

50TG402807

50TG402807

50TG402807

Control Wiring Harness

50TG403083

50TG403083

50TG403083

Snap Bushing

HY93NH091

HY93NH091

HY93NH091

Plug Plate

50TG500128

50TG500128

50TG500128

Left Hand Bracket

50TG502765

50TG502765

50TG502765

50TG502765

Right Hand Bracket

50TG502865

50TG502865

50TG502865

50TG502865

Screw -

1

/

4

x

3

/

4

AL31AZ308 (9)

AL31AZ308 (9)

AL31AZ308 (9)

AL31AZ308 (9)

Seal Strip

48/50HG014-028, 48/50PG20-28

with

COMFORT

LINK™ Controls

Power Exhaust and

Barometric Relief Accessory

Fig. 1 — Model Number Chart

Position No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Example:

4

8 H G D 0

1

6 A

A

C

6

1

1

A

A

DESIGN REVISION NUMBER

Summary of Contents for COMFORTLINK 48HG014

Page 1: ...there are two different versions of this accessory This accessory literature covers acces sories manufactured for units with design revision 1 Design revision 0 units are not covered in this acces sor...

Page 2: ...it and into final operating position See Fig 8 10 Secure the assembly using the screws removed earlier from Step 1 11 Snap the 6 pin connector of the control box harness into the plug plate provided w...

Page 3: ...ngs configured in the unit Default password is 1111 23 To access the configuration use the arrow keys to scroll the red LED on the display to the Configuration position and press Use the arrow keys to...

Page 4: ...EXHAUST CONTACTOR Fig 8 Assembly in Operating Position Fig 10 Compressor Section Fig 6 Power Exhaust Relief Damper Assembly Fig 7 Bracket and Hood Positioning Fig 9 Control Box Detail Fig 5 Pivot Poin...

Page 5: ...ng Diagram 48 50HG028 208 230 v Units LEGEND C Contactor CAP Capacitor ECB Economizer Control Board FIOP Factory Installed Option FU Fuse IAQ Indoor Air Quality OAQ Outdoor Air Quality PEC1 Power Exha...

Page 6: ...tom The short piece is for the two sides 3 Place the barometric relief assembly into the unit The accessory should pivot on the unit end panel See Fig 5 4 Fold barometric relief assembly back into the...