32
MOTOR
FAN GRILLE
MOTOR SHAFT
A
A08505
MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE
SIZE
“A”
IN.
MM
24
9.0
228
30
7.1
180
36
7.6
193
42
7.6
193
48
7.6
193
60
7.6
193
Fig. 22 -- Fan Blade Position
Step 9 — Loss of Charge Switch
This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch
should be closed. To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
NOTE
:
Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psig. Never open system
without breaking vacuum with dry nitrogen.
Step 10 — High--Pressure Switch
The high--pressure switch is located in the discharge line and
protects against excessive condenser coil pressure. It opens at 650
psig.
High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
Step 11 — Copeland Scroll Compressor (Puron
Refrigerant)
The compressor used in this product is specifically designed to
operate with Puron (R--410A) refrigerant and cannot be
interchanged.
EXPLOSION HAZARD
Failure to follow this warning could
result in personal injury, death or
property damage.
Wear safety glasses and gloves when
handling refrigerants. Keep torches
and other ignition sources away from
refrigerant and oils.
!
WARNING
The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an internal
pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port
has an operating range between 550 and 625 psig differential
pressure.
Step 12 — Refrigerant System
This step covers the refrigerant system including the compressor
oil needed, servicing systems on roofs containing synthetic
materials, the filter drier and refrigerant charging.
Refrigerant
PROPERTY HAZARD, PERSONAL INJURY OR
ENVIRONMENTAL HAZARD
Failure to follow this warning could result in property damage
or personal injury or death.
This system uses Puron (R--410A) refrigerant which has
higher operating pressures than R--22 and other refrigerants.
No other refrigerant may be used in this system. Gauge set,
hoses, and recovery system must be designed to handle Puron.
If you are unsure consult the equipment manufacturer.
!
WARNING
50V
T
--
C
Summary of Contents for Comfort 50VT C Series
Page 3: ...3 Fig 2 24 30 Unit Dimensions 50VT C...
Page 4: ...4 Fig 3 36 60 Unit Dimensions 50VT C...
Page 11: ...11 A150518 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT C...
Page 12: ...12 A150519 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT C...
Page 13: ...13 A150520 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT C...
Page 14: ...14 A150521 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT C...
Page 15: ...15 A150522 Fig 14 Connection Wiring Diagram 460 3 60 50VT C...
Page 16: ...16 A150523 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT C...