Fig. 2 -- Slab Mounting Details

Step 3 — Field Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal

applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate

and weatherproof all external ductwork, joints, and roof openings

with counter flashing and mastic in accordance with applicable
codes.

Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.

Read unit rating plate for any required clearances around ductwork.

Cabinet return--air static shall not exceed --.25 IN. W.C.

Step 4 — Provide Clearances

IMPORTANT

: The unit must be secured to the curb by installing

screws through the bottom of the curb flange and into the unit base
rails. When installing large base units onto the common curb, the
screws must be installed before allowing the full weight of the unit
to rest on the curb. A minimum of six screws are required for large
base units. Failure to secure unit properly could result in an
unstable unit. See Warning near Rigging/Lifting information and
accessory curb instructions for more details.
The required minimum operating and service clearances are shown

in Fig. 3 and 4. Adequate combustion, ventilation and condenser
air must be provided.

IMPORTANT

: Do not restrict outdoor airflow. An air restriction

at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
The condenser fan pulls air through the condenser coil and
discharges it through the top grille. Be sure that the fan discharge

does not recirculate to the condenser coil. Do not locate the unit in

either a corner or under an overhead obstruction. The minimum
clearance under a partial overhang (such as a normal house

overhang) is 48--in. (1219 mm) above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48--in.

(1219 mm).
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units

should be at least 2 in. (51 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.

Step 5 — Rig and Place Unit

Rigging and handling of this equipment can be hazardous for

many reasons due to the installation location (roofs, elevated
structures, etc.).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,

and any other safety precautions that might apply.

Training for operators of the lifting equipment should include, but
not be limited to, the following:

1. Application of the lifter to the load, and adjustment of the

lifts to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting

kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work

gloves.

Inspection

Prior to initial use, and at monthly intervals, all rigging shackles,

clevis pins, and straps should be visually inspected for any

damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist

hooking points and load support areas. Materials showing any kind
of wear in these areas must not be used and should be discarded.

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury or death.
Never stand beneath rigged units or lift over people.

!

WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal

injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36

in. (914 mm) above the unit top cover.

!

WARNING

Rigging/Lifting of Unit (See Fig. 6)

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury or death.
Large base units must be secured to common curb before

allowing full weight of unit to rest on curb. Install screws

through curb into unit base rails while rigging crane is still

supporting unit.

!

WARNING

Lifting holes are provided in base rails as shown in Fig. 3 and 4.

1. Leave top shipping skid on the unit for use as a spreader bar

to prevent the rigging straps from damaging the unit. If the

skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.

2. Attach shackles, clevis pins, and straps to the base rails of

the unit. Be sure materials are rated to hold the weight of the
unit (See Fig. 6).

3. Attach a clevis of sufficient strength in the middle of the

straps. Adjust the clevis location to ensure unit is lifted level
with the ground.

After the unit is placed on the roof curb or mounting pad, remove

the top skid.

48V

L

--

(C

,D

)

Summary of Contents for Comfort 48VL-C

Page 1: ...ck Heating Control 13 Check Gas Input 14 Adjust Gas Input 14 Check Burner Flame 15 Normal Operation 22 Airflow and Temperature Rise 22 Heating Sequence of Operation 22 Limit Switches 22 Rollout Switch...

Page 2: ...l gas installations RECEIVING AND INSTALLATION Step 1 Check Equipment Identify Unit The unit model number and serial number are stamped on the unit information plate Check this information against shi...

Page 3: ...it if it has been under water Step 5 Rig and Place Unit Rigging and handling of this equipment can be hazardous for many reasons due to the installation location roofs elevated structures etc Only tra...

Page 4: ...4 A180293 Fig 3 24 36 Unit Dimensions 48VL C D...

Page 5: ...5 Fig 4 42 60 Unit Dimensions 48VL C D...

Page 6: ...6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether...

Page 7: ...m 2500 24 609 6 1 10 810 2500 24 609 6 1 10 810 2700 24 609 6 1 10 810 2700 24 609 6 1 10 810 3200 24 609 6 1 5 810 3200 24 609 6 1 5 810 3600 26 660 4 1 5 810 3600 26 660 4 1 5 810 INDOOR COIL Rows F...

Page 8: ...locity of 300 to 350 ft minute for throwaway type Air filter pressure drop for non standard filters must not exceed 0 08 IN W C If using accessory filter rack refer to the filter rack installation ins...

Page 9: ...f local building codes adhere to the following pertinent recommendations 1 Avoid low spots in long runs of pipe Grade all pipe 1 4 in 6 35 mm for every 15 ft 4 6 m of length to prevent traps Grade all...

Page 10: ...downshot ducts are aligned with the down shot knockout areas 7 Re install horizontal metal covers as needed to seal unit Ensure openings are air and watertight NOTE The design and installation of the...

Page 11: ...ternal components when drilling through any panel to mount electrical hardware conduit etc CAUTION High Voltage Connections When routing power leads into unit use only copper wire between disconnect a...

Page 12: ...ts of the conditioned space and inefficient energy utilization however the required setting may be changed slightly to provide a greater degree of comfort for a particular installation Transformer Pro...

Page 13: ...2 Repair leak following accepted practices NOTE Install a filter drier whenever the system has been opened for repair 3 Add a small charge of Puron R 410A refrigerant vapor to system and leak test un...

Page 14: ...at Sea Level X Derate Multiplier Factor Furnace Input Rate at Installation Altitude 90 000 X 0 90 81 000 When the gas supply being used has a different heating value or specific gravity refer to nati...

Page 15: ...5 13 0 11 0 13 0 3 2 3 8 10 0 130 000 3 4 5 13 0 11 0 13 0 3 2 3 8 10 0 When a unit is converted to propane different size orifices must be used See separate natural to propane conversion kit instruc...

Page 16: ...16 A150502 Fig 14 208 230 1 60 Connection Wiring Diagram 48VL C D...

Page 17: ...17 A150510 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram 48VL C D...

Page 18: ...18 A150508 Fig 15 208 230 3 60 Connection Wiring Diagram 48VL C D...

Page 19: ...19 A150511 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram 48VL C D...

Page 20: ...20 A150509 Fig 16 460 3 60 Connection Wiring Diagram 48VL C D...

Page 21: ...21 A150512 Fig 16 Cont 460 3 60 Ladder Wiring Diagram 48VL C D...

Page 22: ...ses and completes the control circuit The direct spark ignition system cycles and the unit returns to normal heating operation Table 7 LED Indications STATUS CODE LED INDICATION Normal Operation2 On N...

Page 23: ...e temperature See Table 9 6 Compare actual liquid line temperature with desired liquid line temperature Using a tolerance of 2 F 1 1 C add refrigerant if actual temperature is more than 2 F 1 1 C high...

Page 24: ...etermine correct normal cooling fan speed for unit and application Add the wet coil pressure drop in Table 13 to the system static to determine the correct cooling airflow speed in Table 11 or 12 that...

Page 25: ...Board COM LOW HIGH GAS HEAT Q1 R1L C8 RL3 Q3 DCR QCR QC1 G1 G2 A7 D4 D6 C2 OILL R9 AB A15 C4 C9 C0 R4 RL4 C7 R2 R3 R5 R6 QCB Y Y R U C 24VAC JW1 P2 P1 W2 Y2 Y1 Y DH G C R SSTZ 8 P3 SDL 24VAC R CDM C F...

Page 26: ...empt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcool...

Page 27: ...28 NA NA High Black CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 Heat Rise o F 25 26 28 30 32 33 35 38 43 49 Heat Rise o C 14 15 16 17 18 18 20...

Page 28: ...26 28 NA NA High Black CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 Heat Rise o F 25 26 28 30 32 33 35 38 43 49 Heat Rise o C 14 15 16 17 18 18...

Page 29: ...28 30 High Black CFM 1596 1542 1482 1424 1362 1304 1238 1173 1201 1143 BHP 0 74 0 74 0 74 0 75 0 75 0 75 0 76 0 76 0 77 0 77 Heat Rise o F 28 29 30 31 33 34 36 38 37 39 Heat Rise o C 16 16 17 17 18 19...

Page 30: ...23 24 High Black CFM 1575 1528 1488 1447 1406 1360 1314 1264 1213 1159 BHP 0 40 0 42 0 43 0 44 0 45 0 46 0 47 0 48 0 49 0 50 Heat Rise o F 28 29 30 31 32 33 34 35 37 39 Heat Rise o C 16 16 17 17 18 18...

Page 31: ...23 25 High Black CFM 2267 2201 2133 2071 1997 1923 1835 1739 1654 1551 BHP 1 03 1 00 0 97 0 93 0 89 0 86 0 82 0 78 0 74 0 69 Heat Rise o F NA NA NA NA NA 35 37 39 41 44 Heat Rise o C NA NA NA NA NA 20...

Page 32: ...33 36 High Black CFM 2267 2201 2133 2071 1997 1923 1835 1739 1654 1551 BHP 1 03 1 00 0 97 0 93 0 89 0 86 0 82 0 78 0 74 0 69 Heat Rise o F 42 44 45 46 48 50 52 55 58 62 Heat Rise o C 24 24 25 26 27 28...

Page 33: ...0 41 0 42 0 43 0 45 0 45 Heat Rise o F 59 60 NA NA NA NA NA NA NA NA Heat Rise o C 33 33 NA NA NA NA NA NA NA NA Medium 2 Red CFM 1736 1710 1668 1630 1600 1557 1522 1479 1450 1406 BHP 0 53 0 54 0 55...

Page 34: ...Heat Rise o F 55 56 57 59 60 62 63 65 NA NA Heat Rise o C 31 31 32 33 33 34 35 36 NA NA Med High 1 Orange CFM 1935 1909 1867 1836 1808 1766 1696 1619 1535 1454 BHP 0 71 0 73 0 74 0 76 0 78 0 79 0 77...

Page 35: ...42 45 Heating Rise o C 16 17 18 19 20 20 22 23 25 High Black CFM 1560 1491 1416 1337 1255 1233 1160 1082 998 Heating Rise o F 28 30 31 33 35 36 38 41 44 Heating Rise o C 16 16 17 18 19 20 21 23 24 360...

Page 36: ...47 50 Heating Rise o C 18 19 19 20 22 23 24 26 28 High Black CFM 1472 1401 1326 1251 1275 1198 1139 1085 1023 Heating Rise o F 29 31 33 35 34 36 38 40 42 Heating Rise o C 16 17 18 19 19 20 21 22 24 4...

Page 37: ...36 37 Heating Rise o C NA NA NA NA NA NA 20 20 21 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F NA NA NA NA NA NA NA 35 37 Heating Rise o C NA NA NA NA NA NA NA 20 21 4...

Page 38: ...51 53 Heating Rise o C 25 25 26 26 27 27 28 28 29 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F 41 41 42 43 44 46 48 50 53 Heating Rise o C 23 23 23 24 25 26 27 28 29 6...

Page 39: ...19 36 o C Low Blue CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1678 1635 1602 1558 1513 1...

Page 40: ...1 43 46 48 51 54 NA NA NA Heating Rise o C 22 23 24 26 27 28 30 NA NA NA Medium 2 Red CFM 1208 1144 1091 1025 964 902 886 830 746 663 WATTS 345 350 358 366 373 377 390 396 407 410 BHP 0 37 0 38 0 38 0...

Page 41: ...NA NA NA NA NA NA NA NA Heating Rise o C 32 34 NA NA NA NA NA NA NA NA Medium 2 Red CFM 1208 1144 1091 1025 964 902 886 830 746 663 WATTS 345 350 358 366 373 377 390 396 407 410 BHP 0 37 0 38 0 38 0...

Page 42: ...43 46 49 53 NA NA NA NA NA NA Heating Rise o C 24 26 27 29 NA NA NA NA NA NA Medium Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0 3...

Page 43: ...NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA NA Medium 1 Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0 3...

Page 44: ...F 43 44 46 47 48 50 51 53 55 57 Heating Rise o C 24 25 25 26 27 28 29 30 30 32 Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 4...

Page 45: ...55 56 58 59 NA NA NA NA NA NA Heating Rise o C 30 31 32 33 NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 43...

Page 46: ...61 63 65 NA NA NA NA NA NA NA Heating Rise o C 34 35 36 NA NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 43...

Page 47: ...F 36 37 38 39 40 41 41 42 44 45 Heating Rise o C 20 21 21 22 22 23 23 24 24 25 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP 0 5...

Page 48: ...46 47 48 49 50 52 53 54 56 58 Heating Rise o C 26 26 27 27 28 29 29 30 31 32 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP 0 52...

Page 49: ...0 58 0 59 0 61 0 62 0 64 0 65 Heating Rise o F 49 50 51 52 53 54 55 56 58 59 Heating Rise o C 27 28 28 29 29 30 31 31 32 33 Med High 1 Orange CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751 WAT...

Page 50: ...00 1400 CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 30 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 220...

Page 51: ...ectric wires are not in contact with refrigerant tubing or sharp metal edges 6 Check and inspect heating section before each heating season Clean and adjust when necessary 7 Check flue hood and remove...

Page 52: ...e Fig 20 4 Disconnect gas piping at unit gas valve 5 Remove fan partition mounting bracket 2 screws located on the left side of control compartment on the fan partition panel Slide bracket forward bot...

Page 53: ...g 23 6 Ensure that setscrew engages the flat area on the motor shaft when tightening 7 Replace grille Electrical Controls and Wiring Inspect and check the electrical controls and wiring annually Be su...

Page 54: ...g on size Pressure Switches Pressure switches are protective devices wired into control circuit low voltage They shut off compressor if abnormally high or low pressures are present in the refrigeratio...

Page 55: ...to the surrounding area It is also known as a high side design since high pressure gas surrounds the motor and compression chamber The majority of the shell will be hot to the touch The rotary compres...

Page 56: ...nly compatible with POE synthetic oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suct...

Page 57: ...wn on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor...

Page 58: ...Limit switch faults LED 2 flashes High temperature limit switch is open Check the operation of the indoor evaporator fan motor Ensure that the supply air temperature rise is in accordance with the ran...

Page 59: ...AT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEM...

Page 60: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 11 18 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48VL 15...

Reviews: