ACCESSORY USAGE GUIDELINE

Accessory

REQUIRED FOR

LOW---AMBIENT APPLICATIONS

(Below 55

°

F / 12.78

°

C)

REQUIRED FOR LONG

LINE APPLICATIONS*

(Over 80 Ft. / 24.38 m)

REQUIRED FOR SEA

COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist

Capacitor and Relay

Yes

{

Yes

No

Crankcase Heater

Yes

{

Yes

No

Evaporator Freeze Thermostat

Yes

{

No

No

Isolation Relay

Yes

{

No

No

Liquid Line Solenoid Valve

No

See Long Line Application

Guideline

No

Motor Master

®

Control

or Low---ambient Pressure Switch

Yes

{

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. vertical (6.09 m) differential, refer to Residential Split System Long Line

Application Guideline.

{

Required for Low---Ambient Controller MotorMaster

r

Control only.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMaster

r

is used.

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor motor

at each start up.

Usage Guideline:

Required for reciprocating compressors in the following

applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves

compressor lubrication on restart and minimizes the chance of
liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Cycle Protector

The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay after

power to the compressor has been interrupted for any reason,

including power outage, protector control trip, thermostat jiggling,
or normal cycling.

6. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation

when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7. High Pressure Switch

A high pressure switch that protects unit against excessive pressure.

Usage Guideline:

Required in all heat pumps operated in dual fuel

applications.

8. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

9. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is to
be installed at the outdoor unit to control refrigerant off cycle

migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.

10. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order

to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain

working head pressure at low--ambient temperatures down to

0

_

F/--17.78

_

C when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling

operation is used at outdoor temperatures below 55

_

F

(12.8

_

C).

25H

C

R

3C

Summary of Contents for Comfort 25HCR3C

Page 1: ...S Front seating service valves S Scroll compressor S Internal pressure relief valve S Internal thermal overload S High and Low pressure switch S Filter drier S Balanced refrigeration system for maximu...

Page 2: ...ed capacity and efficiency Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy e...

Page 3: ...ivalent length is 250 ft 76 2 m The maximum vertical separation is 200 ft 60 96 m when outdoor unit is above indoor unit and 60 ft 18 29 m when the outdoor unit is below the indoor unit Refer to Acces...

Page 4: ...use in zoning heat pump applications Outdoor temperature sensor is an accessory for all Carrier electronic thermostats except the non programmable air conditioner version and builder s thermostats It...

Page 5: ...ompressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial...

Page 6: ...ectric heaters when outdoor air temperature drops below the second stage set point Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 15 Snow Stand C...

Page 7: ...G or smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage...

Page 8: ...8 DIMENSIONS 25HCR3C...

Page 9: ...8 11 7 14 6 17 6 20 5 23 4 kW 25HCR324C FA4CN F C 024 25HCR348C FC4DN F B 048 25HCR336C FC4DN F B 036 25HCR360C FC4DN F B 060 BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 25HCR318C FA4CN F C 018...

Page 10: ...2 58MVB060 14 CNRV 2417A 17 200 TDR TXV 14 50 12 50 17 400 3 66 9 900 2 44 8 2 58UVB060 14 CNRV 2417A 17 300 TXV 13 20 11 00 17 400 3 46 10 600 2 34 7 7 CSRH 2412A 17 300 TDR TXV 14 50 12 50 16 900 3...

Page 11: ...TDR TXV 14 50 11 70 23 600 3 72 14 100 2 54 8 7 58MVB060 14 CNRV 3017A 23 600 TDR TXV 14 50 11 70 23 600 3 72 14 100 2 54 8 7 58UVB060 14 CNRV 3017A 23 600 TXV 13 00 10 80 24 000 3 58 15 000 2 42 8 5...

Page 12: ...0 80 28 400 3 30 17 200 2 26 7 7 58CV A X 070 12 CNRV 3017A 28 600 TDR TXV 13 20 11 00 28 200 3 34 17 000 2 30 7 7 58CV A X 090 16 CNRV 3017A 28 400 TDR TXV 13 00 10 80 28 400 3 30 17 100 2 28 7 7 58M...

Page 13: ...3 00 10 80 35 400 3 36 20 800 2 44 8 2 58CV A X 135 22 CNRH 3617A 34 000 TDR TXV 13 20 11 00 35 400 3 38 20 800 2 46 8 2 58CV A X 155 22 CNRH 3617A 33 600 TDR TXV 13 00 10 80 35 400 3 30 21 000 2 40 8...

Page 14: ...0 2 40 7 7 58UVB100 20 CAR 4224A 40 000 TDR TXV 13 50 11 20 39 500 3 46 23 800 2 44 7 7 58CV A X 135 22 CAR 4224A 40 000 TDR TXV 13 50 11 20 39 500 3 46 23 800 2 44 7 7 58CV A X 155 22 CAR 4224A 39 50...

Page 15: ...22 CSRH 4212A 40 500 TDR TXV 13 20 11 00 40 500 3 50 24 200 2 40 7 7 58MVB040 14 CSRH 4212A 40 500 TDR TXV 13 50 11 20 40 500 3 54 24 200 2 42 7 7 58MVB060 14 CSRH 4212A 40 500 TDR TXV 13 20 11 00 40...

Page 16: ...29 600 2 58 8 3 58CV A X 135 22 CNRV 6024A 46 500 TDR TXV 13 50 11 20 45 500 3 40 29 400 2 60 8 3 58CV A X 155 22 CNRV 6024A 46 000 TDR TXV 13 50 11 20 46 000 3 32 29 800 2 56 8 2 58MVB120 20 CNRV 60...

Page 17: ...70 13 70 2 15 675 72 20 52 10 72 1 31 19 77 10 45 1 46 18 98 10 18 1 62 18 15 9 89 1 80 17 28 9 59 2 00 16 37 9 27 2 21 67 18 64 13 73 1 30 17 93 13 44 1 44 17 19 13 14 1 61 16 42 12 83 1 78 15 60 12...

Page 18: ...0 89 CAR 2414A 1 01 1 01 CAR 2417A 1 01 1 01 CAR 3014A 1 02 1 02 CAR 3017A 1 02 1 02 CNRF 2418A 1 01 1 01 CNRH 2417A 1 01 1 01 CNRH 3017A 1 02 1 02 CNRV 2414A 1 01 1 01 CNRV 2417A 1 01 1 01 CNRV 3014...

Page 19: ...99 0 99 58CV A X 070 12 CNRH 3617A 0 99 0 99 58CV A X 070 12 CNRV 3014A 0 99 0 99 58CV A X 070 12 CSRH 3012A 0 99 0 99 58CV A X 070 12 CSRH 3612A 1 01 1 00 58CV A X 070 12 CAR 3017A 0 99 0 97 58CV A...

Page 20: ...090 16 CNRH 4221A 0 99 0 96 58CV A X 090 16 CNRV 3617A 0 98 0 98 58CV A X 090 16 CSRH 3612A 0 98 0 95 58CV A X 090 16 CSRH 4212A 0 99 0 95 58CV A X 090 16 CAR 3621A 0 98 0 96 58CV A X 110 20 CAR 4221A...

Page 21: ...7 13 37 13 4 13 35 63 35 63 4 55 34 09 34 09 5 01 Cooling Indoor Model Capacity Power Furnace Model FC4DN F B 042 1 00 1 00 CSRH 4812A 1 01 1 03 FC4DN F B 048 1 02 1 01 FK4DN B F 003 0 98 0 96 FK4DN B...

Page 22: ...odel Capa city Power Furnace Model FC4DN F B 048 1 00 1 00 CSRH 6012A 0 98 0 98 FK4DNB006 1 01 0 95 FK4DNF005 0 99 0 95 CAR 4817A 0 94 0 92 58CV A X 090 16 CNRH 4821A 0 96 0 94 58CV A X 090 16 CNRH 60...

Page 23: ...4 60 68 38 37 73 5 01 65 49 36 67 5 47 62 53 35 60 5 98 59 43 34 48 6 54 56 21 33 32 7 14 67 64 95 49 52 4 53 62 36 48 43 4 94 59 68 47 33 5 40 56 94 46 20 5 91 54 09 45 03 6 46 51 12 43 81 7 06 63 6...

Page 24: ...16 96 16 96 1 50 16 39 16 39 1 48 75 525 7 00 6 44 1 24 8 98 8 25 1 32 11 19 10 20 1 40 13 72 12 19 1 49 16 47 14 99 1 61 18 71 18 71 1 70 19 76 19 76 1 74 19 86 19 86 1 74 600 7 15 6 58 1 26 9 14 8 4...

Page 25: ...1 00 0 96 CNRH 3017A 1 00 0 99 CNRV 2414A 1 00 0 96 CNRV 2417A 1 00 0 96 CNRV 3014A 1 00 0 99 CNRV 3017A 1 00 0 99 CSRH 2412A 1 00 0 96 CSRH 3012A 1 00 0 99 CAR 2414A 0 99 0 96 58CV A X 070 12 CAR 301...

Page 26: ...01 58CV A X 070 12 CSRH 3012A 0 98 1 00 58CV A X 070 12 CSRH 3612A 0 96 0 96 58CV A X 070 12 CAR 3017A 0 98 0 99 58CV A X 090 16 CAR 3617A 0 97 0 98 58CV A X 090 16 CNRH 3017A 0 98 0 99 58CV A X 090...

Page 27: ...8CV A X 090 16 CSRH 4212A 0 97 0 95 58CV A X 090 16 CAR 3621A 1 01 1 00 58CV A X 110 20 CAR 4221A 0 99 0 98 58CV A X 110 20 CNRH 3617A 1 01 1 01 58CV A X 110 20 CNRH 4221A 0 99 0 97 58CV A X 110 20 CN...

Page 28: ...RV 4221A 0 99 1 03 58CV A X 110 20 CNRV 4821A 0 99 0 98 58CV A X 110 20 CSRH 4212A 1 00 1 00 58CV A X 110 20 CSRH 4812A 1 00 0 99 58CV A X 110 20 CAR 4224A 0 98 1 01 58CV A X 135 22 CAR 4824A 0 99 0 9...

Page 29: ...6012A 0 98 0 99 CAR 4817A 0 96 0 99 58CV A X 090 16 CNRH 4821A 0 98 1 02 58CV A X 090 16 CNRH 6024A 0 98 1 02 58CV A X 090 16 CSRH 4812A 0 98 1 01 58CV A X 090 16 CSRH 6012A 0 98 1 00 58CV A X 090 16...

Page 30: ...5 67 83 67 83 5 29 68 80 68 80 5 30 2250 26 22 24 12 4 21 31 81 29 23 4 35 37 85 34 51 4 50 44 65 39 66 4 67 52 37 47 66 4 87 59 78 59 78 5 03 64 71 64 71 5 17 64 66 64 66 5 14 75 1750 24 93 22 93 4 2...

Page 31: ...totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openin...

Page 32: ...W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HCR3C 2PD Replaces 25HCR3C 1PD...

Reviews: