background image

4

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F/12.8

_

C)

REQUIRED FOR LONG LINE

APPLICATIONS*

(Over 80 ft./24.38 m)

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shut---Off TXV

Yes

Yes

Yes

Liquid Line Solenoid Valve

No

No

No

Motor Master

®

or Low---ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

Winter Start Control

Yes

No

No

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMaster

r

Control.

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 5 -- Line Connections

Connect Control Wiring

Route 24--v control wires through control wiring grommet and
connect leads to control wiring (See Fig. 6). Refer to Installation

Instructions packaged with thermostat.

Use No. 18 AWG color--coded, insulated (35

_

C minimum) wire. If

thermostat is located more than 100 ft. (30.48 m) from unit, as

measured along the control voltage wires, use No. 16 AWG
color--coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a

minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to

outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. (24.38 m). Refer to the Application Guideline and Service

Manual

Longline

Section--Residential

Split--System

Air

Conditioners and Heat Pumps.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or
accessories when installing.

Start--Up

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury,

equipment damage or improper operation.

S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Compressor dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader

valves.

24AC

S

Summary of Contents for Comfort 24ACS

Page 1: ... switch Lock out and tag switch with a suitable warning label INSTALLATION INSTRUCTIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 3 Run refrigerant...

Page 2: ...Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves Federal regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improp...

Page 3: ... in liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter drier A05178 Fig 3 Liquid Line Filter Drier Evacuate Refrigerant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damag...

Page 4: ...round connection in control box for safety Connect power wiring to contactor as shown in Fig 5 DISCONNECT PER N E C AND OR LOCAL CODES CONTACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING BLUE 3 PHASE ONLY A94025 Fig 5 Line Connections Connect Control Wiring Route 24 v control wires through control wiring grommet and connect leads to control wiring See Fig 6 Refer to Installation Instructio...

Page 5: ...igerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature i...

Page 6: ... FAN A02326 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION CONTACTOR C A97368 Fig 6 Generic Wiring Diagrams See Thermostat Installation Instruction for specific unit combinations Copyright 2008 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 04 08 Manufacturer reserves the right to change at any time specifications and designs without not...

Reviews: