GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system air conditioner

unit suitable for ground or rooftop installation. Unit consists

of a hermetic compressor, an air--cooled coil, propeller--type

condenser fan, and a control box. Unit will discharge supply

air upward as shown on contract drawings. Unit will be used

in a refrigeration circuit to match up to a packaged fan coil

or coil unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition

of ARI Standard 210.

— Unit will be certified for capacity and efficiency, and

listed in the latest ARI directory.

— Unit construction will comply with latest edition of

ANSI/ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval. Unit

will have c--UL approval.

— Unit cabinet will be capable of withstanding Federal

Test Method Standard No. 141 (Method 6061) 500--hr

salt spray test.

— Air--cooled condenser coils will be leak tested at 150

psig and pressure tested at 450 psig.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is

stored

and

handled

per

unit

manufacturer’s

recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory--assembled,

single--piece,

air--cooled

air

conditioner unit. Contained within the unit enclosure is

all factory wiring, piping, controls, compressor,

refrigerant charge Puron

r

(R--410A), and special

features required prior to field start--up.

Unit Cabinet

— Unit cabinet, including louvered coil guard, will be

constructed of galvanized steel, bonderized, and coated

with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER

24ACA3

1--1/2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated

bearings. Shafts will be corrosion resistant.

— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated

steel wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

— Compressor will be covered with a sound absorbing

blanket.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,

dehydrated, and sealed.

Refrigeration Components

— Refrigeration

circuit

components

will

include

liquid--line shutoff valve with sweat connections,

vapor--line shutoff valve with sweat connections,

system charge of Puron

r

(R--410A) refrigerant, and

compressor oil.

— Unit will be equipped with high--pressure switch, low

pressure switch and filter drier for Puron refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____

Btuh at a suction temperature of _____

_

F. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____

Btuh or greater at conditions of _____ CFM entering air

temperature at the evaporator at _____

_

F wet bulb and

_____

_

F dry bulb, and air entering the unit at _____

_

F.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Nominal unit electrical characteristics will be _____ v,

three phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available

enhancements.

Copyright 2006 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 24ACA3---2PD

Replaces: 24ACA3---1PD

Printed in U.S.A.

edition date: 07/06

24ACA324ACA3

Summary of Contents for Comfort 24ACA3

Page 1: ...w as 74 dBA S Compressor sound blanket Comfort S System supports Thermidistatt Control or standard thermostat Diagnostics S TechAssistt with 6 step diagnostics at a glance Reliability S Puronr refrigerant environmentally sound won t deplete the ozone layer and low lifetime servce cost S Front seating service valves S Scroll compressor S Internal pressure relief valve S Internal thermal overload S ...

Page 2: ...ct Data for system combinations that meet Energy Star guidelines the environmentally sound refrigerant REGISTERED ISO 9001 2000 STANDARD FEATURES Feature 18 24 30 36 42 48 60 Puron Refrigerant X X X X X X X Upt to 15 SEER X X X X X X X Scroll Compressor X X X X X X X Louvered Coil Guard X X X X X X X Field Installed Filter Drier X X X X X X X Front Seating Service Valves X X X X X X X Internal Pre...

Page 3: ...tdoor unit is above indoor unit and 80 ft when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline for required accessories See Long Line Application Guideline for required piping and system modifications Also refer to the table below for the acceptable vapor tube diameters based on the total length to minimize the cooling capacity loss UNIT NOMINAL SIZE BTUH ACCEPTABLE LI...

Page 4: ...X X X X KAALS0201LLS SOLENOID VALVE X X X X X X X X X X X X X X X X KAACS0201PTC START ASSIST PTC X X X X X X X KSASF0101AAA SUPPORT FEET X X X X X X X X X X X X X X X X KAATD0101TDR TIME DELAY RELAY X X X X X X X X X X X X X X X X KSATX0201PUR TXV PURON HSO X X X X KSATX0301PUR TXV PURON HSO X X X X X X KSATX0401PUR TXV PURON HSO X X X KSATX0501PUR TXV PURON HSO X X X KAAWS0101AAA WINTER START X ...

Page 5: ...unts to the base of the compressor to keep the lubricant warm during off cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in Low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Cycle Protector The cycle protector is designed to prevent compressor short cycling This contr...

Page 6: ...ant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter tubes and external equalizer tube Hard shutoff types are available NOTE When using a hard shutoff TXV with single phase reciprocating compressors a Compressor Start Assist Capacitor and Relay is required Usage Guideline Accessory required to meet ARI rating...

Page 7: ...SI NFPA 70 Article 336 26 If other than uncoated no plated 60_ or 75 C 140_ or 167 C insulation copper wire solid wire for 10 AWG or smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Roto...

Page 8: ...8 DIMENSIONS 24ACA3 ...

Page 9: ...R TXV 14 50 11 70 58MVB060 14 CSPH 2412A 16 700 TDR TXV 14 50 11 70 58MVB080 14 CSPH 2412A 16 600 TDR TXV 14 50 11 70 58CV A X 070 12 CSPH 2412A 16 700 TDR TXV 14 50 11 70 58CV A X 090 16 FY4ANF018 17 400 TDR TXV 13 00 11 00 FY4ANF024 17 500 TDR TXV 13 00 11 00 FX4CNF018 17 600 TDR TXV 14 50 11 70 FX4CNF024 17 900 TDR TXV 14 50 11 70 FE4ANF002 17 800 TDR TXV 15 00 12 00 FF1ENP018 17 400 TDR TXV 13...

Page 10: ...0 20 CSPH 3012A 22 000 TDR TXV 14 50 11 70 58MVB100 20 CSPH 3012A 21 800 TDR TXV 14 50 11 70 58MVB120 20 CSPH 3012A 21 800 TDR TXV 14 50 11 70 58CV A X 070 12 CSPH 3012A 22 000 TDR TXV 14 50 11 70 58CV A X 090 16 CSPH 3012A 22 000 TDR TXV 14 50 11 70 58CV A X 110 20 CSPH 3012A 22 000 TDR TXV 14 50 11 70 58CV A X 135 22 CSPH 3012A 22 000 TDR TXV 14 50 11 70 58CV A X 155 22 FY4ANF024 22 600 TDR TXV ...

Page 11: ... 11 00 CSPH 3612A 27 200 TDR TXV 14 00 11 50 58MVB040 14 CSPH 3612A 27 200 TDR TXV 14 00 11 50 58CV A X 070 12 FY4ANF030 27 600 TDR TXV 13 00 11 00 FY4ANF036 27 800 TDR TXV 13 00 11 00 FX4CNF030 28 000 TDR TXV 13 50 11 20 FX4CN B F 036 28 200 TDR TXV 14 00 11 50 FE4ANF002 27 800 TDR TXV 14 00 11 50 FE4ANF003 28 000 TDR TXV 14 50 11 70 FE4ANF005 28 800 TDR TXV 15 00 12 00 FF1ENP030 27 400 TDR TXV 1...

Page 12: ...35 400 TDR TXV 15 00 12 00 FF1ENP036 33 800 TDR TXV 13 00 11 00 FV4BNF002 33 600 TDR TXV 14 00 11 50 FV4BNF003 34 000 TDR TXV 14 50 11 70 FV4BNF005 35 000 TDR TXV 15 00 12 00 FV4BNB006 35 400 TDR TXV 15 00 12 00 42 30 42 50 42 60 CAP 4221A 41 000 TXV 13 00 11 00 CAP 4221A 40 000 TDR TXV 13 50 11 20 58MVB080 14 CAP 4221A 40 500 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 4224A 41 000 TXV 13 00 11 00 CA...

Page 13: ...4824A 46 000 TXV 13 00 11 00 CAP 4824A 45 000 TDR TXV 13 50 11 20 58MVB120 20 CAP 4824A 45 500 TDR TXV 13 50 11 20 58CV A X 135 22 CAP 6021A 47 000 TXV 13 20 11 00 CAP 6021A 46 000 TDR TXV 13 50 11 20 58MVB080 20 CAP 6021A 47 500 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 6024A 47 000 TXV 13 20 11 00 CAP 6024A 46 000 TDR TXV 14 00 11 50 58MVB120 20 CAP 6024A 46 500 TDR TXV 14 00 11 50 58CV A X 135 22...

Page 14: ...11 20 58CV A X 135 22 CNPH 6024A 56 500 TDR TXV 13 50 11 20 58CV A X 155 22 CSPH 6012A 56 500 TXV 13 00 11 00 CSPH 6012A 55 500 TDR TXV 13 20 11 00 58CV A X 110 20 CSPH 6012A 55 500 TDR TXV 13 50 11 20 58CV A X 135 22 CSPH 6012A 55 500 TDR TXV 13 50 11 20 58CV A X 155 22 FX4CN B F 060 58 000 TDR TXV 13 20 11 00 FE4ANB006 57 000 TDR TXV 13 50 11 20 FV4BNB006 57 000 TDR TXV 13 50 11 20 FY4ANB060 56 ...

Page 15: ...7 10 67 1 77 16 88 10 28 1 97 15 65 9 85 2 18 67 19 33 14 90 1 27 18 43 14 54 1 42 17 48 14 15 1 59 16 51 13 77 1 77 15 48 13 35 1 97 14 33 12 89 2 19 62 18 01 17 91 1 28 17 30 17 30 1 43 16 54 16 54 1 59 15 76 15 76 1 77 14 92 14 92 1 97 13 97 13 97 2 19 57 18 01 18 01 1 28 17 30 17 30 1 43 16 55 16 55 1 59 15 76 15 76 1 77 14 92 14 92 1 97 13 97 13 97 2 19 Multipliers for Determining the Perform...

Page 16: ...8 2 35 19 87 19 87 2 62 18 66 18 66 2 92 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capacity Power Furnace Model CAP 2414A 1 00 1 00 CAP 2417A 0 99 0 99 CAP 3014A 1 00 1 00 CAP 3017A 1 00 1 00 CNPF 2418A 0 98 0 98 CNPH 2417A 0 98 0 98 CNPH 3017A 0 99 0 99 CNPV 2414A 0 98 0 98 CNPV 2417A 0 98 0 98 CNPV 3014A 0 99 0 99 CNPV 3017A 0 99 0 99 CSPH 2412A ...

Page 17: ... 83 27 83 2 32 26 66 26 66 2 57 25 40 25 40 2 85 24 06 24 06 3 16 22 61 22 61 3 48 57 28 94 28 94 2 10 27 83 27 83 2 32 26 66 26 66 2 57 25 41 25 41 2 85 24 06 24 06 3 16 22 62 22 62 3 51 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capacity Power Furnace Model CAP 3014A 1 00 1 00 CAP 3017A 1 00 1 00 CAP 3614A 1 00 1 00 CAP 3617A 1 00 1 00 CAP 3621A 1...

Page 18: ...32 45 32 45 3 13 30 95 30 95 3 46 29 31 29 31 3 81 27 50 27 50 4 20 57 35 19 35 19 2 58 33 86 33 86 2 84 32 46 32 46 3 13 30 95 30 95 3 46 29 31 29 31 3 81 27 50 27 50 4 20 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capacity Power Furnace Model CAP 3617A 1 00 1 00 CAP 3614A 0 97 0 97 CAP 3621A 1 00 1 00 CAP 4221A 1 00 1 00 CAP 4224A 1 00 1 00 CNPF 3...

Page 19: ...36 68 31 44 5 13 33 99 30 36 5 65 62 42 55 42 13 3 45 40 89 40 89 3 80 39 17 39 17 4 20 37 34 37 34 4 64 35 37 35 37 5 12 33 16 33 16 5 65 57 42 52 42 52 3 45 40 89 40 89 3 80 39 17 39 17 4 20 37 35 37 35 4 64 35 37 35 37 5 12 33 16 33 16 5 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Model Capacity Power Furnace Model CAP 4221A 1 00 1 00 CAP 4224A 1 00 1 00 CAP...

Page 20: ...21 57 47 87 47 87 3 49 46 01 46 01 3 90 44 04 44 04 4 36 41 95 41 95 4 88 39 69 39 69 5 47 37 13 37 13 6 21 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capacity Power Furnace Model CAP 4821A 1 00 1 00 CAP 4817A 0 99 0 99 CAP 4824A 1 00 1 00 CAP 6021A 1 02 1 02 CAP 6024A 1 02 1 02 CNPF 4818A 0 98 0 98 CNPH 4821A 1 00 1 00 CNPH 6024A 1 02 1 02 CNPV 422...

Page 21: ...0 45 70 6 93 57 59 25 59 25 4 27 56 90 56 90 4 70 54 42 54 42 5 18 51 78 51 78 5 72 48 91 48 91 6 30 45 70 45 70 6 93 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capacity Power Furnace Model CAP 6024A 1 00 1 00 CAP 6021A 0 98 0 98 CNPH 6024A 0 97 0 97 CNPV 6024A 0 99 0 99 CSPH 6012A 0 98 0 98 FE4ANB006 0 99 0 97 FV4BNB006 0 99 0 97 FX4CN B F 060 1 01...

Page 22: ...e statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber vibration isolators Compressor will be covered with a sound absorbing blanket Condenser Coil Condenser coil will be air cooled Coil will be constructed of aluminum fins mechanically bonded to copper...