Wiring the Carrier® ChillerVu™ for power
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
8
All rights reserved
WARNING
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
•
The Carrier® ChillerVu™ is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
•
Carrier controllers can share a power supply as long as you:
•
Maintain the same polarity.
○
Use the power supply only for Carrier controllers.
To wire for power
1
Turn off the Carrier® ChillerVu™'s power switch to prevent it from powering up before you can verify the
correct voltage.
2
Remove primary power from the 24 Vac transformer.
3
Pull the screw terminal connector from the controller's power terminals labeled
Return
and
24 Vac/26 Vdc
.
4
Connect the transformer wires to the screw terminal connector.
5
Apply primary power to the transformer.
6
Measure the voltage at the controller's power screw terminal connector to verify that the voltage is within the
operating range of 21.6 - 26.4 Vac.
7
Insert the screw terminal connector into the controller's power terminals.
8
Turn on the Carrier® ChillerVu™'s power switch.
9
Verify that the Power LED is on and the Run LED is blinking.
Wiring the Carrier® ChillerVu™ for power