background image

7

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is

energized.

Cooling

On a call for cooling, thermostat makes circuits R–O and R–Y, and

R–G. Circuit R–O energizes reversing valve, switching it to

cooling position. Circuit R–Y energizes contactor, starting outdoor
fan motor and compressor circuit. R–G energizes indoor unit

blower relay, starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de–energizing

contactor and blower relay. Compressor and motors should stop.

NOTE

: If indoor unit is equipped with a time–delay relay circuit,

the indoor blower will run an additional 90 seconds to increase
system efficiency.

Heating

On a call for heating, thermostat makes circuits R–Y and R–G.
Circuit R–Y energizes contactor, starting outdoor fan motor and

compressor. Circuit R–G energizes indoor blower relay, starting

blower motor on high speed.
Should temperature continue to fall, R–W2 is made through

second–stage room thermostat. Circuit R–W2 energizes a relay,
bringing on first bank of supplemental electric heat and providing

electrical potential to second heater relay (if used). If outdoor
temperature falls below setting of outdoor thermostat (field

installed option), contacts close to complete circuit and bring on

second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de–energizing

contactor and relay. All heaters and motors should stop.

Defrost

The defrost control is a time/temperature control which includes a
field selectable (quick–connects located at board edge) time period

between defrost cycles (30, 60, or 90 minutes), factory set to either
60 or 90 minutes.

The electronic defrost timer sequence is enabled when the T1 input
on the board is energized. The timer starts only when the defrost

thermostat is closed and the contactor is energized.
Defrost mode is identical to cooling mode except that outdoor fan

motor stops and second–stage heat is turned on to continue

warming conditioned spaces.
To initiate defrost, the defrost thermostat must be closed. This can

be accomplished as follows:

1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control

board (see Fig. 12). Tape lead to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate

on outdoor coil.

4. After a few minutes in heating mode, liquid line temperat-

ure should drop below closing point of defrost thermostat
(approximately 30

°

F/–1.11

°

C).

5. Short between speedup terminals with a flat–blade screw-

driver. This reduces the timing sequence to 1/25th of origin-

al time. (See Table 4.)

6. When you hear reversing valve change position, remove

screwdriver immediately; otherwise, control will terminate

normal 10–minute defrost cycle in approximately 2
seconds.

NOTE

: Length of defrost cycle is dependent upon length of time

it takes to remove screwdriver from test pins after reversing valve
has shifted.

7. Unit will remain in defrost for remainder of defrost cycle

time or until defrost thermostat reopens at approximately
65

°

F (18.33

°

C) coil temperature of liquid line.

8. Turn off power to outdoor unit and reconnect fan motor

lead to OF2 on control board.

OUTDOOR FAN

RELAY

Y OUTPUT TO PRESSURE

SWITCHES AND CONTACTOR

THERMOSTAT INPUTS

T1 - ENABLES DEFROST  
       TIMER.MUST BE  
       ENERGIZED FOR  
       DEFROST TIMER  
       TO START 

C - COMMON

O - REVERSING VALVE

SPEEDUP

HK32EA001

DEFROST  THERMOSTAT

MUST BE CLOSED BEFORE

DEFROST TIMER BEGINS

A05332

Fig. 12 – Defrost Control

Table 4 – Defrost Control Speedup–Timing Sequence

PARAMETER

MINIMUM

(MINUTES)

MAXIMUM

(MINUTES)

SPEEDUP

(NOMINAL)

30–minute cycle

27

33

7 sec

50–minute cycle

45

55

12 sec

90–minute cycle

81

99

21 sec

10–minute cycle

9

11

2 sec

5 minutes

4.5

5.5

1 sec

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: CH14NB---01SI

Replaces: New

Summary of Contents for CH14NB

Page 1: ...in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing or operating refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit ...

Page 2: ...rance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units or 18 in 457 2 mm if no overhang within 12 ft 3 66 m Position so water snow or ice from roof or...

Page 3: ...refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected To Factory Approved Indoor Unit Outdoor unit contains approximate system refrigerant charge for operation with approved AHRI rated indoor unit when connected by 15 ft 4 57 m of field supplied or factory accessory tubing and fa...

Page 4: ...cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR Connection Diameter Tube Diameter Connection Diameter Tube Diameter 18 24 3 8 3 8 5 8 5 8 30 36 3 8 3 8 3 4 3 4 42 48 3 8 3 8 7 8 7 8 60 3 8 3 8 7 8 1 1 8 Units are rated with 25 ft 7 6 m of lineset See Product Data sheet for perfor...

Page 5: ...l power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not install unit in system where voltage may fluctuate above or below permissible limits Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to ...

Page 6: ...se electrical disconnect to outdoor unit A crankcase heater is required if refrigerant tubing is longer than 80 ft 23 4 m or when outdoor unit is 20 ft 6 09 m below indoor unit Refer to the Residential Piping and Long Line Guideline Install Electrical Accessories Refer to the individual instructions packaged with kits or accessories when installing Start Up CAUTION PERSONAL INJURY HAZARD Failure t...

Page 7: ...ntactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on to continue warming conditioned spaces To initiate defrost the defrost thermostat must be closed This can be accomplished as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board see Fig 12 Tape lead to prevent ground...

Page 8: ... 6 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcooling temperature at a specific li quid line pressure add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F Units with Indoor Pistons Units installed with indoor pistons require cha...

Page 9: ...024L CSPH 3012AL CNPV 3621AL CSPH 4212AL 5 CSPH 4212AL CSPH 6012AL 3 FFMANP018 FB4CNF030L CSPH 3012AL FB4CNF036L CSPH 4812AL FB4CNF048L FFMANP019 FB4CNP030L CSPH 3612AL 3 FB4CNF042L 5 FB4CNF042L FB4CNP048L FFMANP024 FFMANP024 FB4CNF030L FB4CNP036L FB4CNF048L FB4CNP060L 3 FFMANP025 FFMANP025 FB4CNF036L FB4CNP042L 5 FB4CNP042L FV4CN B F 005L 3 FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4C...

Page 10: ... 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F outdoor ambient and 80 F dry bulb 67 F wet bulb indoor conditions DOE B Test Conditions Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weighed in Note Sup...

Page 11: ... S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600...

Page 12: ...r reserves the right to change at any time specifications and designs without notice and without obligations Catalog No CH14NB 01SI Replaces New ECAC BDP S 7310 W Morris St S Indianapolis IN 46231 Edition Date 11 14 ...

Reviews: