background image

3

Table 1 – Accessory Usage

Accessory

REQUIRED FOR LOW–AMBIENT

COOLING APPLICATIONS

(Below 55

F / 12.8

C)

REQUIRED FOR

LONG LINE APPLICATIONS*

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

No

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long–Line Application Guideline

No

Motor Master

Control or

Low Ambient Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline. .

{

Additional requirement for Low–Ambient Controller (full modulation feature) MotorMaster

r

Control.

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury

or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal.
Use all service ports and open all flow–control devices,

including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4

mm). vertical rise at service valve. Refrigerant tubing lengths

up to 36–in (914.4 mm). may be buried without further special

consideration. Do not bury lines longer than 36 in (914.4 mm).

Outdoor units may be connected to indoor section using accessory

tubing package or field–supplied refrigerant grade tubing of correct

size and condition. For tubing requirements beyond 80 ft,

substantial capacity and performance losses can occur. Following

the recommendations in the

Residential Piping and Long Line

Guideline

will reduce these losses. Refer to Table 1 for accessory

requirements. Refer to Table 2 for field tubing diameters.
There are no buried–line applications greater than 36 in. (914.4

mm)
If refrigerant tubes or indoor coil are exposed to atmosphere, they

must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

Outdoor Unit Connected To Factory Approved Indoor

Unit

Outdoor unit contains approximate system refrigerant charge for

operation with approved AHRI rated indoor unit when connected

by 15 ft (4.57 m) of field–supplied or factory–accessory tubing,

and factory supplied filter drier.

Some indoor units require

additional subcooling to achieve optimal heating performance.

Using Table 5 – Additional Subcooling Required, check refrigerant

charge for maximum efficiency

Service Valves

Service valves are closed and plugged from the factory. Outdoor

units are shipped with a refrigerant charge sealed in the unit. Leave
the service valves closed until all other refrigerant system work is

complete or the charge will be lost. Leave the plugs in place until
line set tubing is ready to be inserted.
Heat pumps require a piston metering device in the liquid service
valve for proper heating operation. Piston is shipped in the piston

body of the liquid service valve, temporarily held in place with a

plastic cap. Do not remove the plastic cap until line set tubing is
ready to be installed.
Refer to Fig. 4 and follow these steps for piston installation:

1. Remove plastic cap holding piston in piston body of liquid

service valve.

2. Check that piston size (stamped on side of piston) matches

with number listed on unit rating plate. Return piston to
piston body of liquid service valve (either direction).

3. Find plastic bag taped to unit containing copper adapter

tube, brass nut, and plastic washer.

4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube onto liquid

service valve. Tighten nut finger tight, then wrench

additional

½

turn only [15--ft lbs (20.3 N--m)]. Over

tightening may damage the plastic washer and service
valve’s piston body.

PISTON BODY

LIQUID SERVICE VALVE

PISTON

PLASTIC WASHER

ADAPTER TUBE

BRASS NUT

A14235

Fig. 4 – Liquid Service Valve with Heating Piston and

Adapter Tube

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: CH14NB---01SI

Replaces: New

Always Ask For

Summary of Contents for CH14NB

Page 1: ...in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing or operating refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit ...

Page 2: ...rance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units or 18 in 457 2 mm if no overhang within 12 ft 3 66 m Position so water snow or ice from roof or...

Page 3: ...refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected To Factory Approved Indoor Unit Outdoor unit contains approximate system refrigerant charge for operation with approved AHRI rated indoor unit when connected by 15 ft 4 57 m of field supplied or factory accessory tubing and fa...

Page 4: ...cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR Connection Diameter Tube Diameter Connection Diameter Tube Diameter 18 24 3 8 3 8 5 8 5 8 30 36 3 8 3 8 3 4 3 4 42 48 3 8 3 8 7 8 7 8 60 3 8 3 8 7 8 1 1 8 Units are rated with 25 ft 7 6 m of lineset See Product Data sheet for perfor...

Page 5: ...l power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not install unit in system where voltage may fluctuate above or below permissible limits Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to ...

Page 6: ...se electrical disconnect to outdoor unit A crankcase heater is required if refrigerant tubing is longer than 80 ft 23 4 m or when outdoor unit is 20 ft 6 09 m below indoor unit Refer to the Residential Piping and Long Line Guideline Install Electrical Accessories Refer to the individual instructions packaged with kits or accessories when installing Start Up CAUTION PERSONAL INJURY HAZARD Failure t...

Page 7: ...ntactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on to continue warming conditioned spaces To initiate defrost the defrost thermostat must be closed This can be accomplished as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board see Fig 12 Tape lead to prevent ground...

Page 8: ... 6 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcooling temperature at a specific li quid line pressure add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F Units with Indoor Pistons Units installed with indoor pistons require cha...

Page 9: ...024L CSPH 3012AL CNPV 3621AL CSPH 4212AL 5 CSPH 4212AL CSPH 6012AL 3 FFMANP018 FB4CNF030L CSPH 3012AL FB4CNF036L CSPH 4812AL FB4CNF048L FFMANP019 FB4CNP030L CSPH 3612AL 3 FB4CNF042L 5 FB4CNF042L FB4CNP048L FFMANP024 FFMANP024 FB4CNF030L FB4CNP036L FB4CNF048L FB4CNP060L 3 FFMANP025 FFMANP025 FB4CNF036L FB4CNP042L 5 FB4CNP042L FV4CN B F 005L 3 FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4C...

Page 10: ... 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F outdoor ambient and 80 F dry bulb 67 F wet bulb indoor conditions DOE B Test Conditions Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weighed in Note Sup...

Page 11: ... S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600...

Page 12: ...r reserves the right to change at any time specifications and designs without notice and without obligations Catalog No CH14NB 01SI Replaces New ECAC BDP S 7310 W Morris St S Indianapolis IN 46231 Edition Date 11 14 ...

Reviews: