background image

Installation Instructions

CH14NB

SPLIT–SYSTEM HEAT PUMP

WITH R–410A REFRIGERANT

1--1/2 TO 5 TONS

NOTE

: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,

or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property

damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory–authorized kits or accessories

when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes and

current editions of the National Electrical Code (NEC) NFPA 70.

In Canada, refer to current editions of the Canadian electrical code

CSA 22.1.
Recognize safety information. This is the safety–alert symbol

!

!

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and

CAUTION. These words are used with the safety–alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death.

WARNING signifies hazards

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors.

Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

INSTALLATION RECOMMENDATIONS

NOTE

: In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding un-

necessary turns and bends.

4. Leave some slack between structure and unit to absorb vi-

bration.

5. When passing refrigerant tubes through the wall, seal open-

ing with RTV or other pliable silicon–based caulk (see Fig.
1).

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing (see Fig. 1).

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation (see Fig. 1).

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25.4 mm)

 MIN

THROUGH THE WALL

SUSPENSION

A07588

Fig. 1 – Connecting Tubing Installation

When outdoor unit is connected to factory–approved indoor unit,
outdoor unit contains system refrigerant charge for operation with

AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field–supplied or factory accessory tubing. For proper unit

operation, check refrigerant charge using charging information

located on control box cover and/or in the Check Charge section of
this instruction.

IMPORTANT

: Maximum liquid–line size is 3/8–in. OD for all

residential applications including long line.

IMPORTANT

: Always install the factory–supplied liquid–line

filter drier. Obtain replacement filter driers from your distributor or
branch.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: CH14NB---01SI

Replaces: New

Summary of Contents for CH14NB

Page 1: ...in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing or operating refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit ...

Page 2: ...rance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units or 18 in 457 2 mm if no overhang within 12 ft 3 66 m Position so water snow or ice from roof or...

Page 3: ...refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected To Factory Approved Indoor Unit Outdoor unit contains approximate system refrigerant charge for operation with approved AHRI rated indoor unit when connected by 15 ft 4 57 m of field supplied or factory accessory tubing and fa...

Page 4: ...cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR Connection Diameter Tube Diameter Connection Diameter Tube Diameter 18 24 3 8 3 8 5 8 5 8 30 36 3 8 3 8 3 4 3 4 42 48 3 8 3 8 7 8 7 8 60 3 8 3 8 7 8 1 1 8 Units are rated with 25 ft 7 6 m of lineset See Product Data sheet for perfor...

Page 5: ...l power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not install unit in system where voltage may fluctuate above or below permissible limits Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to ...

Page 6: ...se electrical disconnect to outdoor unit A crankcase heater is required if refrigerant tubing is longer than 80 ft 23 4 m or when outdoor unit is 20 ft 6 09 m below indoor unit Refer to the Residential Piping and Long Line Guideline Install Electrical Accessories Refer to the individual instructions packaged with kits or accessories when installing Start Up CAUTION PERSONAL INJURY HAZARD Failure t...

Page 7: ...ntactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on to continue warming conditioned spaces To initiate defrost the defrost thermostat must be closed This can be accomplished as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board see Fig 12 Tape lead to prevent ground...

Page 8: ... 6 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcooling temperature at a specific li quid line pressure add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F Units with Indoor Pistons Units installed with indoor pistons require cha...

Page 9: ...024L CSPH 3012AL CNPV 3621AL CSPH 4212AL 5 CSPH 4212AL CSPH 6012AL 3 FFMANP018 FB4CNF030L CSPH 3012AL FB4CNF036L CSPH 4812AL FB4CNF048L FFMANP019 FB4CNP030L CSPH 3612AL 3 FB4CNF042L 5 FB4CNF042L FB4CNP048L FFMANP024 FFMANP024 FB4CNF030L FB4CNP036L FB4CNF048L FB4CNP060L 3 FFMANP025 FFMANP025 FB4CNF036L FB4CNP042L 5 FB4CNP042L FV4CN B F 005L 3 FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4C...

Page 10: ... 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F outdoor ambient and 80 F dry bulb 67 F wet bulb indoor conditions DOE B Test Conditions Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weighed in Note Sup...

Page 11: ... S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600...

Page 12: ...r reserves the right to change at any time specifications and designs without notice and without obligations Catalog No CH14NB 01SI Replaces New ECAC BDP S 7310 W Morris St S Indianapolis IN 46231 Edition Date 11 14 ...

Reviews: