background image

1

     CONTENTS

Page

51302618918-C   0606

SAFETY CONSIDERATIONS ................................ 1

GENERAL ........................................................... 1-6

INSTALLATION ................................................ 6-13

Indoor Unit Installation ........................................ 6

Outdoor Unit Installation ..................................... 8

Power Supply ....................................................... 9

Leak Test ............................................................... 9

Wiring Diagrams ............................................ 11-12

START-UP ........................................................... 13

System Checks ................................................... 13

CARE AND MAINTENANCE ............................... 13

Outdoor Units ..................................................... 13

Indoor Units ........................................................ 13

To Clean the Indoor Unit Front Panel ............... 13

To Clean Indoor Coil .......................................... 13

Air Filters for Indoor Units ................................ 13

SERVICE ............................................................. 13

TROUBLESHOOTING .................................... 14-17

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equip-

ment can be hazardous due to system pressures, electrical compo-
nents, and equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and service mechanics should

install, start-up, and service this equipment.

Untrained personnel can perform basic maintenance func-

tions such as cleaning coils. All other operations should be per-
formed by trained service personnel.

When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the equip-
ment.

Follow all safety codes. Wear safety glasses and work gloves.

Keep quenching cloth and fire extinguisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment.

Before installing or servicing system, always turn off main power
to system and install lockout tag on disconnect. There may be
more than one disconnect switch. Electrical shock can cause
personal injury.

GENERAL

These instructions cover the installation, start-up and servic-

ing of 38BCC/BCQ outdoor and 40BNC/BNQ indoor units cool-
ing only and heat pump duct free systems. See Table 1 for parts
included. See Tables 2 and 3 for Physical Data.

System Requirements

IMPORTANT: The Indoor units & the inter units cable
voltage is 30 VDC.

IMPORTANT: Each refrigerant line must be insulated
Separately. See line sizing requirements in tabel 2.

 •

Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.

Max. cable length. Total voltage drop should not exceed 1V.
Therefore max. length:

For #18 AWG

24.3 Feet (7.4 m)

For #16 AWG

37.7 Feet (11.5 m)

For #14 AWG

50.0 Feet (18 m)

Use only type "G" or "C" fuses. Use single length power
cable without extension. Allow sufficient space for airflow
clearance on condensing units for wiring, refrigerant piping,
and servicing unit. See Fig. 1 and 2 for minimum required
distances between unit and walls or ceilings.

Indoor and outdoor units should be installed at a
Minimum length of 10 ft. apart.
Maximum line length of 50 ft. and
vertical separation of 30 ft.

Do not install indoor units near a direct source of heat such as
direct sunlight, steam or flame.

Do not bury more than 36 in. of refrigerant pipe in the ground. If
any section of pipe is buried, there must be a 6 in. vertical rise to
the valve connections on the outdoor units. If more than the rec-
ommended length is buried, refrigerant may migrate to the cooler
buried section during extended periods of system shutdown. This
causes refriger-ant slugging and could possibly damage the com-
pressor at start-up.

 WARNING

Pg 1

 CAUTION

 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc.          Printed in Israel

Fig. 1 — 38BCC/BCQ 018, 024 Outdoor Unit Clearances

 Installation, Start-Up and Service Instructions

BCC/BCQ 018, 024

Duct Free Systems

Cooling Model

BCC018

BCC024

Heat Pump

BCQ018

BCQ024

LEFT (min.)
6" (0.15m)

TOP (min.)
2" (0.6m)

REAR (min.)
6" (0.15m)

RIGHT (min.)
2" (0.6m)

FRONT (min.)
2" (0.6m)

R-22

Summary of Contents for BCC018

Page 1: ...al Data System Requirements IMPORTANT The Indoor units the inter units cable voltage is 30 VDC IMPORTANT Each refrigerant line must be insulated Separately See line sizing requirements in tabel 2 Cons...

Page 2: ...IAGRAM Mounting Bracket 2 X 1 Long Screws 2 X 8 Outdoor Sensor Connecting Cable 2 X 1 Available for HEAT PUMP ONLY Absorption Cushions 4 Electric Terminals 2 X 8 2 X Remote Controller 1 Mounting Mount...

Page 3: ...NQ012 COOLING CAPACITY Btuh 2 X 9 000 2 X 11 400 SEER 13 0 13 0 HEATING CAPACITY Btuh 17 200 23 600 HSPF 7 7 7 7 SYSTEM CHARGE Ib 2 X 2 4 2 X 3 1 MOISTURE REMOVAL pt hr 2 X 2 6 2 X 4 5 AIRFLOW 3 Speed...

Page 4: ...nch mm FRONT VIEW RIGHT SIDE VIEW BOTTOM VIEW LEFT SIDE VIEW TOP VIEW A C B 20 06 2006 GAD L EITANC NEW 815 260 185 635 230 40 12 7 6 35 27 50 32 08 10 23 7 28 25 9 06 1 57 1 2 1 4 1 06 1 96 815 260 1...

Page 5: ...R EITANC SUPERSEDES NEW 38BCC BCQ 018 024 101 CONDENSING UNITS REV TOP VIEW AIR DISCHARGE AIR IN VIEW MINIMUM CLEARANCES SEE NOTE 1 MOUTING SLOT FIELD POWER CONNECTION CONTROL CONNECTION UNDER THIS CO...

Page 6: ...four long screws to attach the mounting bracket to the wall 5 Check that the bracket is leveled and securely fastened to the wall DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER UNIT CONNECTIONS To m...

Page 7: ...p the cables back 1 4 inch 2 Remove the unit s front panel by lifting the lower part and pulling it gently outward and upward See Fig 6 3 Remove the two screws from the control box cover and take off...

Page 8: ...all the connections are made Bend tubing with special bending tools to avoid the forma tion of sharp bends Take care to avoid kinks or flattening of the tubing Keep the tubing free of dirt sand moist...

Page 9: ...ns to eliminate contamination and moisture 3 Disconnect the vacuum pump Unit should maintain 500 microns for 5 minutes 4 Remove the service port caps from the mixed phase valve and suction line valve...

Page 10: ...both sections NOTE Specifications and performance data are subject to change without notice Table 5 Electrical Data Outdoor Units 115 1 60 UNIT VOLTAGE MCA MOCP FULL LOAD FAN MOTOR COMPRESSOR COMPRES...

Page 11: ...D O O R U N I T TH2 WH YEL GREEN RED J12 J6 J7 J8 FAN RVS COMP J18 K6 K5 K1 K2 STEPPER MOTOR K8 K9 K7 J11 J14 BLK RED 1 3 12V 12V BLK WH RED GREEN BLDC MOTOR J1 J5 1 3 J3 J4 TH1 TAC 670 control TAC 6...

Page 12: ...YEL 2 3 4 6 5 TB H L T V 1 OR GND BLK I N D O O R U N I T TH2 WH GREEN RED J12 J6 J7 J8 FAN RVS COMP J18 K6 K5 K1 K2 STEPPER MOTOR K8 K9 K7 J11 J14 BLK RED 1 3 12V 12V BLK WH RED GREEN BLDC MOTOR J1 J...

Page 13: ...rt and debris from drain holes in base of unit Fan motors are waterproof WARNING Indoor Units To avoid the possibility of electric shock before performing any cleaning and maintenance operations alway...

Page 14: ...harge Check thermistors TH1 and TH2 for correct resistance Check system pressures 4 Flashes High Pressure Check refrigerant charge Check thermistors TH1 and TH2 for correct resistance Check operating...

Page 15: ...41 0 5 1 8 1 0 10 40 10 80 11 21 42 8 6 1 8 1 0 9 986 10 370 10 76 44 6 7 1 8 1 0 9 595 9 960 10 33 46 4 8 1 8 1 0 9 222 9 569 9 921 48 2 9 1 8 1 0 8 866 9 196 9 530 50 0 10 1 8 1 0 8 526 8 840 9 157...

Page 16: ...2 055 2 137 2 220 123 8 51 2 3 1 3 1 990 2 070 2 151 125 6 52 2 3 1 3 1 928 2 006 2 085 127 4 53 2 3 1 3 1 867 1 943 2 021 129 2 54 2 3 1 3 1 809 1 883 1 959 131 0 55 2 5 1 4 1 753 1 826 1 900 132 8...

Page 17: ...oor fan motor In Heat mode Delayed start for indoor fan motor Normal software delay maximum of 20 sec Clogged air filters Clean filters Lack of refrigerant Ice formation on the evaporator coil Unit mu...

Reviews: