The BACview®6 device
BACview®
CARRIER CORPORATION ©2021
Installation and User Guide
All rights reserved
15
Wiring the BACview®6 device
Rnet wiring specifications
NOTE
Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, unshielded, CMP, plenum rated cable
Conductor
18 AWG
Maximum length
500 feet (152 meters)
Recommended coloring
Jacket: White
Wiring: Black, white, green, red
UL temperature rating
32
–
167°F (0
–
75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
To wire the BACview®6 device
1
Turn off the controller's power.
2
Pull the screw terminal connector from the BAC
view
®
6
device.
3
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)