6 - STANDARD CONTROL OPERATIONS AND OPTIONS
6.17 - Trending
This function enables to visualise the operations of the unit and
monitor a set of selected parameters.
To display trends
1. Go to the Main menu.
2. Select
Trendings
(TRENDING).
3. Select parameters to be displayed and press the
Save
button
in the lower-left part of the screen.
4. Press the
Trending
button
to display the graph showing
trends for the set of selected parameters.
■
Press
to navigate across the timeline or press
to go to the beginning or the end of the selected period.
■
Press the
Zoom in
button
to magnify the view or
the
Zoom out
button
to expand the viewed area.
■
Press the
Refresh
button
to reload data.
NOTE: The 7" touch screen can display 10 points instead of
4 on the graph.
For web interface only:
■
Set the time range (start/end dates and time) at the bottom of
the Trendings Plot screen and press the
Arrow
button
on
the right side to display the graph showing the performance of
the unit within a selected period of time.
6.18 - User quick test
The Quick Test functionality allows users to test and verify if certain
components of the unit behave correctly (only logged-in users can
activate the Quick Test).
To enable Quick Test
1. Navigate to the Main menu.
2. Select
Quick Test 1
(QCK_TST1). The menu can be accessed
when logged in at user access level.
3. Set
Quick test Enable
[QCK_TEST] to “on”.
Quick test Enable [QCK_TEST]
Off/On
On
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
Once the Quick Test functionality is enabled, it is possible to test
parameters such as valves, pumps’ commands, etc. For more
details, please see the Quick Test 1 table description (QCK_TST1
– Quick Test 1) in section
5.1.
6.19 - BACnet (option 149)
The BACnet/IP communication protocol is used by the building
management system or the programmable controllers to
communicate with the SmartVu
TM
control.
NOTE: This option requires the Software Activation Key
(see section 6.21).
6.20 - Modbus (option 149B)
The Modbus communication protocol is used by the building
management system or the programmable controllers to
communicate with the SmartVu
TM
control.
NOTE: This option requires the Software Activation Key
(see section 6.21).