17
INPUTS – Inputs Status (continued)
No. Name
Status
Unit
Displayed text*
Description
13 REM_LOCK open/close
-
Customer Interlock
Customer interlock: When the contact is closed, the unit will be
stopped with no delay (alarm 10014). The switch is provided on the
customer's terminal block of the optional EMM.
14 ICE_SW
open/close
-
Ice Done Storage Switch
Ice done storage switch
15 OCC_OVSW open/close
-
Occupied Override Switch
Occupied override switch
16 LIM_ANAL
-
mA
Limit 4-20mA Signal
4-20 mA signal, capacity limit
17 ELEC_BOX
open/close
-
Electrical Box Interlock
Electrical box interlock
18 leak_v
-
V
Leakage detector 1 val
Refrigerant leakage detection (optional): Leakage detector 1 value
19 leak_2_v
-
V
Leakage detector 2 val
Refrigerant leakage detection (optional): Leakage detector 2 value
20
ElBxF1_s
off/on
-
ElecBoxFan input state
Electrical box fan input state
*Depends on the selected language (English by default).
OUTPUTS – Outputs Status
No. Name
Status
Unit
Displayed text*
Description
1
COMP_A
off/on
-
Compressor A
Compressor A status (circuit A)
2
OIL_SL_A
off/on
-
Oil Solenoid Output A
Oil solenoid output, circuit A
3
SLID_1_A
off/on
-
Slide Valve 1 Output A
Slide valve 1 output, circuit A
4
SLID_2_A
off/on
-
Slide Valve 2 Output A
Slide valve 2 output, circuit A
5
CAPT010A
-
V
Capacity Signal Cir A
0-10V capacity signal, circuit A
6
COMP_B
off/on
-
Compressor B
Compressor B status (circuit B)
7
OIL_SL_B
off/on
-
Oil Solenoid Output B
Oil solenoid output, circuit B
8
SLID_1_B
off/on
-
Slide Valve 1 Output B
Slide valve 1 output, circuit B
9
SLID_2_B
off/on
-
Slide Valve 2 Output B
Slide valve 2 output, circuit B
10 CAPT010B
-
V
Capacity Signal Cir B
0-10V capacity signal, circuit B
11 COMP_C
off/on
-
Compressor C
Not applicable to this unit
12 OIL_SL_C
off/on
-
Oil Solenoid Output C
Not applicable to this unit
13 SLID_1_C
off/on
-
Slide Valve 1 Output C
Not applicable to this unit
14 SLID_2_C
off/on
-
Slide Valve 2 Output C
Not applicable to this unit
15 CAPT010C
-
V
Capacity Signal Cir C
Not applicable to this unit
16 CAPT_010
-
V
Chiller Capacity signal
Chiller capacity signal
17 ALARM
off/on
Alarm Relay Status
Alarm relay status
18 RUNNING
off/on
Running Relay Status
Running relay status
19 ALERT
off/on
Alert Relay State
Alert relay state
20 SHUTDOWN
off/on
Shutdown Indicator State
Shutdown indicator state
21 pos_3wv
0 to 100%
%
Cond 3 Way Valve Pos
Condenser 3-way valve position
22 READY
off/on
-
Ready or Running Status
Unit ready/running status
23
ElBxFan
off/on
-
Electrical Box Fan sw
Electrical box fan status
*Depends on the selected language (English by default).
PUMPSTAT – Pump Status
No. Name
Status
Unit
Displayed text*
Description
1
SET_FLOW
no/yes
-
Cooler Flow Setpoint Out
Cooler flow setpoint output
2
CPUMP_1
off/on
-
Cooler Pump #1 Command
Cooler pump 1 control enabled
3
CPUMP_2
off/on
-
Cooler Pump #2 Command
Cooler pump 2 control enabled
4
ROTCPUMP no/yes
-
Rotate Cooler Pumps ?
Cooler pumps' rotation
5
FLOW_SW
open/close
-
Cooler Flow Switch
Cooler flow switch
6
HPUMP_1
off/on
-
Condenser Pump Cmd1
Condenser pump control enabled
7
HPUMP_2
off/on
-
Condenser Pump Cmd2
Not applicable to this unit
8
ROTHPUMP no/yes
-
Rotate Condenser Pumps ?
Rotate condenser pumps?
9
CONDFLOW
open/close
-
Condenser Flow Status
Condenser flow status
*Depends on the selected language (English by default).