26
4.3 - Physical data 30XBP
30XBP 250 to 800
30XBP
250
300
350
400
450
500
600
700
750
800
Sound levels
Standard unit
Sound power
(1)
dB(A)
99
99
99
99
101
99
101
99
103
103
Sound pressure at 10 m
(2)
dB(A)
67
67
67
67
69
67
68
67
70
70
Unit + option 15
(3)
Sound power
(1)
dB(A)
93
93
94
95
95
95
97
96
97
98
Sound pressure at 10 m
(2)
dB(A)
61
61
62
63
63
63
65
63
64
65
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
87
87
87
90
91
91
93
92
94
94
Sound pressure at 10 m
(2)
dB(A)
55
55
55
58
59
59
60
59
61
61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
-
-
-
-
89
89
91
90
91
92
Sound pressure at 10 m
(2)
dB(A)
-
-
-
-
56
56
57
56
58
58
Dimensions
Standard unit
Length
mm
3604 3604 3604 4798 4798 5992 7186 7186 7186 7186
Width
mm
2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height
mm
2322 2322 2322 2322 2322 2322 2322 2322 2322 2322
Operating weight
(4)
Standard unit
kg
2999 3030 3049 3629 3692 4023 4726 4860 5127 5439
Unit + option 15
(3)
kg
3267 3298 3317 3928 3991 4322 5057 5191 5458 5770
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
39
37
37
52
53
59
60
61
69
69
teqCO
2
55,8
52,9
52,9
74,4
75,8
83,7
85,8
87,2
98,0
98,7
Circuit B
kg
40
38
39
40
40
36
61
64
61
67
teqCO
2
55,1
51,5
52,9
52,2
52,9
46,5
84,4
88,7
82,9
93,0
Oil
Circuit A
l
20,8
20,8
20,8
23,5
23,5
23,5
23,5
23,5
27,6
27,6
Circuit B
l
20,8
20,8
20,8
20,8
20,8
20,8
23,5
23,5
23,5
23,5
(1) In dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS